ACB Catalog

ACB Catalog
1 / 56 PagesView full catalog

ACB Catalog

Product catalog summary
Overview
This document provides comprehensive technical specifications and operational instructions for the BW series air circuit breakers (ACB-OB) by Shihlin. These breakers are designed for AC circuits with voltages of 400V and 690V, supporting continuous currents from 630A to 6300A. They offer protection against overload, under-voltage, short-circuit, and single-phase earthing, enhancing power distribution reliability.
Specifications
The BW series includes fixed and drawout types, with motor-driven and manual operation options. Available in 3-pole and 4-pole configurations, they have a rated current range of 630A to 6300A with adjustable settings. The breakers operate at a voltage of AC 690V and an insulation voltage of AC 1000V, complying with IEC 60947-2 standards.
Intelligent Controller
The intelligent controller provides protection features such as overload long time-delay, short-circuit short time-delay, and instantaneous protection. It supports inverse time and definite time protection modes and includes a programming port and various status indicators.
Protection Features
Protection features include:
  • Overload Protection: Long time-delay trip protection with settable curves.
  • Short-Circuit Protection: Short time-delay and instantaneous protection with precise settings.
  • Earth Fault and Leakage Protection: Inverse time and definite time protection modes, with external transformer options.
Installation and Maintenance
Guidelines for mounting, usage, and maintenance are provided, including instructions for plugging and drawing out the breaker and regular maintenance procedures.
Accessories and Functions
Breakers can be equipped with accessories such as shunt release, undervoltage release, motor-driven mechanisms, and auxiliary contacts. Locking devices and optional accessories like under-voltage trip and ST-DP interface are also available.
Conclusion
The BW series air circuit breakers are versatile and reliable solutions for electrical distribution and protection, suitable for various applications with intelligent and selective protection features.
Inverse Time Delay Characteristics
The inverse time delay characteristic allows for adjustable curve slope and setting current values. If running currents recover after a sub-circuit overload and remain below a set value for 60 seconds, the controller restores the power supply.
Technical Parameters
Primary and secondary current values are provided for different patterns, outlining setting current values and output characteristics for non-making and delay relay making conditions.
Testing and Fault Management
Describes stimulation tests for tripping and non-tripping, fault recording, self-diagnosis, and thermal memory functions. The controller records fault data and manages overloads with thermal memory.
Programming and Interface Functions
The controller offers a programming interface for setting parameters, choosing protection curves, and managing communication protocols, including historical data recording and contact wear analogy calculation.
Characteristic Curves
Six types of overload protection characteristic curves are detailed, including standard, quick, and super inverse time curves, with formulas and examples for calculating delay times based on fault currents.
Specifications and Functional Overview
Detailed instructions for operating and configuring the KST45-2H model air circuit breaker, including lightening device display checks, functional window displays, and parameter settings.
Fault Occurrence and Time Indication
Procedure to identify fault occurrence time using a system clock function, displaying time in stages.
Simulation Test Methods
Outlines instantaneous trip and no trip simulation tests, including detailed steps for conducting these tests.
Self-Diagnose Fault Search
Explains how to search for self-diagnose fault codes using the controller, with a table of fault codes and descriptions.
System Clock Setting
Instructions for setting the system clock, including entering the clock set state and adjusting time settings.
Other Parameters Setting
Mentions setting communication settings and characteristic curves using a programmer, typically pre-set at the factory.
Communication State Display
Indicators for transmit (TxD) and receive (RxD) states show the communication status of the controller.
Breaker Handling
Instructions for plugging in and drawing out the breaker, emphasizing the need to disconnect before handling.
Maintenance
Routine maintenance tasks include cleaning, lubricating, and inspecting the contact system, with specific checks recommended after short-circuit events.
Regular Failures and Solutions
A table lists common issues with circuit breakers, their possible causes, and suggested solutions.
See more

Catalog excerpts

ACB Catalog-1

SHIHLIN ELECTRIC & ENGINEERING

 Open the catalog to page 1
ACB Catalog-3

6.1 Shunt release, Undervoltage release, Motor-driven mechanism, Closing electromagnet 7. Secondary connection diagram 7.1 M series intelligent controller 7.2 H series intelligent controller (Communication type) 8. Outline and installing dimension 8.1 Withdrawable circuit breaker 8.2 Fixed circuit breaker 9. Mounting, usage and maintenance 9.2 Usage of intelligent controller 9.3 Plugging into the breaker and drawing out the breaker 10. Regular failure and obviate methods

 Open the catalog to page 3
ACB Catalog-4

1. BW series specification Frame (AF) Fixed type Drawout type Fixed type Drawout type Drawout type Adjustable range of rated current (A) Max. rated operation voltage (Ue) V (50/60Hz) Rated insulation voltage (Ui) V (50/60Hz) Rated impulse withstand voltage (Uimp) kV Rated current of N pole (A) Rated breaking capacity (kA) Rated short time withstand capacity AC 400V (Icw) kA (1 sec) Electrical control type Standard type (M Type) Communication type (H Type) Mechanical life time (without Maintenance) Horizontal / Vertical Horizontal Vertical Auxiliary switch (Standard device) Motor drive Optional...

