3AH47 Vacuum Circuit-Breakers for Traction Applications

3AH47 Vacuum Circuit-Breakers for Traction Applications
1 / 42 PagesView full catalog

3AH47 Vacuum Circuit-Breakers for Traction Applications

Product catalog summary
Overview: The document is a technical catalog for Siemens 3AH47 Vacuum Circuit-Breakers, designed for traction applications in railway electrification systems. It includes specifications, operational guidelines, and maintenance instructions for these medium-voltage components.
Specifications: The 3AH47 circuit-breakers are suitable for railway systems operating at 17.5 kV and 27.5 kV, with rated normal currents up to 2500 A and short-circuit breaking currents from 25 kA to 50 kA. They are designed for up to 60,000 operating cycles with minimal maintenance.
Construction and Operation: The circuit-breaker consists of a pole assembly and an operating mechanism box, using vacuum interrupters for arc-quenching and a stored-energy spring mechanism for operation. It includes mechanical and electrical interlocking systems for safe operation.
Standards and Compliance: The 3AH47 circuit-breakers comply with international standards such as EN 50152-1, IEC 62271-100, and IEEE C37.09, meeting endurance classes E2, S1, and C2, and exceeding class M2.
Maintenance and Ambient Conditions: These circuit-breakers are maintenance-free for up to 10,000 cycles under normal conditions and are suitable for various climatic, biological, and mechanical conditions as per IEC 60721 standards.
Product Range and Equipment: The catalog details the product range, including single-pole and two-pole designs for different voltage levels, and basic and alternative equipment options like operating mechanisms, releases, and auxiliary switches.
Technical Data: Detailed technical data includes electrical specifications, dimensions, and circuit diagrams, with guidelines for selecting the appropriate circuit-breaker based on voltage levels and application requirements.
Order Number Structure: The order number for the 3AH47 vacuum circuit-breakers is a 16-digit code covering primary and secondary parts, with special versions indicated by a "-Z" suffix.
Secondary Equipment Selection: The document outlines the selection process for secondary equipment, including operating voltages for components like the closing solenoid and shunt releases, with specific order codes for each configuration.
Configuration Examples: Configuration examples assist in selecting the correct order number for the desired circuit-breaker type, demonstrating how to configure both primary and secondary parts.
Additional Equipment and Accessories: Additional equipment, accessories, and spare parts are available, along with a rating plate and accessories catalog.
Installation and Retrofitting: Instructions for retrofitting releases and solenoids emphasize the need for correct order numbers and trained personnel for replacements.
Procedures: Instructions for configuring the 3AH47 traction circuit-breaker are outlined step-by-step, involving defining primary and secondary equipment features and selecting appropriate release combinations and operating voltages.
Recommendations: Recommendations include specifying the number of poles, type of closing mechanism, and auxiliary contacts, with advice to use the online configuration tool for ease and accuracy.
Key Data from Tables: Tables provide essential data on power consumption and tripping voltage ranges for various releases, including closing solenoids and shunt releases, and list rated voltage and current values for different configurations.
Additional Information: An inquiry form is included for customers to request offers or further assistance from Siemens, along with contact information for Siemens' Customer Support Center.
See more

Catalog excerpts

3AH47 Vacuum Circuit-Breakers for Traction Applications-1

3AH47 Vacuum Circuit-Breakers for Traction Applications Medium-Voltage Equipment

 Open the catalog to page 1
3AH47 Vacuum Circuit-Breakers for Traction Applications-2

3AH47 Vacuum Circuit-Breakers · Siemens HG 11.52 · 2017

 Open the catalog to page 2
3AH47 Vacuum Circuit-Breakers for Traction Applications-3

3AH47 Vacuum Circuit-Breakers Medium-Voltage Equipment Catalog HG 11.52 • 2017 Construction and mode of operation 7 Maintenance, ambient conditions, current carrying capacity and dielectric strength 9 Product range overview and basic equipment 10 Order number structure 12 Selection of basic types, circuit-breakers 13 Selection of secondary equipment 15 Selection of additional equipment 22 Accessories and spare parts 24 Electrical data, dimensions, weights and dimension drawings 28 Operating times, short-circuit protection of motors, consumption data of releases 35 Annex Inquiry form Configuration...

 Open the catalog to page 3
3AH47 Vacuum Circuit-Breakers for Traction Applications-4

3AH47 Vacuum Circuit-Breakers · Siemens HG 11.52 · 2017

 Open the catalog to page 4
3AH47 Vacuum Circuit-Breakers for Traction Applications-5

Description Contents Pole assembly Operating mechanism Trip-free mechanism Circuit-breaker tripping signal Railway control center Switching medium Maintenance, ambient conditions, current carrying capacity, dielectric strength Construction and mode of operation Product range overview and basic equipment 3AH47 Vacuum Circuit-Breakers · Siemens HG 11.52 · 2017

 Open the catalog to page 5
3AH47 Vacuum Circuit-Breakers for Traction Applications-6

Description General 3AH47 circuit-breaker – The Special for railway electrification applications at 17.5 kV and 27.5 kV The electrical power supply for railway systems requires circuit-breakers with special features. Not only are there single-pole circuit-breakers in normal operation, but also the high requirements regarding operational reliability and number of operating cycles reach far beyond the standards of other applications. The vacuum circuit-breaker series 3AH47 offers – both for 16.7 Hz at a rated voltage of 17.5 kV, for 25 Hz at a rated voltage of 25 kV and for 50 / 60 Hz at a rated...

