Product catalog summary
Overview: The Cerberus PRO product catalog by Siemens Switzerland Ltd offers a comprehensive range of fire safety products and accessories, designed to meet the growing demand for energy-efficient, safe, and secure buildings and infrastructure.
Key Sections:
  • Stand-alone Fire Control Panels: Includes FC72x Compact Fire Control Panels and the FC721 Series, with options for expansion and accessories.
  • Fire Control Network Participants: Details on networkable fire control panels such as the FC722, FC724, and FC726 Series, along with network components and accessories.
  • Conventional Fire Control Panels: Covers 1-zone to 12-zone panels, including the Genesis and FC10 Series, with expansion options and accessories.
  • Conventional Extinguishing Control Panels: Features the XC10 and XT10 Series, connectable to fire detection systems.
  • Fire Detection Network Peripherals: Includes addressable fire detectors, manual call points, alarm equipment, and addressable modules.
  • Visual Parallel Alarm Indicators: Provides information on alarm indicators for C-NET devices.
  • Fire Detection Conventional/Collective Peripherals: Details on conventional/collective line detectors and manual call points.
  • Conventional Alarm Equipment: Focuses on sounders and optical signaling equipment.
  • Special Applications: Discusses special detectors, explosion-hazard area products, and interfaces.
  • Special Equipment: Includes test equipment, batteries, and spare parts.
Critical Information: The catalog emphasizes the importance of specifying required features at the time of contract closure, as not all technical options may be present in individual cases. Siemens positions itself as a preferred partner for comprehensive fire safety and security solutions, integrating fire safety systems with building management systems for enhanced safety and comfort.
System Components: The Cerberus PRO system includes a range of control panels, detectors, and peripheral devices. Key components include stand-alone and networkable control panels, multi-sensor detectors, and manual call points. The system is designed for both small and large applications, offering flexibility and scalability.
Key Features: The system boasts unique safety features such as built-in isolators and degrade mode, ensuring continued operation even in the event of faults. It supports auto-configuration for easy commissioning and can be integrated into Siemens' danger management system.
Networking Capabilities: Cerberus PRO supports extensive networking possibilities, allowing for the creation of campus-wide networks using industrial LAN technology. It can be integrated into existing IT networks, enhancing usability and information distribution.
Technical Specifications: The document details technical specifications for various components, including power supply, operating voltage, and environmental conditions. It also outlines compatibility with different detector types and provides ordering information for accessories and expansion modules.
Applications: The system is suitable for a wide range of environments, from small workshops to large, complex buildings. It is designed to protect people and assets by providing fast, reliable fire detection and alarm signaling.
Conclusion: Cerberus PRO is presented as a reliable and innovative fire protection solution, backed by Siemens' experience and commitment to safety. The system's flexibility, ease of use, and integration capabilities make it a valuable investment for ensuring comprehensive fire safety.
Specifications: The document provides detailed specifications and configurations for Siemens' FC72x series of networkable fire control panels, specifically the FC724 and FC726 models. These panels are designed for use in large and complex buildings, offering modular and expandable solutions for fire detection and control.
Modules and Accessories: Various modules are available for expansion, including RS232 and RS485 communication modules, sounder modules, and network modules (SAFEDLINK). License keys for Cerberus-Remote and connection to danger management systems are available. Additional accessories include event printers, key switches, and mounting kits for Ethernet switches.
Network and Configuration: The panels can be configured using the Cerberus-Engineering-Tool, allowing for versatile system setups. Up to 2000 events can be stored, with automatic summer/winter time adjustments and auto-configuration of C-NET devices. Network topology supports up to 64 fire control panels and terminals, conforming to EN 54 standards.
Applications: The FC724 and FC726 panels are suitable for large-scale applications such as industrial plants, office complexes, and university campuses, offering flexible cross-linking possibilities for extensive systems.
License Keys: The document outlines two types of license keys: FCA2012-A1 and FCA2013-A1. Both are iButton licenses for Sinteso and Cerberus PRO systems, with the latter also supporting BACnet. Only one license key is needed per station.
Event Printer: The FTO2001-A1 is a thermal event printer for logging alarms and messages, requiring an RS232 module for operation. It operates at 9-48 VDC and has specific current requirements.
