EMCCB Catalog

Product catalog summary
Product Overview: The document provides detailed specifications and operational guidelines for various electrical components including Motor Control, Circuit Breakers (MCCB, ELCB, EMCCB, MCB), Air Circuit Breakers, Automatic Transfer Switches, Surge Protective Devices, Low Voltage Power Capacitors, Smart Meters, and Inverters. The focus is on EMCCB (Electronic Molded Case Circuit Breakers).
Specifications: The EMCCB adheres to IEC/EN 60947-2 standards and is CE marked. It supports a rated current range of 40-1250A, with a frequency of 50/60Hz, and rated insulation voltage of 690V. The operational voltage is 400V. Key features include long-time and short-time delay over-current protection, short-circuit current protection, and remote control capabilities via a communication module.
Operational Conditions: The EMCCB operates within an ambient temperature range of -5 to +40 degrees Celsius, at altitudes below 2000 meters, and in environments with a maximum humidity of 90% and pollution grade 3. Installation categories are specified as Category III for circuit breakers and Category II for auxiliary and control circuits.
Selection Instructions: The document provides a detailed selection guide for different frame sizes (100, 160, 250, 400, 630, 800, 1000, 1250) and their corresponding rated currents, short-circuit breaking capacities, and available accessories. It notes limitations on accessory installations when communication functions are enabled.
Protection Settings and Characteristics: The EMCCB offers adjustable settings for overload long-time delay tripping current and time, short-circuit short-time delay tripping current and time, and instantaneous tripping current. Tolerances for current and tripping time are specified, and certain functions cannot be disabled.
Technical Parameters: Detailed technical parameters are provided for various models, including rated currents, operation and insulation voltages, breaking capacities, dimensions, weight, and endurance. Optional accessories such as alarm switches, auxiliary switches, shunt trips, and communication modules are listed.
Control Panel Description: The control panel allows for setting overload and short-circuit protection parameters, testing tripping functions, and monitoring operation and overload indicators.
Communication Function: The EMCCB supports remote control and monitoring via the ETU-COM module, using RS485 and ModBus-RTU protocols. It allows data observation, measuring, and setting, with memory functions for remote operation control.
Installation and Connection: Instructions for connecting the ETU-COM module and communication hubs are provided, including diagrams for extending communication to other systems.
See more

Catalog excerpts

EMCCB Catalog-1

ELECTRONIC MOLDED CASE CIRCUIT BREAKER

 Open the catalog to page 1
EMCCB Catalog-3

. Product Description Standard: IEC/EN 60947-2 & CE Marked Rated current: 40~1250A Frequency: 50/60Hz Rated insulation voltage Ui(V): 690V Rated operation voltage Ue(V): 400V Function : + Long-time delay over-current protection + Short-time delay over-current protection + Short-circuit current protection Flexible adjustable: Tripping time, current Remote control via communication module . Operation Condition Ambient temperature: -5~+40 Altitude limit: Below 2,000M Humidity: Max. 90% Pollution: Grade 3. Installation category (over-voltage category): - Category for the circuit breaker - Category...

 Open the catalog to page 3
EMCCB Catalog-4

Rated long-time current delay current Option code AL Alarm switch c communication — functon available SHT Shunt trip Blank: N/A the circuit breaker with no communication function When the MCCB quips with communication function, there communication modules

 Open the catalog to page 4
EMCCB Catalog-5

1. Long-time delay over-current protection Current setting Ir = 0.4/0.45/0.5/0.6/0.7/0.8/0.9/0.95/1.0 x In Current Tripping time requirement Tripping time setting Tr (s) V. Protection Setting and Characteristics ★ The current value tolerance is ±10%; tripping time tolerance is ±20%. ★ Please specify, when place the order of 4P circuit breaker with neutral protection and setting at 0.5Ir or 1.0Ir. ★ This function cannot be "off" 2. Short-time delay over-current protection Current setting Is=2/3/4/5/6/7/8/10×Ir Current Tripping time requirement Inverse time curve Inverse-time Tripping time setting...

 Open the catalog to page 5
EMCCB Catalog-6

IV. Selection Instruction Frame size (AF) (Inm) Rated operation voltage Ue (V) Rated insulation voltage Ui (V) Rated impulse withstand voltage Uimp (kV) Rated current In (A) at ambient temp. 40 Rated breaking capacity Icu (kA) Mechanical life (10 thousand) Clamp terminal Clamp terminal Clamp terminal Trip unit Trip button Electrical life Auxiliary switch Optional accessories Alarm switch Shunt trip Under-voltage trip Lead wiring terminal Motor operation device Communication Communication 1. Ics= 50 Icu 2. Frame size 100/160/250: When the MCCB quips with communication function, there will be no...