 Open the catalog to page 4
ACB Catalog-5

2.1 Purpose Shihlin's BW series of air circuit breakers (hereafter refers to as breaker) are available in the circuit of AC 50/60Hz with rated voltages of 400V, 690V and rated continuous current from 630A to 6300A. The BW offers electric energy distribution and circuit protection, making it the ideal solution for current supply device damages which made by overload, under-voltage, short-circuit and single-phase earthing in distribution network. It is suitable for intelligent and selective protection with accurate action to improve power distribution reliability and avoid unnecessary power cuts....

 Open the catalog to page 5
ACB Catalog-6

1. Primary circuit terminal (stationary) 2. Cradle 3. Shutter 4. Drawout handle 5. Secondary circuit terminal (movable) 6. Auxiliary contacts 11 7. Under-voltage release 8. Shunt release 9. Closing coil 10. Operation mechanism 11. Intelligent controller 12. Panel 13. Motor-driven mechanism

 Open the catalog to page 6
ACB Catalog-7

1. Mechanical reset button 設置 2. Rated current label 警報 ALARM MEMORY 3. Power meter window 4. Ammeter window 5. Protection category indicator 6. Status indicator 7. Function button 8. Position lock 9. Communication indicator 10. Programming port

 Open the catalog to page 7
ACB Catalog-8

4.1 Intelligent controller function 4.1.1 Protection features 4.1.1.1 Overload long time-delay trip protection features Table 1 for reference of technical parameters of overload long time-delay protection features Table 1: Technical parameters of overload long time-delay protection features Ir1 = In ___ Setting current value Distribution or motor protection Inverse time delay setting value tL (s) (corresponding to 2lr1) Operating characteristic Generator protection N-phase protection Inverse time-delay setting value tL (s) (corresponding to 2lr1) Characteristic curve Curve 1 ~ Curve 6* (settable)...

 Open the catalog to page 8
ACB Catalog-9

Short time protection has two modes: 1. Inverse time protection: when the fault current exceeds setting current value of definite time, if it is curve (1~5), controller protects according to the curve (1~5) of overload long time delay, but the speed 10 times of it. (In other words, it equals to the tenth of the delay tripping time, which computed from the overload long time curve expression.) If it's curve 6, then calculate the inverse time delay tripping time from the expression of short-circuit shot time delay curve 6 characteristic. 2. Definite time protection: when the fault current exceeds...

 Open the catalog to page 9
ACB Catalog-10

4.1.1.3 Short circuit instantaneous protection features Table 3: Technical parameters of short circuit instantaneous protection features Ir3 Setting current value Operating characteristic Actuation time > 1.15 Ir3 tripping < 100ms (Including original break time of the circuit-breaker) Note : If the controller is Frame I, the setting values of instantaneous protection is 1.01 ln ~ 50kA +OFF. If it is Frame II, that setting value is 1.01 ln ~ 75kA +OFF. And 1.01 ln ~ 100kA +OFF as Frame III. 4.1.1.4 Unsymmetrical earthing or leakage protection features Table 4: Technical parameters of Unsymmetrical...

 Open the catalog to page 10
ACB Catalog-11

There are two styles of above two protections: 1. Inverse time protection: TG=tG x KG x If / I In the expression: TG defines as delay actuation time of actual protection tG defines as setting value of definite time delay KG defines as coecient value of inverse time If defines as setting current value I defines as real working current Delay actuation time of inverse time protection could be obtained from above expression, but it is greater than or equal to setting value of definite time delay. It is definite time protection when KG is in OFF position. 2. Definite time protection: delay actuation...

 Open the catalog to page 11
ACB Catalog-12

(1) Specification of ZCT1 transformer Primary current Secondary current Note : 1. 200-400A/1A and 600-2000A/5A are customizable. 2. ZCT1 supplies bus bar through layout for Frame I. If ZCT1 is chosen for FrameII and Frame III, then use the way of pulling on cables. (2) Specification of ZT100 transformer Primary current Secondary current 4.1.1.5 Overload supervision and control protection features Table 5 for reference of technical specification of short circuit instantaneous protection features Controller is programmed output two passive signal contacts, which can charge of overload supervision...

 Open the catalog to page 12
ACB Catalog-13

Table 6 for reference of technical specification of imbalance current protection features Unbalance current and Loss of phase and 3-phase are protected by this imbalance current protection. Here is the expression of imbalance current ratio: =| l- lav| / lav ( lav is average of 3-phase) Imbalance current protection feature is a kind of definite time protection. The setting value of time delay use T mark, protection of imbalance currant with the function of alarming without tripping when T position. Table 6: Technical specification of imbalance current protection features = Setting value of imbalance...

 Open the catalog to page 13
ACB Catalog-14

4.1.2.6 MCR make-break and overstep tripping (optional) Make-break and overstep tripping protections are parts of back-up functions, which are optional. They are both instantaneous tripping actions whose tripping value relate to their service breaking and ultimate breaking capacities. Usually, MCR current is 40kA, 60kA, 80kA, overstep tripping current is 50kA, 75kA, 100kA The factory defaults of current values are 40/50kA for Frame I, 60/75kA for Frame II, 80/100kA for Frame III). Fault current signal sends out tripping instruction directly by hardware comparison circuit. MCR make-break protection...

 Open the catalog to page 14

All Shihlin Electric & Engineering Corporation catalogs and technical brochures

  1. AC drives

    15  Pages

  2. BHP Catalog

    8  Pages

  3. EMCCB Catalog

    20  Pages

Archived catalogs

  1. ACB/MCCB MCB/MS

    28  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.