Mounting Plate: FHA2007-A1 is a pivoting mounting plate for housing modules, allowing access to underlying components.
Fire Brigade Periphery Module: FCI2001-D1 is designed for VdS-compliant switching in Germany, with specific voltage and current specifications.
Sounder Module: FCA2005-A1 allows splitting a horn line into four individual lines, with specific voltage and current requirements.
Housings: Various housings (FH7201-Z3 to FH7205-Z3) are described for different applications, each with specific dimensions, color, and battery space options.
Operating Add-ons: FCM7205-Y3, FCM7211-Y3, and FCM7212-Y3 are LED display groups for updating fire control panels, with varying LED capacities.
Power Supply Kits: FP2003-A1, FP2004-A1, and FP2005-A1 are auxiliary power supplies with different power outputs and dimensions.
Network Modules: FN2001-A1 and FN2002-A1 are network modules for connecting multiple stations, with FN2006-A1 and FN2007-A1 supporting fiber-optic connections over long distances.
Ethernet and Security Modules: FN2008-A1 is an Ethernet switch for connecting clusters, and FN2009-A1 is a security module for network protection.
Accessories: Various accessories like key switches and relay modules are mentioned for additional functionalities.
Relay Module Specifications: The relay module is activated by the fire control panel's control output with a contact rating of 250 VAC / 10 A. It is delivered in units of 10 pieces.
Mounting and Installation Accessories: The FHA2015-A1 and FHA2017-A1 are flush mounting bezels for fire control panels and operating terminals, available in white color with dimensions specified. The FHA2016-A1 is a 19" mounting kit for installing panels in third-party housings.
Fire Control Network Components: The FC72x and FT724 are networkable fire control panels and operating terminals. The FT724 can operate independently with its own power supply and supports various interfaces and network modules. It can connect up to 32 panels in a cluster, expandable to 64 with a fiber-optic backbone.
Printer and Communication Modules: The DL3750+ is a matrix printer used for documenting system events, requiring the RS232 module FCA2001-A1 for operation. The FCA2001-A1 and FCA2002-A1 are RS232 and RS485 modules for peripheral device connections.
Power Supply and Housing: The FP2003-A1 is a 70 W power supply kit for control panels and terminals, converting mains voltage to system voltage. The FH7201-Z3 is an eco housing for various components, including power supply kits and printers.
Genesis Series Fire Control Panels: The Genesis Series offers a single-zone fire detection system compatible with conventional and collective devices. It operates on a 12 VDC supply and provides 24 VDC output for detectors.
FC10 Fire Control Panel: The FC10 is designed for easy operation with clear LED displays and ergonomic controls. It supports manned/unmanned operation modes and offers programmable functions to reduce false alarms.
Specifications: The document outlines the specifications for Siemens' conventional extinguishing control panels and addressable fire detectors. The XC1003-A extinguishing panel offers a robust cabinet with a maximum of 72-hour backup time using a 17 Ah battery. It includes space for optional interfaces or modules and features a countdown timer before extinguishing release. The panel supports a mains voltage of 115-230 VAC and has a battery capacity of 2 x 12 V / 4.5-17 Ah. It complies with standards EN 12094-1, EN 54-2/A1, and EN 54-4/A2.
Procedures and Connectivity: The XC1003-A panel can be connected to fire detection systems and configured to control complex multi-sector installations. Up to 16 panels can be installed in a 19" housing, allowing for common control cylinder activation and monitoring of selector valves. The panel includes alarm relay outputs, control outputs, and control inputs.
Accessories and Expansion Modules: The document lists various accessories and expansion modules, such as the XCE1002 trigger element, XCA1020 accessory set for FDCIO, and XCA1030 multi-zone extension module. These components enhance the functionality and connectivity of the extinguishing control panels.
Fire Detection Network (C-NET) Peripherals: Siemens offers a range of addressable fire detectors, including multi-sensor smoke detectors (OH720), fire and CO detectors (OOHC740), and heat detectors (HI720). These detectors utilize ASAtechnology for reliable fire detection in environments with deceptive phenomena. They operate on a communication protocol called C-NET and are compatible with the FS720 system.
Key Features of Detectors: The detectors feature selectable parameter sets to adjust to surrounding conditions, ensuring high immunity to false alarms. They are designed to detect flaming and smoldering fires using optical and heat sensors. The detectors are powered by C-NET, reducing wiring requirements and allowing for the reuse of existing cables.
Standards and Compliance: The detectors comply with various standards, including EN 54-5, EN 54-7, and EN 54-17. They are designed to operate within specific temperature and humidity ranges and offer protection categories up to IP44 with additional seals.