 Open the catalog to page 6
EMCCB Catalog-8

VII. Description of Control Panel (1) Overload long-time delay tripping current Ir setting, 9-steps setting (lr= 0.4/0.45/0.5/0.6/0.7/0.8/0.9/0.95/1.0 * In) (2) Overload long-time delay tripping timeTr (21 r tripping time), 5-steps setting (Tr=20,40,60,80,160s). (3) Short-circuit instantaneous current li setting, 7-steps setting (Ii= 1.5/2/4/6/8/10/11*ln). (4) Testing port is used for tripping simulation test. (5) Electronic trip protection characteristic curve. (7) Operation indicator: indicator flashes green during normal operation. (8) Overload indicator: indicator flashes red if the current...

 Open the catalog to page 8
EMCCB Catalog-9

Description of Control Panel VIII. Optional Accessories Installation Table Notes: 1. Standard mounting: AL/AX – left mount; SHT/UVT – right mount 2. SHT equipped coil anti-burning protection switch 3. Accessories of MCCB BM100, BM160 and BM250 (HE/RE/UE) right-side mount is not allowed. 4. The communication function takes 2 mounting space of AL(AX); therefore BM-100-E, 160E and 250E (HE/RE/UE), can only equip either communication or AL(AX)

 Open the catalog to page 9
EMCCB Catalog-10

IX. Trip curve 1BM100-EBM160-EBM250-E Long-time delay tripping current Ir lr=0.4~1ln Long-time delay tripping time (2Ir) Tr=(20~160)s±20% Current setting (×Ir) Instantaneous tripping current (×In) Instantaneous tripping current Ii Max. Instantaneous tripping time 7 Long-time delay tripping current Ir lr=0.4~1ln Long-time delay tripping time (2Ir) Tr=(20~160)s±20% Short-time delay tripping current Is Is=(2~10)Ir ±15%+off Short-time delay tripping time Ts 0.4±0.08s 0.3±0.06s 0.2±0.04s 0.1±0.03s Instantaneous tripping current Ii Ii(1.5~11)In ± 15% Max. Instantaneous tripping time Instantaneous tripping...

 Open the catalog to page 10
EMCCB Catalog-11

Insulation spacer (removable) M8 screw Mounting hole Mounting dimension Power side 24 Load side 22.5 Test button Insulation spacer (removable) MCCB Mounting hole Test button Wiring limit MCCB

 Open the catalog to page 11
EMCCB Catalog-12

Mounting dimension Insulation spacer (removable) Mounting hole Neutral pole Test button Wiring limit Insulation spacer (removable) Mounting dimension MCCB Mounting hole

 Open the catalog to page 12
EMCCB Catalog-13

Remote control function is available via PC system if BM-E series with ETU-COM Communication function Data observe: + Model, series number, Certificate of Original, Production date. + Communication parameter: Potocal, Baud Rate, IP address + Operation condition: ON, OFF, Trip + Operation mode: Manual, Remote control + Last failure history: Failure phase, error mode, current on each phase when fault, fail time Data measuring: + Current on each phase: Ia, Ib, Ic, IN Data setting: + Overload long-time delay tripping current(Ir) & time(Tr) + Short-circuit short-time delay tripping current(Is) & time(Ts)...

 Open the catalog to page 13
EMCCB Catalog-14

1. ETU-COM module ETU-COM is required for communication function on BM-E series circuit breaker, The features as below: ETU-COM module Specification : + Protocol : RS485, ModBus-RTU + Baud Rate : 19200bps & 9600bps + IP address shall be different in the same network system + Data format : 1bit (Start) +8bit(Data)+ 1bit (even)+1bit(Stop) + Standard RS485 twisted pair communication cable + Max. 32 devices, 1200 meter. With RS485 repeater, more devices and distance can be made Connection between circuit breaker and ETU-COM + one ETU-COM connects to one circuit breaker with special cable + 2 meter...

 Open the catalog to page 14
EMCCB Catalog-15

Circuit breaker Connect with ETU-COM module & Manual Operation Device To motor operation device Terminal of Motor Operation Device Control voltage on Motor Operation Device Us=AC220VAC110VDC220VDC110VDC24V Connect with ETU-COM & ETU-HUB ( HUB is required for communication function) Connect with ETU-COM module & Manual Operation Device 6x RS485 port, Max. 5x ETU-COM ETU-HUB for communication port extending. Install on standard 35mm Din-rail Noted: Special cable required.

 Open the catalog to page 15
EMCCB Catalog-16

How to connect ETC-HUB and ETC-COM +Cable in 2 meter(Standard accessory of ETC-COM) +Connect between ETC-HUB and ETC-COM

 Open the catalog to page 16