FC1002, FC1004 Control units-1

• Compatible with all conventional Siemens detectors • 2 selectable detector line standards for a wide range of detector compatibility • 2 monitored control lines for sirens, strobe lights etc. • Programmable alarm organization for manned/unmanned operation • Alarm verification • Suitable to collect non-fire related events with non-latching zone option • Simple user controls with isolate/test button per zone • Key code user access with optional key switch alternative • Easy on-site configuration • Integral capacity for emergency power of up to 72 h Fire & Security Products Siemens Building Technologies

 Open the catalog to page 1
FC1002, FC1004 Control units-2

System overview Detector line AlgoRex DS110x Detector line Synova 600 (non-current limited) Monitored control lines for - horns, sirens - beacons Detector line Synova 300 (current limited) Fire controls - internal relays Detector line Synova 300 with line continuity according to BS 5839 Pt1 FC10 Remote transmission - internal contact Call point line Mixed line (detector/call point with differentiation) EX-area Intrinsically safe detectors SB3 Linear smoke detector or flame detector Series MS6/7/9 Non-fire alarm (technical alarm) EOL Detector line termination with two different types, depending...

 Open the catalog to page 2
FC1002, FC1004 Control units-3

Simple “out of the box” start up with preset default values Country variants FC1002/04-B For British Standard (BS) market. Incorporates special detection circuit end-of-line monitoring which on removal of a detector will indicate a fault on the control unit but still allow devices fitted beyond the removed detector to function. Each detector base must be fitted with a continuity diode. FC1002/04-C For Nordic Countries. This unit comes fitted as standard with a Nordic fire authority key switch. FC1004-E For Dutch Market. Incorporates additional evacuation control line and integral evacuation function....

 Open the catalog to page 3
FC1002, FC1004 Control units-4

Technical Data Supply voltage Power consumption Quiescent current FC1002-A/-B/-C FC1004-A/-B/-C/-E Emergency power operating Outputs Dry contact Alarm Dry contact Fault Fire control relays (optional, 1…2) monitored control lines (2) Driver outputs (5 or 7) Control inputs (3) Operating temperature Storage temperature Humidity (no condensation permitted) at T = 25 ±3 °C at T = 40 ±2 °C Cabinet Dimensions (W x H x D) Color cover FC10xx-A/-B/-C/-E Protection category (IEC 60529) Standards AC 115/230 V, +10 %/–15 %, 50/60 Hz 13 ... 25 VA 80 mA 90 mA … 72 h 30 V/1 A, NO/NC 30 V/1 A, NO/NC 250 V/10...