Conclusion: This document provides comprehensive technical details on Siemens' extinguishing control panels and fire detection systems, highlighting their specifications, connectivity options, and compliance with industry standards. The accessories and expansion modules enhance the systems' capabilities, making them suitable for complex fire safety applications.
Specifications: The document outlines the specifications for various alarm sounders and related equipment used in fire detection systems. The operating voltage for these devices ranges from 12 to 33 VDC, with an operating current of 3.5 mA when sound is activated. The sound intensity varies between 80 to 99 dBA, and the devices are compatible with FDnet and C-NET systems.
Procedures and Installation: The alarm sounders are designed for wall or ceiling mounting along escape routes, corridors, and staircases. They require an addressable detector base for operation, and power is supplied via FDnet/C-NET, eliminating the need for an auxiliary power supply. The devices support both recess and surface supply lines, with specific base attachments required for different installation environments.
Standards and Compatibility: The equipment complies with standards EN 54-3 and EN 54-17, ensuring reliability and safety in fire detection systems. The devices are compatible with various Siemens fire detection systems, including FS20, AlgoRex, SIGMASYS, and FS720.
Protection and Environmental Conditions: The protection category varies depending on the base and sealing elements used, ranging from IP40 to IP54. The devices operate within a temperature range of -25 to +70 °C and can be stored at temperatures between -30 to +75 °C. They are designed to function in environments with relative humidity up to 95%.
Accessories and Additional Components: The document lists several accessories, including detector locking devices, base attachments, and designation plates. These components enhance the functionality and security of the alarm systems, providing options for theft protection and environmental sealing.
Sound Patterns and Intensity: The alarm sounders offer 11 different sound patterns, each with specific frequency and pulse characteristics. The sound intensity is adjustable, with typical values provided for different voltage levels. The document includes a detailed table of sound patterns, their corresponding norms, and intensity levels.
Line Separators: Line separators are used to prevent the breakdown of multiple stub lines in case of a short circuit. They are integrated into the FDnet/C-NET and ensure continued operation of the short circuit-free side. The separators are compatible with various Siemens fire detection systems and comply with standard EN 54-17.
Overview: The document provides detailed technical specifications and functionalities of various modules and components used in fire detection systems, specifically within the FDnet/C-NET framework. It includes information on input modules, input/output modules, and accessories for mounting and protection.
Specifications:
  • Communication Protocol: FDnet/C-NET
  • Operating Voltage: 12... 33 VDC
  • Operating Temperature: -25... +70 °C
  • Storage Temperature: -30... +75 °C
  • Protection Category: IP30, with optional IP65 housing
  • Standards: EN 54-17, EN 54-18
Modules:
  • Input Modules: Designed for connecting circuits with potential-free contacts for technical state indication or alarm actuation. They include status indication by LED and are powered via FDnet/C-NET.
  • Input/Output Modules: These modules connect circuits for technical state indication and alarm actuation, with configurable inputs and outputs. They support decentralized control of fire doors and ventilation systems.
  • Floor Repeater Terminals: These terminals provide a user interface for event localization and system operation, with a backlit display for clear text readout.
Accessories:
  • U-Rails: Universal mounting rails for equipment installation.
  • Housing: FDCH221 housing for wet applications, providing IP65 protection.
  • Connection Terminals: For cross-connection in bases for external alarm indicators and other components.
Key Features:
  • Modules are compatible with various fire detection systems like FS20, AlgoRex, SIGMASYS, and FS720.
  • Modules support both loop and stub line configurations.
  • LED indicators provide status updates for easy monitoring.
Overview: The document provides detailed specifications and descriptions of various fire detection and alarm system components, including floor repeater displays, mimic display drivers, alarm indicators, and conventional fire detectors. It outlines technical specifications, operating conditions, and compatibility with different systems.
Floor Repeater Display: This section describes the floor repeater display, which can show alarms, pre-alarms, technical messages, faults, and isolations. It features navigation keys for scrolling through lists and an internal buzzer that can be silenced during alarms. The display is powered via FDnet/C-NET or a separate 24 V power supply and can operate in loops or stub lines. Key specifications include operating voltage (12-32 VDC), supply voltage (20-30 VDC), and current consumption (5 mA quiescent, 45 mA max).
