video corpo

Distribution circuit breakers

Distribution circuit breakers

Distribution circuit breakers

Product catalog summary
Overview of SDV7 Circuit Breaker Family:
The SDV7 distribution circuit breaker family includes several types:
  • SDV7-SE: Non-arc-resistant with stored-energy operator.
  • SDV7-MA: Non-arc-resistant with magnetic-actuator operator.
  • SDV7-SE-AR: Arc-resistant with stored-energy operator.
  • SDV7-MA-AR: Arc-resistant with magnetic-actuator operator.
Enclosure Types:
The SDV7 offers two enclosure types:
  • Standard: Non-arc-resistant.
  • Optional: Arc-resistant, accessibility type 2B, tested to ANSI/IEEE C37.20.7.
Operator Features:
Stored-energy Operator:
  • Based on the type 3AH3 operator, with over 120,000 units produced since 1977.
  • Common operator for all ratings, tested to ANSI/IEEE C37.09.
Magnetic-actuator Operator:
  • Adapted from the 3AH3 configuration, with identical high-voltage compartment.
  • Includes a fast discharge circuit for electronic controller power capacitors.
  • Manual opening handle requires minimal force, with an estimated electronic controller life of 30 years.
Additional Features and Benefits:
  • Optional extended capacitor switching.
  • Tested for out-of-phase switching ratings (ANSI/IEEE C37.09).
  • Large relay and control compartment, stainless steel exterior hardware.
  • Porcelain dry-type bushings with extended creep.
  • Highly reliable vacuum interrupters with MTTF over 53,000 years.
  • Compatible with Siemens protective relays for various applications.
  • Seismic qualification available for Zones 1-4.
  • Meets or exceeds ANSI, IEEE, and NEMA standards, with rain-tested enclosure (ANSI/IEEE C37.20.2).
Technical Ratings:
The document provides detailed technical ratings for various SDV7 circuit breaker types, including rated maximum voltage, withstand voltages, short-circuit current, interrupting time, continuous current, transient recovery voltage, and permissible tripping delay time. Specific ratings are provided for 15.5 kV, 27.6 kV, and 38 kV models.
Dimensions:
Detailed dimensions are provided for different voltage and current ratings, with measurements in inches and millimeters.
Disclaimer:
The technical data is based on actual cases or designed parameters and should not be relied upon for specific applications. Siemens reserves the right to modify technology and product specifications.
See more

Catalog excerpts

Distribution circuit breakers-1

Other features and benefits include: • Extended capacitor switching (optional) • Tested for out-of-phase switching ratings (ANSI/IEEE C37.09) • Large relay and control compartment • Stainless steel exterior hardware • Porcelain dry-type bushings with extended creep • Highly reliable vacuum interrupters -MTTF over 53,000 years Type SDV7 distribution circuit breaker family includes: • Type SDV7-SE: type SDV7 non-arc-resistant with stored-energy operator Stored-energy operator features: • Time-proven type 3AH3 operator derived from operators introduced in 1977 (over 120,000 produced) • Pair with Siemens protective relays to match any typical application • Moderate and high seismic qualification (Zones 1-4) available • Type SDV7-MA: type SDV7 non-arc-resistant with magnetic-actuator operator • Type SDV7-SE-AR: type SDV7-AR arc-resistant with stored-energy operator • Type SDV7-MA-AR: type SDV7-AR arc-resistant with magnetic-actuator operator. Type SDV7 enclosure types offered: • Standard: non-arc-resistant enclosure • Optional: arc-resistant, accessibility type 2B, tested to ANSI/IEEE C37.20.7. • Common operator for all ratings • Design tested to ANSI/IEEE C37.09. Magnetic-actuator operator features: • Design adapted from type 3AH3 stored-energy operator configuration • High-voltage compartment configuration identical to stored energy version • Design tested to ANSI/IEEE C37.09 • Built-in fast discharge circuit for electronic controller power capacitors • Manual opening handle requires very modest force for operation • Electronic controller life estimated at 30 years. • Meets or exceeds the latest ANSI, IEEE and NEMA standards • ANSI/IEEE "rain tested" enclosure (ANSI/IEEE C37.20.2).

 Open the catalog to page 1
Distribution circuit breakers-2

Technical ratings Footnotes: 1 83 ms/five-cycle optional for stored-energy operator. 2 TRV values are in accordance with ANSI/IEEE C37.06-2009 TRV peak value uc roughly equal to historic E2 value in ANSI/IEEE C37.06-2000. Value t3, time to voltage uc is approximately 1/1.138 times T2 value in ANSI/IEEE C37.06-2000. 3. First value is full-wave impulse withstand circuit breaker open or closed. Second value is chopped-wave impulse withstand, applicable only with circuit breaker closed. 4. Magnetic-actuator availability to be announced for these ratings. Consult factory. Front view Published by Siemens...