 Open the catalog to page 6
3AH47 Vacuum Circuit-Breakers for Traction Applications-7

Description Construction and mode of operation The 3AH47 vacuum circuit-breaker consists of the pole a ssembly (1) and the operating mechanism box (2). The pole assembly is fixed to the operating mechanism box via post insulators (3). The switching movement is transferred by m eans of operating rods (4) and levers. The vacuum switching technology, proven and fully d eveloped for more than 40 years, serves as arc-quenching principle by using vacuum interrupters. 1 Pole assembly 2 Operating mechanism box 3 Post insulator Switching medium Pole assembly A pole assembly consists of the vacuum interrupter...

 Open the catalog to page 7
3AH47 Vacuum Circuit-Breakers for Traction Applications-8

Description Construction and mode of operation, standards Releases A release is a device which transfers electrical commands from an external source, such as a control room, to the l tching mechanism of the vacuum circuit-breaker so that a it can be opened or closed. How many releases are used and how they are combined is defined when the secondary equipment is selected. Circuit-breaker tripping signal The NO contact makes brief contact while the vacuum c ircuit-breaker is opening, and this is often used to operate a hazard-warning system which, however, is only allowed to respond to automatic...

 Open the catalog to page 8
3AH47 Vacuum Circuit-Breakers for Traction Applications-9

Description Maintenance, ambient conditions, current carrying capacity and dielectric strength Maintenance The 3AH47 vacuum circuit-breakers are maintenance-free up to 10,000 operating cycles under normal ambient conditions according to IEC 62271-1. After that, maintenance is to be effected according to the maintenance schedule, e.g. r elubrication every 10,000 operating cycles, and replacement of the vacuum interrupters every 30,000 operating cycles. Ambient conditions The vacuum circuit-breakers are designed for the normal o perating conditions defined in IEC 62271-100. Current carrying capacity...

 Open the catalog to page 9
3AH47 Vacuum Circuit-Breakers for Traction Applications-10

* Other ratings on request ■ Available design Anti-pumping Available None Circuit-breaker tripping signal Operations counter Available None Interlocking Without Mechanical interlocking 3AH47 Vacuum Circuit-Breakers ■ Siemens HG 11.52 ■ 2017

 Open the catalog to page 10
3AH47 Vacuum Circuit-Breakers for Traction Applications-11

Order number structure 12 Selection of basic types, circuit-breakers Voltage level 17.5 kV; 16.7 Hz, single-pole 13 Voltage level 25 kV; 25 Hz, single-pole Voltage level 25 kV; 25 Hz, two-pole 13 Voltage level 27.5 kV; 50/60 Hz, single-pole Voltage level 27.5 kV; 50/60 Hz, two-pole 14 Selection of secondary equipment Release combination 15 Operating voltage, closing solenoid 15 Operating voltage, 1st shunt release 16 Operating voltage, 2nd release 17 Operating voltage, 3rd release 18 Operating voltage of the drive motor 19 Auxiliary switch, low-voltage interface, interlocking 20 Selection of...

 Open the catalog to page 11
3AH47 Vacuum Circuit-Breakers for Traction Applications-12

Equipment Selection Order number structure and configuration example Order number structure Special versions («) The 3AH47 vacuum circuit-breakers consist of a primary and a secondary part. The relevant data make up the 16-digit order number. The primary part covers the main electrical data of the circuit-breaker poles. The secondary part covers the auxiliary devices which are necessary for operating and controlling the vacuum circuit-breaker. In case of special versions, “- Z” is added to the order number and a descriptive order code follows. If several special versions are required, the suffix...

 Open the catalog to page 12
3AH47 Vacuum Circuit-Breakers for Traction Applications-13

17.5 kV 16.7 Hz, single-pole, 60,000 operating cycles 1) 10,000 operating cycles 2) 20,000 operating cycles 25 kV 25 Hz, single-pole, 60,000 operating cycles 25 Hz, two-pole, 60,000 operating cycles 3) Other ratings on request Configuration example 3AH47 vacuum circuit-breaker, single-pole Rated voltage r = 17.5 kV, 16.7 Hz Rated lightning impulse withstand voltage p = 125 kV Rated short-circuit breaking current Isc = 40 kA Rated normal current Ir = 2500 A Example for Order No.: |3AH4756-6 ■■■■ - ■■■■ Order codes: 3AH47 Vacuum Circuit-Breakers ■ Siemens HG 11.52 ■ 2017

 Open the catalog to page 13
3AH47 Vacuum Circuit-Breakers for Traction Applications-14

Selection of basic types, circuit-breakers 27.5 kV 50/60 Hz, single-pole, 60,000 operating cycles Order codes 1) 20,000 operating cycles 27.5 kV 50/60 Hz, two-pole, 60,000 operating cycles Configuration example 3AH47 vacuum circuit-breaker, single-pole (r = 17.5 kV, 16.7 Hz, p = 125 kV, ISC = 40 kA, Ir = 2500 A) 5 6-6 Example for Order No.: |3AH4756-6 ■■■■ - ■■■■ Order codes: 3AH47 Vacuum Circuit-Breakers ■ Siemens HG 11.52 ■ 2017

 Open the catalog to page 14