Mimic Display Driver: The FT2001-A1 mimic display driver activates LEDs on mimic display panels and includes control outputs for a local buzzer and LED operation. It supports firmware updates via an MC-Link plug-in point and operates on FDnet/C-NET. Specifications include operating voltage (12-32 VDC) and current (max 45 mA).
Alarm Indicators: Various alarm indicators are described, including door frame, surface, and flush models. These indicators connect in parallel to fire detectors to quickly show alarm sources. They feature screwless connection terminals and operate at 5-8 VDC with a max current of 35 mA. Protection categories range from IP40 to IP65, depending on the model and housing used.
Conventional Fire Detectors: Siemens offers conventional fire detectors designed for easy installation and maintenance. These detectors are resistant to contamination and electromagnetic interference and feature screwless connection technology. The OOH740 multi-sensor smoke detector uses ASAtechnology for reliable detection in environments with deceptive phenomena, operating at 12-33 VDC.
Accessories: The document lists various accessories, including adapter frames, housing units, and connection terminals, which enhance the functionality and installation flexibility of the fire detection components.
Overview: This document provides detailed specifications and descriptions of various fire detection peripherals and accessories, primarily focusing on the Siemens Conventional/Collective Line SynoLINE300/600 and AlgoRex Series. It includes information on detectors, bases, and related components.
Specifications:
  • Screwed Cable Gland M20: Designed for M20 cable feed-through, enhancing protection category. Delivery unit includes 10 pieces.
  • Alarm Indicator Housing DJZ1193: Suitable for surface mounting in wet areas, with dimensions 87 x 87 x 64 mm and protection category IP65.
  • Fire Detectors: Includes multi-sensor, smoke, and heat detectors with selectable detection behaviors, operating voltage of 16-28 VDC, and various protection categories (IP40/IP42).
  • Detector Bases: Various models (DB110, DB110D, DB110R, etc.) for different parameter settings and wiring configurations, with dimensions 117 x 23 mm.
Procedures and Standards:
  • All detectors comply with EN 54-7 standards, ensuring reliable fire detection in environments with deceptive phenomena.
  • Operating and storage temperature ranges are specified for each device, ensuring functionality in diverse conditions.
Accessories:
  • Micro and Connection Terminals: Used for cross-connection in bases, available in different cable capacities and delivery units.
  • Protective Cages and Base Attachments: Designed for humid and wet environments, providing additional protection and mounting options.
  • Acoustic and Relay Bases: Integrated sounders and relays for enhanced alerting and control capabilities.
Recommendations:
  • Use appropriate detector bases and accessories to ensure optimal performance and protection in specific environmental conditions.
  • Follow installation guidelines for each component to maintain compliance with safety standards.
Overview: This document provides detailed specifications and accessory information for Siemens manual call points used in fire detection systems. These devices are designed for immediate manual actuation of fire alarms and are suitable for both indoor and outdoor applications.
Specifications:
  • Models: FDM1101-RG, FDM1101-RP, DM1101__, DM1104__, DM1103__.
  • Operating Voltage: 16-28 VDC.
  • Operating Current: 60-100 mA.
  • Operating Temperature: -25 to +70 °C.
  • Protection Category: IP44 for most models, IP54/IP65 with additional protection for others.
  • Standard Compliance: EN 54-11.
  • Dimensions: Vary by model, e.g., 87 x 87 x 20 mm for FDM1101 models.
Procedures:
  • Manual call points are activated by pushing in a glass plate or pressing a plastic element.
  • Resetting involves replacing the glass plate or using a key for models with a resettable element.
Accessories:
  • Housing Bases: FDMH295-R, FDMH295-S for surface mounting.
  • Protective Covers: FDMC295, DMZ1197-AC to prevent accidental glass breakage.
  • Cable Glands and Nuts: A5Q00004478, A5Q00004479 for enhanced protection.
Recommendations:
  • Ensure compatibility with SynoLINE600 communication protocol.
  • Use protective covers and seals in wet or hazardous environments to maintain device integrity.
Key Data from Tables:
  • Various housing colors available for different models, e.g., red, blue, yellow, green.
  • Specific accessories like connection terminals and locking plugs are available for customization and enhanced functionality.
Specifications and Components:
1. Alarm Indicator Housing: DJZ1193 for surface mounting in wet areas, dimensions 87 x 87 x 64 mm, IP65 protection.
2. Smoke Detectors: OP320C and OH320C with operating voltage 16-28 VDC, IP44 protection, and EN 54-7 standard compliance.
3. Heat Detectors: HI320C and HI322C with reliable response to temperature changes, IP44 protection, and EN 54-5 standard compliance.
4. Manual Call Points: FDM1101A-RG and FDM1101A-RP for immediate fire alarm actuation, IP44 protection, and EN 54-11 standard compliance.
5. Alarm Devices: AGN24.6 and AGT24.1 sounders with adjustable volume and multiple tones, IP54 protection.
6. Flashing Signal Lamps: ALB24.1OR and ALB24.1R with electronic flash tube, IP54 protection.

