SIPROTEC 7SA82

SIPROTEC 7SA82

SIPROTEC 7SA82

Product catalog summary
Description
The SIPROTEC 7SA82 is a distance protection relay designed for cost-effective and compact protection of medium and high-voltage lines. It offers solutions for protection, control, automation, monitoring, and basic power quality management using the DIGSI 5 engineering tool.

Main Function
The primary function is distance protection for medium and high voltage applications, with interoperability between SIPROTEC 4 and 5 devices. It features a 3-pole tripping mechanism with a minimum tripping time of 19 ms.

Inputs and Outputs
The device supports 4 current transformers, 4 voltage transformers, and offers configurations of 11 or 23 binary inputs and 9 or 16 binary outputs.

Hardware Flexibility
Different hardware configurations are available, but expansion modules cannot be added. It comes with either a large or small display.

Applications
  • Detection and selective tripping of short circuits in various network configurations.
  • Ground fault detection in isolated or arc-suppression-coil-ground systems.
  • Serial protection communication over various media.
  • Backup protection for differential protection devices.
  • Phasor Measurement Unit (PMU) and power-quality data recording.

Functions
  • Configurable functions via DIGSI 5, including multiple distance-protection methods and ground fault detection.
  • Adaptive power-swing blocking and arc protection.
  • Automatic frequency relief and power protection options.
  • Graphical logic editor for automation functions.
  • Communication via Ethernet and optional modules supporting various protocols.
  • Cybersecurity features like role-based access control and secure web access.

Benefits
  • Compact, low-cost, and reliable protection.
  • High availability and cybersecurity compliance.
  • Compatibility with IEC 61850 standards.
  • Future-oriented solutions ensuring high investment security and low operating costs.
See more

Catalog excerpts

SIPROTEC 7SA82-1

Description The SIPROTEC 7SA82 distance protection has been designed particularly for the cost-optimized and compact protection of lines in medium-voltage and high-voltage systems. With its flexibility and the high-performance DIGSI 5 engineering tool, the SIPROTEC 7SA82 device offers future-oriented solutions for protection, control, automation, monitoring, and Power Quality - Basic. Main function Distance protection for medium-voltage and high voltage applications Interoperability of SIPROTEC 4 and SIPROTEC 5 line protection devices Tripping 3-pole, minimum tripping time: 19 ms Inputs and out- 4 current transformers, 4 voltage trans-puts formers, 11 or 23 binary inputs, 9 or 16 binary outputs Hardware flexibi- Different hardware quantity structures lity for binary inputs and outputs are availa ble in the 1/3 base module. Adding 1/6 expansion modules is not possible; available with large or small display. Applications • Detection and selective 3-pole tripping of short circuits in electrical equipment of star networks, lines with infeed at one or 2 ends, parallel lines, and open-circuited or closed ring systems of all voltage levels • Detection of ground faults in isolated or arc-suppres-sion-coilground systems in star, ring, or meshed arrangement • Serial protection communication with SIPROTEC 5 and SIPROTEC 4 devices over different distances and physical media, such as optical fiber, two-wire connections, and communication networks • Backup protection for differential protection devices of all kind for lines, transformers, generators, motors, and busbars • Phasor Measurement Unit (PMU) • Detection and recording of power-quality data in the mediumvoltage and subordinate low-voltage power system Functions DIGSI 5 permits all functions to be configured and combined as required. • inimum tripping time: 19 ms • 6 independent measuring loops (6-system distance protection) • Several distance-protection functions can be selected: Classic, reactance method (RMD), impedance protection for transformers • Directional backup protection and various additional functions • Detection of ground faults of any type in compensated or isolated electrical power systems using the following functions: 3I0>, V0>, transient ground fault, cos 0, sin 0, dir. detection of intermittent ground faults, harmonic detection, and admittance measurement • Ground-fault detection using the pulse-detection method • Adaptive power-swing blocking

 Open the catalog to page 1
SIPROTEC 7SA82-2

Detection of current-transformer saturation for fast tripping with high accuracy Fault locator Plus for accurate fault location with inho-mogenous line sections and targeted automatic overhead line section reclosing (AREC) Arc protection Automatic frequency relief for underfrequency load shedding, taking changed infeed conditions due to decentralized power generation into consideration Power protection, configurable as active or reactive-power protection Directional reactive-power undervoltage protection (QU protection) Detection of current and voltage signals up to the 50th harmonic with high...