1. Catalogs
  2. Shenzhen Socan Technologies Co.,Ltd
  3. Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series

Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series

Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series

Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series

Product catalog summary
Product Description: The Split Core Hall Effect Current Sensor models SCY6 and SCY6R by Shenzhen SoCan Technologies Co., Ltd are designed for easy installation without disassembling the busbar. They utilize the Hall effect measurement principle in an open loop circuit mode and offer an isolation voltage greater than 3000VAC. These sensors comply with the UL94-V0 flame retardant rating and are equipped with automotive special connectors.
Features: The sensors can measure DC, AC, pulse, and various irregular waveform currents under isolation conditions. They offer a wide measurement range, fast response speed, low zero and temperature drift, high accuracy, and good linearity. They are optimized for dynamic performance when the busbar is fully filled with primary perforations and have strong resistance to external electromagnetic interference.
Applications: These sensors are suitable for use in communication power supplies, UPS systems, photovoltaic inverters, electric vehicle drives, and other products.
Implementation Standards: The sensors adhere to several standards including GB/T 7665-2005, JB/T 7490-2007, JB/T 25480-2010, JB/T 9473-2020, and SJ 20792-2000.
Technical Parameters: The sensors operate within an input power supply voltage range of ±11 to ±18 VDC, with a current consumption of up to 20 mA. They have a withstand resistance of 1000 MΩ at 500V DC and an output voltage of ±4V at ±IPN with a load resistance of 10KΩ. The accuracy and linearity are both ±1% at IPN and 25°C. The sensors have a response time of 3 to 5 microseconds and can operate in ambient temperatures ranging from -40°C to 125°C.
Model Specifications: The SCY6 and SCY6R models are available for primary currents of 50A, 100A, 200A, 300A, and 500A, with maximum peak values ranging from ±100A to ±1000A.
Notes: The document includes notes on size error, primary aperture, output terminal specifications, and wiring instructions to prevent sensor damage.
See more

Catalog excerpts

Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series-1

Split Core Hall effect Current Sensor SCY6, SCY6R Product description Features Based on Hall effect measurement principle, open loop circuit mode. The isolation voltage between primary and secondary is greater than 3000VAC. Can be opened and closed up and down, no need to disassemble the busbar, easy to install. Comply with UL94-V0 flame retardant rating. V0 Provide lead output and use automotive special connectors (SCY6R Series) e Performance It can measure DC, AC, pulse, and various irregular waveform currents of cable conductors waveform under isolation conditions. Wide measurement range, fast response speed, low zero drift, low temperature drift, high accuracy and good linearity. Dynamic performance (di/dt and response time) is optimal when the busbar i fully filled with is primary perforations. Strong ability to resist external electromagnetic interference (BCI, EFT, CS, CE, ESD, dv/dt, etc.). Application It can be widely used in communication power supply, UPS, photovoltaic inverter, electric vehicle drive and other products. Implementation standards GB/T 7665-2005 JB/T 7490-2007 JB/T 25480-2010 JB/T 9473-2020 SJ 20792-2000 Certification Shenzhen SoCan Technologies Co.,Ltd SoCan is committed to continuously improving product quality, and the company reserves the right to update its the products. m oc . na c os z s. w w w 1

 Open the catalog to page 1
Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series-2

Technical Parameters Model Primary Current (A)IPN Primary Current Max. Peak Value (A) IPM Output voltage (V) Vout @±IPN, L=10KΩ R Electrical Data Item Current consumption Ic Withstand resistance RINS @500V DC Output voltage Vout @IPN Input power supply voltage range Vc Output internal resistance ROUT Load Resistance RL Remark 3 Ambient operating temperature TA Ambient storage temperature Ts Response time tD @ 0→IPN (Remark 4) Withstand voltage VD@50Hz,60s,0.1mA Weight m Temperature Coefficient of Offset Voltage TCVOE Output voltage temperature coefficient Remarks: VC less than the minimum value...

 Open the catalog to page 2
Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series-3

maximum value will cause the measurement device to fail permanently. Shenzhen SoCan Technologies Co.,Ltd SoCan is committed to continuously improving product quality, and the company reserves the right to update its products. m oc . na c os z s. w w w 3

 Open the catalog to page 3
Open-loop Hall effect current sensor / AC / DC ø20, 50 - 500 A | SCY6 series-4

Notes: 1. Size error: ±1mm; 2. Primary aperture: φ21mm; 3. SCY6T output terminal: 2EDGVC-5.08-4P 4. SCY6R output interface: Amphenol BD-04AFMM-QL8XX 5. The IP indication direction is the positive direction of the current, OFS is the zero adjustment, and GIN is the output regulation; 6. Incorrect wiring may cause damage to the sensor. Shenzhen SoCan Technologies Co.,Ltd SoCan is committed to continuously improving product quality, and the company reserves the right to update its products. m oc . na c os z s. w w w 4

 Open the catalog to page 4

All Shenzhen Socan Technologies Co.,Ltd catalogs and technical brochures

  1. SCB12-5A

    1  Page

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.