Procedures and Installation:
1. Mounting Brackets: MVH1 for alarm indicator housing and detectors in hollow floors.
2. Base Attachments: SOA322 for surface mounting and additional wire space.
3. Connection Terminals: DBZ1190-AB for cross-connection and power supply integration.
4. Adapter Bases: ZS/AGN24.5 for upgrading devices to IP65 protection.

Standards and Compliance:
1. Protection Categories: Devices range from IP40 to IP65, ensuring suitability for various environments.
2. Standards: Compliance with EN 54-7 for smoke detectors and EN 54-5 for heat detectors.

Recommendations and Best Practices:
1. Use in Humid Areas: Specific washers and housings are recommended for humid environments.
2. Surface and Recess Mounting: Options available for different installation needs.
3. Color Customization: Most devices are white but can be sprayed a different color if needed.

Key Accessories:
1. Screwed Cable Gland: A5Q00004478 for M20 cable feed-through.
2. Protective Covers: FDMC295 to prevent unintentional glass breakage on manual call points.
3. Adapter Frames: AI330 for alarm indicators to accommodate different mounting needs.
Overview: This document provides detailed specifications and descriptions of various fire detection systems and components, including infrared flame detectors, linear smoke detectors, and air sampling smoke detection kits. It includes information on system compatibility, operating conditions, and accessories.
Infrared Flame Detectors: The document describes two types of infrared flame detectors: FDF221-9 and FDF241-9. The FDF221-9 is suitable for simple applications without interference sources, while the FDF241-9 is designed for environments with deceptive phenomena. Both require the FDFB291 base, operate within specific voltage ranges, and have defined operating and storage temperature limits. The FDF241-9 offers enhanced protection with IP67 rating.
Linear Smoke Detectors: The FDL241-9 ASA Linear smoke detector is designed for monitoring large areas with a detection range of 5 to 100 meters. It uses a light emitter and receiver system with various reflectors available for different distances. The system is compatible with multiple communication protocols and requires the FDLB291 base.
Air Sampling Smoke Detection: The FDBZ292 kit is a passive monitoring system that utilizes existing ventilation systems to detect smoke. It is compatible with several smoke detectors and bases, and operates within specific environmental conditions. Accessories include various air flow tubes and a sealing kit.
Accessories and Components: The document lists various accessories such as mounting brackets, reflectors, filters, and connection terminals, each with specific dimensions and compatibility details. These components are essential for the installation and operation of the detection systems.
Standards and Compliance: The systems comply with relevant standards such as EN 54-10, EN 54-17, and EN 54-12, ensuring reliability and safety in fire detection applications.
Specifications:
The document outlines various products designed for explosion-hazard areas, focusing on flame detectors, manual call points, alarm indicators, and test equipment. Key specifications include:
  • Stabex HF test lamp for performance checks of infrared flame detectors.
  • DF1101-Ex infrared flame detector with intrinsic safety for Ex-protected areas, featuring intelligent signal processing for high detection reliability.
  • DFB1190 base for infrared flame detectors, providing isolated installation and EMI protection.
  • DM1103(Ex) and DM1104(Ex) manual call points for immediate alarm actuation in explosion-hazard areas.
  • FDAI92-Ex and FDAI93-Ex alarm indicators for quick alarm signal indication.
  • DB3 alarm device for audible alerts in potentially explosive atmospheres.
Procedures:
Installation and operation procedures are detailed for each product, emphasizing the need for separate ordering of components like bases and housings. The document specifies:
  • Use of test lamps and detector testers for performance checks.
  • Manual call points require glass plate replacement and button reset after activation.
  • Alarm indicators are connected in parallel to fire detectors for visibility of alarm signals.
Standards and Norms:
The products comply with various standards for safety and performance, including:
  • EN 54-10 for flame detectors.
  • EN 50014 and EN 50020 for explosion-hazard areas.
  • EN 54-11 for manual call points.
Recommendations:
Recommendations include:
