EMC TEST REPORT For Shenzhen Consnant Technology Co., Ltd. Building B6, Junfeng Industrial Park, Yonghe Road, Fuhai Sub-District, Bao'an District, Shenzhen City, 518103 P.R.China. Test Model: APF-150A Note: This test report is limited to the above client company and the product model only. It may not be duplicated without prior written consent of Shenzhen BCT Technology Co., Ltd. This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com

Open the catalog to page 1
APF- EMC test report - 3

This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com Page 3 of 33

Open the catalog to page 3
APF- EMC test report - 4

1. GENERAL INFORMATION 1.1 Product Description for Equipment Under Test (EUT) Client Information Applicant: Shenzhen Consnant Technology Co., Ltd. Building B6, Junfeng Industrial Park, Yonghe Road, Fuhai Sub-District, Bao'an District, Shenzhen City, 518103 P.R.China. Shenzhen Consnant Technology Co., Ltd. Building B6, Junfeng Industrial Park, Yonghe Road, Fuhai Sub-District, Bao'an District, Shenzhen City, 518103 P.R.China. General Description of E.U.T EUT Description: Trade Name: EUT Model No.: Supplementary Model: Power Supply: Active Power Filter CONSNANT APF-150A APF-30A, APF-50A,...

Open the catalog to page 4
APF- EMC test report - 5

1.3 Description of Test Facility The test facility is recognized, certified, or accredited by the following organizations: EMC Lab. Description: There is one 10m semi-anechoic an area test sites and two line conducted labs for final test. The Open Area Test Sites and the Line Conducted labs are constructed and calibrated to meet the FCC requirements in documents ANSI C63.4 and CISPR 22/EN 61000 requirements. Name of Firm : CCIC Southern Electronic Product Testing (Shenzhen) Co., Ltd. Site Location : Electronic Testing Building, No.43 ShaHe Road, XiLi Street, Nanshan District, Shenzhen,...

Open the catalog to page 5
APF- EMC test report - 6

This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com

Open the catalog to page 6
APF- EMC test report - 7

Table 2: Test Equipment for Immunity Test This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com

Open the catalog to page 7
APF- EMC test report - 8

For the EUT described above. Table 1: Tests Carried Out Under EN IEC 61000-6-4:2019 V Indicates that the test is applicable x Indicates that the test is not applicable Note: This product is beyond the standard requirements, so refer to EN 61000-3-2 & EN 61000-3-3, and make the evaluation test results according to the customer requirements, meeting the requirements. This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com

Open the catalog to page 8
APF- EMC test report - 9

3.1 Measurement Uncertainty All measurements involve certain levels of uncertainties, especially in field of EMC. The factors contributing to uncertainties are spectrum analyzer, cable loss, antenna factor calibration, antenna directivity, antenna factor variation with height, antenna phase center variation, antenna factor frequency interpolation, measurement distance variation, site imperfections, mismatch (average), and system repeatability. The Treatment of Uncertainty in EMC Measurements, the best estimate of the uncertainty of a radiation emissions measurement is+4.0 dB. Note: (1) The...

Open the catalog to page 9
APF- EMC test report - 10

3.5 Test Procedure Maximizing procedure was performed on the highest emissions to ensure that the EUT complied with all installation combinations. All data was recorded in the peak detection mode. Quasi-peak readings performed only when an emission was found to be marginal (within -10 dB^V of specification limits), and are distinguished with a "QP" in the data table. 3.6 Corrected Amplitude & Margin Calculation The Corrected Amplitude is calculated by adding the Antenna Factor and Cable Factor, and subtracting the Amplifier Gain from the Amplitude reading. The basic equation is as follows:...

Open the catalog to page 10
APF- EMC test report - 11

Radiated Emission Measurement No. Mk. Freq. Reading Correct Measure- Limit Margin Antenna Table Height Degree degree consent Radiated Emission Measurement Reading Correcl Measure Limit Margin Antenna Table Height Degree degree comment This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com Page 11 of 33

Open the catalog to page 11
APF- EMC test report - 12

4.1. Measurement Uncertainty All measurements involve certain levels of uncertainties, especially in field of EMC. The factors contributing to uncertainties are spectrum analyzer, cable loss, and LISN. The Treatment of Uncertainty in EMC Measurements, the best estimate of the uncertainty of any conducted emissions measurement is +2.4 dB. 4.3. EUT Setup The setup of EUT is according with CISPR 16-2-1 measurement procedure. The specification used was the EN IEC 61000-6-4:2019 limits. The EUT was placed center and the back edge of the test table. The cables were draped along the test table and...

Open the catalog to page 12
APF- EMC test report - 13

4.5. Test Procedure During the conducted emission test, the EUT power cord was connected to the auxiliary outlet of the first Artificial Mains. Maximizing procedure was performed on the six (6) highest emissions to ensure EUT compliance using all installation combination. All data was recorded in the peak detection mode. Quasi-peak and Average readings were only performed when an emission was found to be marginal (within -10 dB ^ V of specification limits). Quasi-peak readings are distinguished with a "QP". Average readings are distinguished with a "AV". 4.6. Summary of Test Results...

Open the catalog to page 13
APF- EMC test report - 14

This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com

Open the catalog to page 14
APF- EMC test report - 15

5.2 Test StandardAccording to EN 61000-4-13: 2002+A2: 2016 & EN 61000-3-2: 20145.3 Test Data Overall Rasul: Class Multiplier This report shall not be reproduced except in full, without the written approval of Shenzhen BCT Technology Co., Ltd. Tel: 86-755-2947 5656 Fax: 86-755-2947 5655 http://www.bct-test.com

Open the catalog to page 15