Cerberus® PROA Comprehensive Fire-Protection System Architect & Engineer Specifications__ Standard 50-point, 252-point and 504-point fire systems Remote viewing for the 252-point and 504-point systems One (1) or (2) two-height-unit enclosures Powerful, but user-friendly system interface Softkey buttons RS—485 interface Four-way navigation menu with extended-views capability Primary, regulated power Universal AC power input: Fully field programmable, via a Windows®-laptop PC Built-in strobe synchronization protocol Global annunciation and control capability Several relay commands: ■ Alarm, Trouble, Supervisory, etc. Light-emitting diodes (LEDs) for: ■ Power, Alarm, Supervisory, Silenced, Ground Fault, Trouble, and system-status LEDs - Alarm command has a larger, distinctive LED LED-option provides LED annunciation of system activity Backlit liquid-crystal display (LCD) SureWire™ addressable-loop technology - Patented polarity-insensitive detection circuits Intelligent / analog detection circuits: 'Class A' or 'Class B' Supports FirePrint™ detection applications Supports single-person, 'Walk Test' Sprinkler Supervision End-user 'Help' screens Multiple command stations Supports pre-action, deluge and Sinorix®-agent releasing for 252 / 504-point systems - Releasing-valve monitoring 10,000 event history / event log Detector Sensitivity Readout / Printout per NFPA 72 ISOtechnology device compatibility including PAD-5 addressable NAC power supply Network up to 32 panels using SafeDLink / CV Web Cerberus® DMS Danger Management Station can monitor, control up to 16 Model FC922, FC924 FACPs □ Supervised remote printer, via the Remote Peripheral Module for the 252 / 504-point systems □ Menu-driven operator commands □ 10,000-event history-logging capability with on-line and off-line reports - Off-line reports can be viewed the custom-configuration programming tool - EEPROM software compatible □ Multiple levels of password protection □ Automatic environmental compensation for smoke detectors □ Alarm verification (by device or zone) □ Logic-controlled output functions □ Optional city-tie / leased-line module □ Gas Alarm events for CO detection, per NFPA 720 for the 252 / 504-point systems □ Optional notification-appliance-circuit (NAC) expansion module ■ Up to 3.0 amps (24VDC) load per output ■ Module used for 252/ 504-point systems ■ UUKL Listing for smoke control □ FM (#3010), CSFM (#7165-0067:0259) and FDNY (#6104) Approved □ Supports built-in TCP/IP Connectivity Cerberus PRO System Overview Cerberus PRO, a comprehensive fire-protection system from Siemens - Fire Safety, is a technologically advanced f ire-and-life-safety system. Each Cerberus PRO system provides easy operation via its push-button soft keys; a backlit LCD screen, and a (4) four-way navigation push button — all located in the upper portion of each panel. Through the use of its unique multiprocessor 'Network' design - along with its ability to utilize intelligent detection devices - Cerberus PRO epitomizes a flexible and highly configurable fire system.

 Open the catalog to page 1
Cerberus PRO Comprehensive Fire Protection System, Data Sheet-2

Cerberus PRO System Overview (cont.) 252 / 504-point System Components (cont.) addressable-loop technology is supported by Cerberus PRO. Cerberus PRO is ideally suited for small and mid-market applications by providing 50, 252 and 504-point addressable fire-alarm-control-panel (FACP). The 252 and 504-point systems are networkable. In conjunction with these new, improved FACPs is a stateof-the-art line of intelligent detectors. For example, the Multi-Criteria Fire / CO Detector [with ASAtechnologyTM] is cutting-edge technology for specialized applications ─ such as carbon-monoxide detection ─...

 Open the catalog to page 2
Cerberus PRO Comprehensive Fire Protection System, Data Sheet-3

252 / 504-point System Components Fire Terminal (and equipment) The Fire Terminal (Model FT924) consists of the Fire Terminal Board (Model FTI2001-U1); the Operating Unit (Model FCM2018-U3 or Model FCM2019-U3), and a oneheight-unit (1HU) system enclosure. Each Model FT924 terminal contains one (1) backlit, 2” ─x─ 4-3/4” Video Graphics Array (VGA) monochrome LCD screen with LEDs for displaying system status. An audible will sound when there are ‘unacknowledged’ events on the system. The display of each operating unit categorizes events by type, providing a separate event tab for Alarm, Gas Alarm,...

 Open the catalog to page 3
Cerberus PRO Comprehensive Fire Protection System, Data Sheet-4

252 / 504-point System Components Power Supply Modules (cont.) Releasing Module (cont.) The 170-Watt power supply incorporates a 4.0A, nonresettable slow-blow fuse on the primary input, and includes a built-in AC-line filter for surge and noise suppression. Model FP2011-U1 mounts in a standard Cerberus PRO-brand enclosure, and there are no serviceable parts to be maintained. The 300-Watt power supply incorporates two (2) 6.3A replaceable, non-resettable slow-blow fuses on the primary input and includes a built-in AC-line filter for surge and noise suppression. Model FP2012-U1 mounts in a Cerberus...

 Open the catalog to page 4
Cerberus PRO Comprehensive Fire Protection System, Data Sheet-5

252 / 504-point System Components Remote Display Terminals (with RS─485 interface) Leased-Line / City-Tie Module (Cont.) The Remote Display Terminals (Models FT2014-U3 / R3 and FT2015-U3 / R3) are LED / LCD units that show the existing status of a Cerberus PRO 252 / 504-point system. A Remote Annunciator (Model FSD901-U3 / R3) is used for the Cerberus PRO 50-point FACP (Model FC901). A LED will illuminate for any given Alarm, Supervisory and Trouble Cerberus PRO-system event. An LCD screen will give details of the event in alphanumeric form. The display screen can be scrolled to reveal additional...

 Open the catalog to page 5
Cerberus PRO Comprehensive Fire Protection System, Data Sheet-6

252 / 504-point System Components Inner Doors One-Height-Unit Enclosure For each Cerberus PRO panel, one (1) red or black back box supports one (1) red or black outer door, respectively. The inner door, which is available in black, specifically stores the system operating units (Models FCM2018-U3 and FCM2019-U3). The back box supports the fire-terminal board (Model FTI2001-U1), and optionally supports the DACT (Model FCA2015-U1). The one-height-unit enclosure is the smaller housing used on Cerberus PRO panels. The following components comprise a complete one-height-unit enclosure:  One (1) inner...