  • Ordering separate components for complete installation.
  • Using specific accessories like protective covers and seals to enhance protection categories.
  • Ensuring proper installation and maintenance to maintain safety and functionality.
Key Data from Tables and Figures:
The document provides dimensions, operating temperatures, and protection categories for each product, ensuring suitability for specific environments. For example:
  • DF1101-Ex dimensions: 135 x 135 x 32 mm, operating voltage: 16-28 VDC.
  • DM1103(Ex) dimensions: 134 x 134 x 43 mm, operating temperature: -25 to +70 °C.
  • DB3 alarm device volume: 101-115 dB, protection category: IP66/67.
Overview: This document provides detailed specifications, accessories, and spare parts information for Siemens fire detection and control systems. It includes descriptions of various equipment, their operating conditions, and ordering information.
Specifications:
  • Operating and storage temperature ranges for various devices are specified, ensuring proper usage and storage conditions.
  • Relative humidity is maintained at 95% for most devices, indicating the need for controlled environments.
Equipment and Accessories:
  • Adapters and Telescope Rods: The RE7T-A adapter and FDUM291/292 telescope rods are essential for extending the reach of detector testers.
  • Test Lamps: LE3 and StabexHF test lamps are used for testing flame detectors, with specific models for explosion-hazard areas.
  • Line Tester: FDUL221 is a universal device for testing fire detection lines, providing troubleshooting capabilities.
  • Interface Adapters: FDUZ221 MCL USB adapter facilitates connection of devices to a PC for firmware updates.
Batteries:
  • Various rechargeable, sealed lead-acid batteries are available for emergency power supply, with specifications for voltage and dimensions.
Spare Parts:
  • Spare parts for fire control panels, operating terminals, and extinguishing control panels are listed, including main boards, power supplies, and cover sets.
  • Manual call points and input/output modules have specific spare parts like replacement glass, keys, and mounting feet.
Recommendations:
  • Ensure all equipment is used within specified temperature and humidity ranges to maintain functionality and safety.
  • Order necessary accessories and spare parts in advance to ensure uninterrupted operation of fire detection systems.
Spare Parts and Test Equipment
1. FDUL221-C PC Cable (RS232): Used as a spare part for the line tester FDUL221.
2. Halogen Lamp 12 V / 50 W: Spare part for LE3.
3. RE7T-B Solo760 Battery: Spare part for RE7T heat detector tester.
4. RE7T-C Solo725 Charger: Used for charging the battery baton of the RE7T heat detector tester.
5. RG320 and DZZ1190 Bellows: Fitted to RE6 for SynoLINE300 and SynoLINE600/AlgoRex point detectors respectively.
Repair Parts
Fire Control Panels and Operating Units:
1. FCM7201-Z3, FCM7202-Y3, FCM7203-H3: Operating units used as repair parts.
2. Periphery Boards: FCI2010-A1, FCI2002-A1, FCI2004-A1, and FTI2001-A1 are used as repair parts.
3. Network Module FN2001-A1: Used as a repair part for SAFEDLINK.
Danger Management System
MM8000 Management Station: Provides centralized alarm management and supervision for fire safety, security, and control systems. It integrates subsystems like fire safety, intrusion detection, access control, and video surveillance. Features include guided event treatment, history database, and flexible configuration.
Key Features:
- Integration with various subsystems.
- Central control and operation with easy navigation.
- Advanced graphics and automatic/manual alarm dispatching.
- System security based on Microsoft Windows.
Fire Control Panels
1. FC721, FC722, FC724, FC726: Various models with features like C-NET loops, integrated control units, and networkability via backbone or Ethernet.
2. Networking: Supports Ethernet and C-WEB/SAFEDLINK for connecting panels and clusters, with redundancy and safety features.
Additional Components
- Housings: Various sizes and types for different installations.
- Power Supply Kits: Options for 70W and 150W power supplies.
- Operating Add-ons: LED indicators and key switches for enhanced functionality.
Overview
Siemens offers a comprehensive portfolio for fire safety and security needs, integrating fire protection, detection, and security systems with building management solutions. Their approach aims to protect people and assets, minimize downtime, and prevent business interruptions.

