Device Description
The SICAM P850 is a multifunctional power meter designed for the acquisition, visualization, evaluation, and transmission of electrical measured variables such as voltage, current, frequency, power, and harmonics. It adheres to the IEC 61000-4-30 power quality measurement standard, ensuring accurate processing and evaluation of measured values and events. Data can be transmitted to a PC or SCADA system or displayed directly on the device.

Benefits
  • Comprehensive acquisition and analysis for early detection of power quality issues.
  • High investment security through standard compliance.
  • Improved availability and open connectivity.

Applications
The device is used in power systems and industrial plants for measuring and analyzing electrical parameters.

Features
  • PQ measurement compliant with IEC 61000-4-30.
  • Harmonics measurement according to IEC 61000-4-7.
  • Energy management and power monitoring capabilities.
  • Standard communication protocols and data export formats.

Device Characteristics
  • True RMS values of voltage and current with a sampling rate of 10.24 kHz at 50 Hz.
  • Measures voltage, current, frequency, and harmonics up to the 40th harmonic.
  • Includes power factor, unbalance, and THD of voltage and current.
  • Compliant with IEC 61000-4-30 and IEC 61000-4-7 for power quality and harmonics.
  • Active, reactive, and apparent power and energy management with accuracy class 0.5S for active power.

Communication Protocols
  • Ethernet: IEC 61850, Modbus TCP, SNMP.
  • Serial: Modbus RTU master and IEC 60870-5-103.

Data Export
  • CSV data for PQ recordings and measured-value recorder.
  • COMTRADE format for fault records.

Input Measuring Circuits
  • 4 x alternating voltage, VL-N/VL-L: AC 400 V/690 V.
  • 3 x alternating current, IN: 1 A/5 A.

Binary Inputs/Outputs
  • 2 digital outputs.

Operation and Display
  • Graphic display with operation via 4 function keys.
  • Integrated Web server for PC interaction and HTML page display.

Time Synchronization
  • Via Ethernet: NTP client (Network Time Protocol).

Auxiliary Voltage
  • AC 110 V to 230 V, DC 24 V to 250 V.

Housing Specification
  • Dimensions: 96 mm x 96 mm x 100 mm (WxHxD).
  • IP51 protection.
See more

Catalog excerpts

SICAM P850 Multifunctional power meter for acquisition, visualization, evaluation, and transmission in one device-1

Device Description The SICAM P850 multifunctional power meter is used for acquisition, visualization, evaluation, and transmission of electrical measured variables such as magnitudes of voltage and current, frequency, power, harmonics. The acquisition, processing, and accuracy of measured values and events are performed acc. to the IEC 61000-4-30 power quality measurement standard. The measured values can be forwarded to a personal computer or power automation/SCADA system via communication interfaces or shown on a display. Measured values can be recorded in parameterizable time intervals with various recorders such as fault recorders. Events are evaluated directly via the Web browser in the device and can be displayed as a report. Benefits • Comprehensive acquisition and analysis of electrical measurands for early detection of power quality issue. • High level of investment security through the use of standards • Improved availability • Open and transparent connectivity and interoperabil Applications SICAM P850 is used in power systems and industrial plants to measure and analyze electrical measurands. Features • PQ measurement according to IEC 61000-4-30 • Harmonics acc. to IEC 61000-4-7 • Energy management and power monitoring functionality • Standard communication protocols and data export formats

 Open the catalog to page 1
SICAM P850 Multifunctional power meter for acquisition, visualization, evaluation, and transmission in one device-2

Device Characteristics Measured Characteristics • True RMS values of voltage and current with 2048 sampled values/10 sampling cycles (sampling rate 10.24 kHz @50 Hz) • Voltage, current, frequency, min/max/average values • Harmonics up to the 40th harmonic • Power factor • Unbalance • THD of voltage and current • Limit violations and indications Power Quality Features • Measurement compliant with IEC 61000-4-30 • IEC 61000-4-7 Harmonics Energy Management • Active, reactive, and apparent power and energy • Accuracy class active power 0.5S according to IEC 62053-22 • Accuracy class voltage/current...