water saving &plume abatement dry cooling system - 1

water saving &plume abatement dry cooling system Water saving &plume abatement dry cooling tower Traditional cooling methods for industrial circulating water A large amount of heat is produced in the production process of industrial field, which needs to be cooled by circulating water cooling system. The traditional cooling method is open circle water cooling tower. Problems with traditional cooling methods ● High water consumption (1.5%~1.8% of circulating water), serious waste of water resources, non-conformity with environmental policy; ● High operating water consumption and sewage treatment cost, poor economy; ● Winter operation produces a large number of white fog, become the carrier of haze, and "culprit “ of the Haze; ● Winter white fog forms snow, frost microclimate, resulting in safety risks. With the tightening of environmental protection policies, traditional circulating water cooling methods will be replaced. Shuangliang's energy-saving, water-saving and mist-eliminating industrial circulating water system aims to achieve the dual benefits of environmental protection and economy. Mist spray dry cooling tower for circulating water

Open the catalog to page 1
water saving &plume abatement dry cooling system - 2

System composition: The spray dry cooling system is composed of stainless steel tube radiator, louver, circulating water system, expansion water tank, spray cooling system, fan group and so on. The air cooling radiator is arranged vertically outside the tower, which depends on the air to cool the circulating water, but when the ambient temperature is high, water spray on the outer surface of the radiator is used to assist the cooling. Main Features: 01/ Low water consumption In the whole year, only in summer high temperature with short time spray cooling will apply, the annual water saving...

Open the catalog to page 2
water saving &plume abatement dry cooling system - 3

area can be reduced by about 20%. 05/ Back-to-back arrangement, small footprint One side air inlet and back-to-back arrangement are adopted to reduce the area, and the influence of hot air reflux is small. 06/ Applicability Suitable for high effluent temperature (above 38℃) of circulating water. V-type separated water saving and plume-abatement system System composition: V separate water-saving and fog-removing system consists of finned tube bundle, circulating water pipeline and fan group. V air cooler and mechanical ventilation water cooling tower are arranged independently and connected...

Open the catalog to page 3
water saving &plume abatement dry cooling system - 4

02/ Maintenance convenience Tube bundle horizontal arrangement, removable cover plate tube box, easy to tube bundle internal cleaning and maintenance. 03/ High annual water saving rate The circulating water is cooled only by the V type air cooler in winter, without evaporation of water vapor; the circulating water in spring and autumn is cooled by the V type air cooler, the cooling load of the mechanical ventilation water cooling tower is partial, the water consumption is low, and the annual water saving rate reaches 60%. 04/ Antifreeze property Adopt special anti-freezing design, winter...

Open the catalog to page 4
water saving &plume abatement dry cooling system - 5

The anti-fogging device of dry-wet combined anti-fogging cooling tower is mainly composed of heat transfer element in dry-cooled section, heat transfer element in wet-cooled section, electric shutter in dry-cooled section, electric shutter in wet-cooled section and pipeline. The circulating water enters the dry cooling section heat exchanger element to cool and then enters the wet cooling section spray layer to be cooled by spraying. Open circle dry-wet water-saving &plume -abatement cooling tower System composition: The open dry-wet combined water-saving &plume abatement cooling tower...

Open the catalog to page 5
water saving &plume abatement dry cooling system - 6

the tower body (outside the tower body), which can be expanded by adjusting the height and layout type, and is suitable for the design requirements of different dry cooling points. 02/ High water saving rate When ambient temperature is above design temperature of dry cooling point and the outlet temperature is higher than the limited temperature, the evaporative cooling coil is sprayed. When the ambient temperature is below design dry cooling point temperature, there is no need to spray water. The dry and wet sections are dry air cooling, no water consumption, and the annual water saving...

Open the catalog to page 6
water saving &plume abatement dry cooling system - 7

2. Xinjiang Xinlianxin Coal Chemical Project V Type Separation Water Saving & plume-abatement System A total of three reconstruction projects, the total amount of water 60500 m3/h Adopt V type separate water-saving and mist-removing system, modular design, flexible arrangement, easy installation, convenient maintenance While eliminating the white fog in the cooling tower in winter ,4.73 million tons of evaporative water and 1.58 million tons of sewage were reduced throughout the year. It has great social and economic benefits More references 3. Xinjiang Xiexin energy 100000 tons polysilicon...

Open the catalog to page 7
water saving &plume abatement dry cooling system - 8

Product link: https://www.shuangliang-ecoenergy.com/water-saving-plume-abatement-dry-cooling-system.ht ml page 8 / 8 Powered by TCPDF (www.tcpdf.org)