Key Offerings
  • Fire Safety: Includes fire protection and detection systems.
  • Security Systems: Integrates with voice-controlled evacuation, extinguishing, and emergency lighting systems.
  • Building Management: Combines safety systems with building management for enhanced security and comfort.

Corporate Objectives
Siemens focuses on protecting personnel and investments, supporting corporate objectives through intelligent building solutions that enhance safety and security.

Technological Integration
Siemens incorporates industrial know-how and experience in research and development to create all-encompassing security concepts based on the latest information technology.

Global Perspective
Siemens addresses global challenges such as demographic change, urbanization, and resource shortages by prioritizing energy efficiency and user comfort.
See more

Catalog excerpts

Cerberus PRO product catalog - Fire safety products and accessories-1

Cerberus PRO product catalog Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel +41 41 724 24 24 The information in this document contains general descriptions of technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract. © Siemens Switzerland Ltd, 2012 • Order no. 0-92284-en • 1,251205 Answers for infrastructure. Our world is undergoing changes that force us to think in new ways: demographic change, urbanization, global warming and resource shortages. Maximum efficiency has top priority – and not only where energy is concerned. In addition, we need to increase comfort for the well-being of users. Also, our need for safety and security is constantly www.siemens.com/cerberus growing. For our customers, success is defined by how well they manage these challenges. Siemens has the answers. Cerberus PRO product catalog Fire safety products and accessories “We are the preferred partner for energy-efficient, safe and secure buildings and infrastructure.” Answers for infrastructure.

 Open the catalog to page 1
Cerberus PRO product catalog - Fire safety products and accessories-2

Everything you need for re safety and security From re protection and re detection to safety and security – Siemens offers a comprehensive portfolio for security needs from one source. Risk management Assessment Consulting Process Training integration Services Fire Intrusion Access Management station Video Time Fire safety & Security Evacuation Scanning Ventilation Heating AC Light Water Power Energy & Comfort Prevent incidents from occurring – protect people and assets Whatever your requirements, Siemens provides a comprehensive portfolio for all fire safety and security needs. Investment in...

 Open the catalog to page 2
Cerberus PRO product catalog - Fire safety products and accessories-6

Does anyone know a clever fire safety system starting with a "C"? Cerberus PRO - enjoy protecting! The new generation of a clever fire safety system. Protecting people and assets. Securing business processes and continuity. This is what fire protection is all about. Cerberus® PRO from Siemens is a smart fire safety system for fast, proven fire detection, alarm signaling and control. Its broad portfolio comprises powerful control panels from stand-alone to networkable units, reliable detectors with patented technology and a comprehensive range of loop- powered peripheral devices. All system components...

