1. Catalogs
  2. SIEMENS Energy automation and smart grid
  3. Catalog Reyrolle 7XG222 · Edition 1

Catalog Reyrolle 7XG222 · Edition 1

Catalog Reyrolle 7XG222 · Edition 1
1 / 16 PagesView full catalog

Catalog Reyrolle 7XG222 · Edition 1

Product catalog summary
Description: The Reyrolle 7XG222 Test Block range is designed for monitoring and secondary injection testing of power system protection schemes. It features test blocks and plugs coded for specific configurations to ensure correct usage and prevent incorrect insertion.
Devices and Application: The series includes the 2RMLG Test Block and 2RLMB-R Test Plug. These test blocks have 14 pairs of spring-loaded contacts linked to a terminal block, with models coded for specific test plugs to ensure compatibility and safety.
Hardware Construction: The 2RMLG is a size E2 unit with a rear terminal block featuring 28 terminals for external wiring. The 2RMLB-R series test plugs are securely retained and include multiple test sockets for connection.
Technical Documentation: Connection diagrams and dimension drawings are provided for various configurations, illustrating typical applications and installation requirements.
Technical Data: The product complies with European directives on electromagnetic compatibility and low voltage, designed for industrial use with high voltage withstand and transient overvoltage specifications. Test blocks and plugs are rated for specific current and voltage withstand levels.
Ordering Information: Detailed ordering codes are provided for test modules and plugs, specifying configurations and mounting options.
Legal Notice: Includes a disclaimer of liability, copyright information, and contact details for Siemens Protection Devices.
See more

Catalog excerpts

Catalog Reyrolle 7XG222 · Edition 1-1

Reyrolle Test Block Catalog Reyrolle 7XG222 · Edition 1

 Open the catalog to page 1
Catalog Reyrolle 7XG222 · Edition 1-2

2 Digital Grid ⋅ Reyrolle Test Block and Plug (7XG22) Catalog ⋅ Siemens Protection Device

 Open the catalog to page 2
Catalog Reyrolle 7XG222 · Edition 1-3

Digital Grid Reyrolle Test Block (7XG222) Catalog Devices and Application Digital Grid ■ Reyrolle Test Block (7XG222) Catalog ■ Siemens Protection Devices 3

 Open the catalog to page 3
Catalog Reyrolle 7XG222 · Edition 1-4

Devices and Application 7XG222 2RMLG Test Block and 2RLMB-R Test Plug Description The 7XG222 range of test blocks, housed within an Epsilon enclosure, offers facilities for monitoring and secondary injection testing of power system protection schemes in conjunction with the appropriate multi-fingered test plug. The 2RMLG Test Block has 14 pairs of spring loaded contacts which are linked to a terminal block positioned at the rear of the enclosure. The 2RMLG07 is coded to only accept the 2RMLB-R7 Test Plug which has connection terminals 21, 23, 25, and 27, internally. The 2RMLG08 is coded to only...

 Open the catalog to page 4
Catalog Reyrolle 7XG222 · Edition 1-5

Hardware Construction The 2RMLG is a size E2 unit in the Epsilon range of enclosures. The rear terminal block has 28 terminals each with an M4 screw outlet for the attachment of external wiring, fitted with 'L' shaped pre-insulated ring tongue terminations. 2RMLB-R7 with Shorting Contacts The 2RMLB-R7 is similar to the 2RMLB-R1 with shorted contact pairs 21-23-25-27 and is coded to be used with the MMLG07 Test Socket only. 2RMLB-R8 with Shorting Contacts The 2RMLB-R8 is similar to the 2RMLB-R1 with shorted contact pairs 1-3, 5-7, 9-11, 15-17 and is coded to be used with the 2RMLG08 Test Socket...

