Steam operated chiller

Steam operated chiller

Steam operated chiller

Product catalog summary
Overview: The steam operated lithium bromide absorption chiller is a large industrial unit that uses steam as its driving energy, lithium bromide solution as the absorbent, and water as the refrigerant. It is particularly beneficial in areas with abundant steam resources, offering a cost-effective solution to electricity and operational expenses, especially during peak power demand in summer.
Specifications: The chiller operates with steam pressures ranging from 0 to 8 bar (G), typically using low-cost steam sources such as waste heat recovery boilers or extraction steam from industrial processes.
Types:
  • Double Effect Chiller: Operates with steam pressures of 2.5 to 8 bar (G) and has a high coefficient of performance (COP) of 1.51, making it energy-efficient.
  • Single Effect Chiller: Operates with steam pressures of 0 to 2.5 bar (G) and is suitable for lower heat grade sources, including steam as low as 100℃.
Functionality: Provides chilled water above 0℃ for cooling or industrial processes.
Capacity Range: 233 to 11630 KW (20 to 1000×104 kcal/h).
Typical Cases:
  • Messe Frankfurt, Germany: 3 units of double effect chillers with a total cooling capacity of 2559 USRT.
  • Pfizer Asia Pacific, Singapore: 3 units of double effect chillers with a total cooling capacity of 2622 USRT.
  • PT. Riau Andalan Pulp & Paper, Indonesia: 7 units of chillers with a total cooling capacity of 14700 USRT.
Additional Information: For more details, visit the product link: Shuangliang Eco-Energy.
See more

Catalog excerpts

Steam operated chiller-1

Steam operated chiller Steam Operated Lithium Bromide Absorption Chiller Steam operated lithium bromide absorption chiller is a kind of large-size industrial unit with steam as the driving energy, lithium bromide solution as the absorbent and water as refrigerant. It not only reduces greatly the cost of electricity and operation fees in regions where there are rich steam resources, but also compensates the peak-valley load difference. While in summer, shortage of electric power poses great concerns for many cities. Concentrated consumption of power caused by the use of air conditioners is the sticking point for such a seasonal problem, for which, steam operated chillers offer an attractive solution. The steam sources suitable for the absorption chiller require the pressure of steam to be in the range of 0~8 bar (G), which is normally the LP or MP steam in the industrial plant. Considering the consumption of steam for driving the absorption chiller, it’s suggested to use the low cost steam sources (i.e. the steam generated by the WHRB from the high temperature flue gas, which is deemed to be the waste heat.) or the steam coming from the extraction of industrial process, but its heat grade is too low to be used in other process (i.e. the extraction steam from the LP system of steam turbine). Based on the heat grade of steam, the steam operated lithium bromide absorption chiller can be divided into two types: Steam Operated Double Effect Lithium Bromide Absorption Chiller Saturated steam pressure range: 2.5~8 bar (G) The most attractive feature of Shuangliang steam operated double effect chiller is its stunning performance in energy saving. High COP of 1.51 ranks it in the leading position worldwide. Steam Operated Single Effect Lithium Bromide Absorption Chiller Saturated steam pressure range: 0~2.5 bar (G) Compared with double effect lithium bromide absorption chiller, the steam operated single effect chiller has lower COP but it has stronger applicability in using the heat sources at lower heat grade.

 Open the catalog to page 1
Steam operated chiller-2

Even the 100℃ steam like esterified steam still can be recycled by Shuangliang steam operated single effect absorption chiller. Function: Provide chilled water above 0℃, suitable for cooling or industrial process. Capacity Range: 233~11630KW(20~1000×104kcal/h) Driving Sources: Saturated steam with pressure in range of 0~8 bar(G) Please contact us to get more details. Steam Typical Case 1. Messe Frankfurt (Germany) 3×Steam Operated Double Effect LiBr Absorption Chiller Total Cooling Capacity: 2559 USRT

 Open the catalog to page 2
Steam operated chiller-3

2. Pfizer Asia Pacific (Singapore) 3×Steam Operated Double Effect LiBr Absorption Chiller Total cooling capacity: 2622 USRT

 Open the catalog to page 3
Steam operated chiller-4

3. PT. Riau Andalan Pulp & Paper (Indonesia) 7×Steam Operated LiBr Absorption Chiller Total cooling capacity: 14700 USRT

 Open the catalog to page 4
Steam operated chiller-6

Product link:https://www.shuangliang-ecoenergy.com/steam-operated-chiller.html page 6 / 6 Powered by TCPDF (www.tcpdf.org)

 Open the catalog to page 6
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.