 Open the catalog to page 6
Cerberus PRO product catalog - Fire safety products and accessories-7

Cerberus PRO – enjoy protecting Powerful control panels, clever re detectors and smart peripheral devices. This is what our comprehensive Cerberus® PRO family offers. The brief overview below demonstrates the most important system components. Remote access with CerberusRemote Customer network Danger management system from Siemens Ethernet Security module (rewall) FN2009-A1 Security module (rewall) FN2009-A1 Ethernet switch FN2008-A1 Ethernet switch FN2008-A1 Backbone (C-WEB/LAN) Ethernet switch FN2008-A1 Ethernet switch FN2008-A1 Manual call point FDM221 C-NET Alarm sounder FDS221 Fire control...

 Open the catalog to page 7
Cerberus PRO product catalog - Fire safety products and accessories-8

Compatibility chart (■) Compatible with an interface * 3 parameter sets only

 Open the catalog to page 8
Cerberus PRO product catalog - Fire safety products and accessories-9

Conventional and collective devices Special applications Optical detector Heat detectors Manual call Special detectors

 Open the catalog to page 9
Cerberus PRO product catalog - Fire safety products and accessories-10

Protecting people and assets reliably Protecting people and assets. Securing business processes and continuity. This is what fire protection is all about. Cerberus® PRO is a powerful fire protection system for fast, reliable fire detection, alarm signaling and control. Its wide portfolio of innovative products provides clever technology with extensive safety features. ■ Protecting people and assets reliably with Siemens products The Cerberus PRO family comprises differ- ent control panels, fire detectors, periph- eral devices and accessories. They all have one thing in common: smart, unique safety...

 Open the catalog to page 10
Cerberus PRO product catalog - Fire safety products and accessories-11

Stand-alone Fire Control Panels Fire Control Network Participants Ensuring comprehensive safety with powerful panels Cerberus® PRO fire control panels combine high security standards with the latest technology. Competitive for simple applications, yet powerful enough for every application - they are the ideal choice whatever the size and complexity of a project. The Cerberus PRO family offers four models, covering small to very large application areas. They can either stand alone or be networked into a larger system. Furthermore, all panels can be accessed either remotely or on site. ■ A competitive...

 Open the catalog to page 11
Cerberus PRO product catalog - Fire safety products and accessories-12

Stand-alone addressable fire control relay modules Control panel shown with 24 indicator groups, each with one red and one yellow LED

 Open the catalog to page 12
Cerberus PRO product catalog - Fire safety products and accessories-13

Stand-alone Fire Control Panels FC72x Compact Fire Control Panels Fire control panel (1-loop) in housing (Eco) The FC721.. is a compact fire control panel with integrated operating unit that can process signals from Cerberus® PRO devices of up to 126 The fire control panel may be used as a stand-alone unit only. In addition, an Ethernet connection is available at each station. Via this fast Ethernet interface remote control service is possible. All detector lines are monitored for ground faults. The Cerberus-Engineering-Tool permits the system to be adapted to specific customers' requirements....

 Open the catalog to page 13
Cerberus PRO product catalog - Fire safety products and accessories-14

Stand-alone Fire Control Panels FC72x Compact Fire Control Panels Fire control panel (1-loop) in housing (Eco) See FC721.. for technical overview and note the additional / other DL3750+ Matrix printer (Extern) FHA2017-A1 Flush mounting bezel Fire control panel (1-loop) in housing (Eco) with 1 LED indicator S54400-C32-A3 See FC721.. for technical overview and note the additional / other With 24 indicator groups, each with one red and one yellow LED. DL3750+ Matrix printer (Extern) FHA2017-A1 Flush mounting bezel

 Open the catalog to page 14
Cerberus PRO product catalog - Fire safety products and accessories-15

Stand-alone Fire Control Panels FC72x Compact Fire Control Panels Fire control panel (1-loop) in housing (Eco) with EVAC operating See FC721.. for technical overview and note the additional / other With 10 evacuation operating zones for Netherlands. DL3750+ Matrix printer (Extern) FHA2017-A1 Flush mounting bezel

 Open the catalog to page 15
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.