Totally Integrated Power – SIVACON 8PS For safe power flows SIVACON 8PS busbar trunking systems
Open the catalog to page 1Contents SIVACON 8PS busbar trunking systems Communication-capable busbar trunking systems Application examples Technical data Advantages of busbars in comparison to cables Any questions? One click – well-informed Totally Integrated Power (TIP) – We bring power to the point. Our products, systems, and solutions for low- and medium-voltage make power distribution efficient, reliable, and safe – in cities, infrastructure, buildings, and industrial plants. They can be linked to industrial and building automation, and are rounded out by comprehensive support throughout the entire lifecycle. As part...
Open the catalog to page 2The consistent SIVACON 8PS busbar trunking systems from 40 A to 6300 A offer flexible options for all low-voltage power distribution requirements. This applies to power transmission, for application between transformer, primary distribution system and the sub-distriibution systems as well as in power distribution to the end consumer. SIVACON 8PS - the advantages at a glance Living up to complex requirements at all times A total of five different busbar trunking systems offer everything required for modern power transmission and distribution matched to your individual requirements. With the SIVACON...
Open the catalog to page 3Power distribution with communication capabilities for small consumers in workshops and lighting systems Power transmission and distribution with communication capabilities in office buildings and transfer lines in all industrial application areas
Open the catalog to page 4Power distribution and transmission with communication capabilities in wind turbines, exhibition halls, in the automotive industry, heavy industry, and on ships Power distribution and transmission of high currents with communication capabilities in large buildings, data centres as well as in industrial applications such as chip and semiconductor industry or chemicals Transmission of large power volumes in harsh ambient conditions, for the supply of tunnels or networking of building sections, and for power transmission in the chemical industry
Open the catalog to page 5Finger-safe connection through guaranteed opening and shutting of the tap-off point Easy configuration and handling through connection flanges with built-in expansion compensation Reliable protection in case of fire due to tested fire barrier Safe, demand-oriented power supply The BD01 system is designed for applications from 40 A to 160 A. It is employed in trade and industry enterprises to safely supply small consumers with power or realise the infeed of a lighting system. Planning is especially simple and it ensures a flexible power supply. In addition to the pre-wired tap-off units, which...
Open the catalog to page 601 Busbar trunking unit os Ancillary equipment unit 06 Suspension bracket In addition to tap-off and feeding units, ancillary equipment units provide space for additional installations. The BD01 busbar trunking system is available The infeed can be fitted to any connection point. up to 160 A in one size with five current Technical data
Open the catalog to page 7Flexibility thanks to two sizes with seven current ratings up to 1250 A, in aluminium or copper Protection against unauthorised access by sealable tap-off points 3D junction unit up to 800 A allows flexible adjustment to all building structures Safe operation and reliable fire protection The BD2 system is particularly suited for applications from 160 A to 1250 A with increased safety requirements. The tested fire barrier and functional endurance in case of fire ensure a high degree of safety – and thus represent an optimum solution for large buildings, industrial applications, as well as for...
Open the catalog to page 804 Tap-off unit os Accessories Components for change of direction facilitate The communication capable BD2 system with load value Individually equipped tap-off units up to an optimum adjustability to the building detection, remote monitoring and switching increases 530 A rated current can be displaced while structures. transparency of operation. energised^. Technical data 1) In acc. with EN 50110-1 (VDE 0105-1); please always observe national regulations/standards
Open the catalog to page 9Reliable and easy planning due to type-tested connection to SIVACON switchboards and transformers Adequate protection against water (sprinkler-suitable) High availability through tap-off units with circuitbreakers up to 1250 A Cost-efficient infrastructure due to compact design High degree of safety due to tap-off units resistant to arc faults The high power requirement of production lines is provided decentrally with the LD system. The communication capability of the LD system allows operating transparency for recording consumption, and for remote switching and monitoring. Reliable power transmission...
Open the catalog to page 10os Flanged end unit 06 Accessories for mounting The LD system is characterised by a robust and compact design with only two sizes for 1100 A to 5000 A. Current is supplied from the transformer to Components for change of direction allow the LD busbar trunking system via feeding units. the power supply to be adapted to building Technical data
Open the catalog to page 11Safe operation as design verified in accordance with current standard IEC 61439-1 / -6 High degree of protection IP55 Fire barriers tested in accordance with European Standard EN 1366-3 Integrated, efficient and future-proof solution due to integration of measuring devices in energy management solutions in accordance with ISO 50001 Cost-efficient infrastructure through compact sandwich design Reliable installation through hook and bolt connection Reliable in operation. Secure your system availability The LI system is particularly suited for applications from 800 A to 6300 A in which large amounts...
Open the catalog to page 12Transformer feeding unit Fire barrier Feeding unit to SIVACON S8 Straight trunking unit Junction unit Tap-off unit Thanks to its sandwich design, the LI system is characterised by low voltage drop when transmitting high currents. Optimum adaptation to building structures is no problem thanks to the various components of the busbar trunking system. For safe power transmission, a multitude of transformer connections are available. Rated insulation voltage Ui Fire load Rated operational voltage Ue Fire load (per tap-off point) Tap-off point Tap-off unit or junction box Rated peak withstand current...
Open the catalog to page 13676 Pages