  3. MS33 series 485 Communication Series Barometer Wiring Definition and MODBUS Protocol

MS33 series 485 Communication Series Barometer Wiring Definition and MODBUS Protocol

MS33 series 485 Communication Series Barometer Wiring Definition and MODBUS Protocol

MS33 series 485 Communication Series Barometer Wiring Definition and MODBUS Protocol

Product catalog summary
Overview: This document provides technical specifications and instructions for a pressure gauge using MODBUS protocol. It includes wiring instructions, communication settings, and command examples for operation.
Specifications:
  • Power Supply: Brown (12~24VDC), Blue (0V)
  • Communication: White (485A D+), Orange (485B D-)
  • Digital Output: Black
  • Default Baud Rate: 19200, with 1 start bit, 8 data bits, 2 stop bits, and no parity bit
  • Address Range: 1 to 247, default 18 (hexadecimal 12H)
MODBUS Functions:
  • 03H: Read Multiple Registers
  • 06H: Write Single Register
  • 10H: Write Multiple Registers
  • 04H: Read Air Pressure Value
Configuration Instructions:
  1. To change the address, press the MODE key for 2 seconds to enter the MENU, navigate to Addr, and adjust using up/down keys.
  2. To change the baud rate, enter the MENU, navigate to BAUD, and adjust with options 9600, 19200, 38400, 115200.
  3. To adjust stop bits, enter the MENU, navigate to SBit, and choose between 1 and 2.
  4. To set parity, enter the MENU, navigate to EOCH, and select NONE, ODD, or EVEN.
Register Descriptions:
  • Pressure Value: 10ms update, follows screen display
  • OUT Target Values: Upper and lower limits, output mode
  • Display Color Settings
  • Unit Settings: MPa, kPa, KGF, BAR, PSI
  • Reset and Normally Open/Closed Settings
Command Examples:
  • 03H Command: Host sends and pressure switch returns data
  • 06H Command: Host sends and pressure switch returns data
  • 10H Command: Host sends and pressure switch returns data
  • 04H Command: Host sends and pressure switch returns data
See more

Catalog excerpts

MS33 series 485 Communication Series Barometer Wiring Definition and MODBUS Protocol-1

485CommunicationPressureGague MODBUSProtocolAndWiringInstructions Brown12~24VDCBlue :0V White 485A D+ Orange 485B D-BlackDigitalswitchingoutput Data CRC Address Funtion DataFormat 8bit 8bit n*2*8 bit 16bit SingleFrame Thedefaultbaudrateis19200,with1startbit,8databits,2stopbits,andnoparitybit. TheaddressofPressureGaguecanbeadjustedfrom1to247,withadefaultvalueof18(hexadecimal12H). Format FunctionCode RegisterAddressDescription: Corresponding Pressurevalue (Followscreendisplay) Normallyopenand normallyclosed settingvalue Read /write PressureSwitch Ontologysettings - 101.0kPa~out1_up_value 0~2 Correspondingto EASY,HYS,WCMP 0~3 Correspondingto R_ON,G_ON,RED,GREEN LO - 1 MENUmode: OUT1 MENUmode: COLO UNIT MENUmode: no.nc Longpressthe upanddownkeys for3seconds

 Open the catalog to page 1
MS33 series 485 Communication Series Barometer Wiring Definition and MODBUS Protocol-2

03HCommandExample Hostsend DriveAddress FunctionCode High-order Low-order High-order Low-order Low-order High-order Pressureswitchreturn DriveAddress 12H FunctionCode 03H DataQuantity 04H High-order 00H Data1 Low-order 00H High-order 00H Data2 Low-order 00H Low-order D8H CRC High-order F2H High-order Low-order High-order Low-order Low-order High-order Pressureswitchreturn DriveAddress 12H FunctionCode 04H DataQuantity 02H High-order 00H Data1 Low-order 00H Low-order 3CH CRC High-order F3H High-order Low-order High-order Low-order Low-order High-order Pressureswitchreturn DriveAddress 12H FunctionCode...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.