1. Catalogs
  2. Shenzhen Socan Technologies Co.,Ltd
  3. SCD4 Series DC Leakage Current Sensor 10mA..100mA

SCD4 Series DC Leakage Current Sensor 10mA..100mA

SCD4 Series DC Leakage Current Sensor 10mA..100mA

Product catalog summary
Technical Specifications
  • Model Variants: SCD4-10mA, SCD4-20mA, SCD4-50mA, SCD4-100mA, SCD4-1A
  • Nominal RMS Current (Ipn): Ranges from 0 to ±10mA DC up to 0 to ±1A DC depending on the model.
  • Measuring Range (Ip): Extends from 0 to ±12mA DC up to 0 to ±1.2A DC.
  • Load Resistance (Rmax): ≥10kΩ
  • Output Voltage: ±5V
  • Working Voltage: DC ±12V (±5%)
  • Accuracy: ±1% at 25°C
  • Linearity: ±1% at 25°C
  • Offset Voltage: Less than ±150mV
  • Thermal Drift of Vo: Less than ±3mV/°C
  • Resolution: 10μA
  • Immunity to External Interference: Less than ±5mV when H=50A DC/m
  • Withstand Voltage: 3kVrms/50Hz/min
  • Current Consumption: Less than 13mA
  • Weight: 193g
  • Operating Temperature: -20 to +80°C
  • Storage Temperature: -40 to +85°C
  • Dimensions: Not specified
Instructions and Recommendations
  • The sensor uses non-contact measurement based on zero magnetic flux modulation and magnetic modulation principles, suitable for measuring small DC currents at the milliamp level.
  • The zero position output can be adjusted according to user needs.
  • Customizations for different current and voltage outputs are available upon request.
  • Handle the product with care as it is a precision measuring device.
  • The manufacturer reserves the right to modify the sensors without prior notice.
See more

Catalog excerpts

SCD4 Series DC Leakage Current Sensor 10mA..100mA-1

DC Leakage Current Sensor Technical parameters Model Parameters(25°C) Measuring Range (Ip) Load resistance Rmax Output Voltage Working voltage Accuracy @ Ta=25°C Linearity @ Ta=25°C Offset Voltage Thermal drift of Vo Resolution Immunity (to external interference) Weight Withstand voltage Current consumption Operating temperature Storage temperature Instructions 1.DC leakage current sensor adapt non-contact measurement, it is develop on the basis of the principle of zero magnetic flux modulation and magnetic modulation, it can measure small DC current MA level’s isolation in perforation measurement. 2.Zero position output of the sensor output can be adjusted according to user needs. 3.We can customize different current and voltage output according to user's requirements. Caution: This product is precision measuring device, please handle with care! SoCan reserve the rights to modify its s

 Open the catalog to page 1

All Shenzhen Socan Technologies Co.,Ltd catalogs and technical brochures

  1. SCB12-5A

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.