 Open the catalog to page 5
Catalog Reyrolle 7XG222 · Edition 1-6

Technical Documentation Connection Diagrams Connection Diagrams Figure 3.1/1 Typical Application of the 2RMLG01 / 2RMLG02 Test Block and 2RMLB-R1 Test Plug NOTE 2RMLG01 13/14 open cct when cover is removed and all other positions are connected. 6 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices 2RMLG02 13/14 connected as in the same way as other positions

 Open the catalog to page 6
Catalog Reyrolle 7XG222 · Edition 1-7

Technical Documentation Connection Diagrams Figure 3.1/2 Typical Application of the 2RMLG07 Test Block and 2RMLB-R7 Test Plug Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices

 Open the catalog to page 7
Catalog Reyrolle 7XG222 · Edition 1-8

Technical Documentation Connection Diagrams Figure 3.1/3 Typical Application of the 2RMLG08 Test Block and 2RMLB-R8 Test Plug Figure 3.1/4 Typical Application of the 2RMLG09 Test Block and 2RMLB-R9 Test Plug 8 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Device

 Open the catalog to page 8
Catalog Reyrolle 7XG222 · Edition 1-9

Technical Documentation Dimension Drawings Dimension Drawings This section displays the different dimensional views of a Test Block. Figure 3.2/1 Panel Cut-out View Figure 3.2/2 Side View (Vertical) Top View (Horizontal) Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection Devices

 Open the catalog to page 9
Catalog Reyrolle 7XG222 · Edition 1-10

Technical Documentation Dimension Drawings Figure 3.2/3 Front View NOTE The ∅3.6 holes are for M4 thread forming (trilobular) screws. These are supplied as standard and are suitable for use in ferrous/aluminum panels 1.6 mm thick and above. For other panels, holes to be M4 clearance (typically ∅4.5) and relays mounted using M4 machine screws, nuts and lockwashers (supplied in panel fixing kit). 10 Digital Grid ⋅ Reyrolle Test Block (7XG222) Catalog ⋅ Siemens Protection De

 Open the catalog to page 10
Catalog Reyrolle 7XG222 · Edition 1-11

Technical Data Indication of Conformity This product complies with the directive of the Council of the European Communities on the harmonization of the laws of the Member States relating to electromagnetic compatibility (EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low Voltage Directive 2014/35/EU) as well as restriction on usage of hazardous substances in electrical and electronic equipment (RoHS Directive 2011/65/EU). This conformity has been proved by tests conducted by Siemens AG in accordance of the Council Directive in accordance...

 Open the catalog to page 11
Catalog Reyrolle 7XG222 · Edition 1-12

Damp heat test, steady state 56 days at 93 % RH and +40 °C Enclosure Protection (2RMLG only) IEC 60529 IP50 (dust protected) 12 Digital Grid ■ Reyrolle Test Block (7XG222) Catalog ■ Siemens Protection Devices

 Open the catalog to page 12
Catalog Reyrolle 7XG222 · Edition 1-13

Product Description Order Number Digital Grid ■ Reyrolle Test Block (7XG222) Catalog ■ Siemens Protection Devices 13

 Open the catalog to page 13
Catalog Reyrolle 7XG222 · Edition 1-14

14 Digital Grid ■ Reyrolle Test Block (7XG222) Catalog ■ Siemens Protection Devices

 Open the catalog to page 14
Catalog Reyrolle 7XG222 · Edition 1-15

Indication of conformity This product complies with the directive of the Council of the European Communities on harmonization of the laws of the Member States relating to electromagnetic compatibility (EMC Council Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low Voltage Directive 2006/95/EC). This conformity has been proved by tests performed according to the Council Directive in accordance with the generic standards EN 61000-6-2 and EN 61000-64 (for EMC directive) and with the standard EN 60255-27 (for Low Voltage Directive) by Siemens AG....

 Open the catalog to page 15
Catalog Reyrolle 7XG222 · Edition 1-16

Published by and copyright © 2019 Siemens Protection Devices P.O. Box 8 North Farm Road Hebburn Tyne & Wear NE31 1TZ United Kingdom Phone: +44 (0)191 401 7901 Fax: +44 (0)191 401 5575 E-mail: [email protected] Subject to changes and errors. The information given in this document only contains general descriptions and / or performance features which may not always specifically reflect those described or which may undergo modification in the course of further development of the products. The requested performance features are binding only when they are expressly agreed upon in the concluded...

 Open the catalog to page 16

All SIEMENS Energy automation and smart grid catalogs and technical brochures

  1. SIPROTEC Compact

    220  Pages

  2. SICAM Q100

    28  Pages

  3. 7SR5 Platform

    86  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.