The MFC1100 series gas mass flow controllers are designed for high-volume gas flow control applications, featuring a full-scale range of 20 to 50 Ln/min. Both analog (0-5 Vdc or 4-20 mA) and an RS485 Modbus interface for mass flow control with the proportional valve. The MFC1100 can be applied for non-corrosive process gas control with a 100:1 dynamic range. It controls within a pressure range of 0.1 to 0.8 MPa (15 to 117 PSI) and a compensated temperature range of 0 to 55 °C. Typical applications are digital anesthesia gas and welding gas delivery. • MEMS thermal calorimetry with diffusivity (The/mal-D ®) • Extended dynamic flow range of 100:1 • Cost-effective applications • Both analog and RS485 Modbus interface
Open the catalog to page 1Flow range o ~ 20, 50 Ln/min Accuracy ± 1.5% (20 ~ 100% of full scale), ±0.3%FS (<20% of full scale) Repeatability ± 0.5% (20 ~ 100% of full scale), ±0.1%FS (<20% of full scale) Control pressure range 0.1 ~ 0.8 MPa Setpoint source (input signal) Analog: 0 ~ 5 Vdc or 4 ~ 20 mA; Digital: RS485 Settling time 100 msec Max pressure loss 37 (50 Ln/min models) kPa Output signal Analog: 0 ~ 5 Vdc or 4 ~ 20 mA; Digital: RS485 Electrical connector 6 pins, HRS:DF51K-6P-2DS Mechanical connection One-touch 6 / 8mm Note: Parameters specified at the calibration conditions. For other gases, please contact the...