Fire control panels (1 loop or 2 loops) for addressable peripheral devices with integrated operating unit • FC361-xx: One loop or two stubs with 126 addresses • FC362-xx: Two loops or four stubs with 252 addresses • Two collective horn lines • Three freely programmable relay outputs • Four freely programmable control inputs/outputs • Optional RS232 module for printer connection • Optional RS485 module for ESPA pager module or DMS • Optional module with four freely configurable monitored outputs • Integrated web-server-based 'FC360 Panel Configurator' software, access via Ethernet connection (port) • Installation space for optional components: - Key switch (standard) or key switch (Nordic) • Emergency power supply for emergency operating time of up to 72 hours Smart Infrastructure
Open the catalog to page 1FC360 is a compact fire control panel with an integrated operating unit. It is possible to use loop as well as stub topology. FC361-xx supports 126 addressable devices over one loop, while FC362-xx supports 252 addressable devices over two loops (max. 126 devices per loop). Automatic fire detectors, alarm devices, input/output modules and a manual call point of the ‘Cerberus™ FIT' peripherals portfolio can be connected to the detector line. Additionally, other 'Cerberus PRO' devices are compatible with the detector line. Smart Infrastructure
Open the catalog to page 2• The 'FC360 Panel Configurator' software is used to configure the fire control panel. All customer texts as well as individual devices and output controllers can be adapted with the 'FC360 Panel Configurator' software. • Monitoring of the detector line for short-circuit and open line: - Precise identification of the error location is possible. - None of the devices on the detector line are lost in the event of a short-circuit on the loop. • Up to 2000 events can be called up according to various criteria. • Changeover to summer time and winter time is automatic. • Individual customer text per...
Open the catalog to page 3Display and operating unit The following components are located on the operating unit: • The electronic components for the operating unit - Key switch (standard or Nordic) Smart Infrastructure
Open the catalog to page 4Smart Infrastructure
Open the catalog to page 5The following components are located on the mainboard: • The connection terminals for the C-NET detector line • Two monitored collective horn lines • Three freely configurable relays (remote transmission - fire - fault, fire control) • Four freely programmable control inputs/outputs • Output module (4M) equipped with 4 monitored freely configurable outputs for sounder line, fire control, and transmission path for alarm or fault • The power supply feeds the hardware and charges the batteries. Emergency power supply • In the event of a power cut, the batteries provide emergency current for up to...
Open the catalog to page 6Smart Infrastructure
Open the catalog to page 71 Supports connection with one loop or two stubs with 126 devices. 2 Supports connection with two loops or four stubs with 252 devices. 3 Not in conjunction with the evacuation module (NL) 4 Either LED indicator (32 zones) or evacuation module (NL): The LED indicator (32 zones) and the evacuation module (NL) cannot be installed simultaneously. 5 Either RS232 module or RS485 module. Fire control panels FC361-xx (1 loop) Smart Infrastructure
Open the catalog to page 8Battery: Max. 2x 12 V, 12 Ah Without integrated LED indicator for 32 zones Battery: Max. 2x 12 V, 25 Ah Without integrated LED indicator for 32 zones
Open the catalog to page 9Smart Infrastructure
Open the catalog to page 10Spare parts Product documentation Smart Infrastructure
Open the catalog to page 11Smart Infrastructure
Open the catalog to page 12Technical data General data Smart Infrastructure
Open the catalog to page 13Smart Infrastructure Performance data Ambient conditions and protection category
Open the catalog to page 14Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID © Siemens 2021 Technical specifications and availability subject to change without notice.
Open the catalog to page 1624 Pages
4 Pages
2 Pages
22 Pages
20 Pages
22 Pages
6 Pages
340 Pages
10 Pages
22 Pages
16 Pages
6 Pages
6 Pages