Technical Features
The universal converter supports a wide range of inputs including thermocouples (types J, K, R, S, T, B, E, N), RTD (PT100, PT500, PT1000, Ni100) with 2, 3, or 4 wire connections, voltage (-150 to +150 mV, -30 to +30 V), current (-24 to +24 mA), and potentiometer (500 Ω to 10 KΩ). It outputs a 4 to 20 mA signal and is loop powered with a power supply range of 7 to 30 Vdc. The device features galvanic isolation of 1.5 kVac and operates within a temperature range of -20 to +65°C.
General Features
The converter is designed with a single input and output channel, consuming less than 660 mW of power. It is equipped with spring clamp connections compliant with EN 60175 standards and holds approvals from CE, EN 61000-6-4, EN 64000-6-2, and EN 61010-1.
Input Specifications
The device supports various input types with specific impedance values: thermocouples and voltage inputs have an impedance of 10 MΩ, while current inputs have an impedance of 40 Ω. The RTD/resistance inputs use an excitation current of 375 µA. The device includes cold junction compensation for thermocouples and settable fault sensor detection.
Output Specifications
The output is a loop-powered 4 to 20 mA signal with a load resistance of 1 KΩ at 28 Vdc and 21 mA. The resolution is 2 µA (< 13 bit), with output adjustments for over-range and fault conditions.
Configuration and Programming
Configuration is performed via the EASY-LP software using the S117P USB adapter. The software allows for easy setup and programming of the device.
Physical and Environmental Specifications
The converter measures 6.2 x 93.1 x 102.5 mm and operates within a temperature range of -20 to +65°C.
Order Information
The model K121 is the universal converter, and the programming kit includes the Easy-LP software and USB adapter.
See more

Catalog excerpts

Universal Converter-1

Universal Converter (RTD, TC, Ohm, mA, V) to 4..20mA (loop powered) Power supply 7..30 Vdc Universal Input Thermocouple (J,K,R,S,T,B,E,N) RTD (PT100-500-1000 Voltage -150…+150mV Current -24…+24mA Potentiometer 500 Resistance up to 1760 Output 4..20 mA (loop powered Galvanic isolation 1,5 kVac Configuration Through EASY-LP software (s117p Operating temperature -20..+65 °C For further information, please visit www.seneca.it 1000-Ni100) with 2,3,4 wire connections 150mV, -30…+30V -10 K powered)

 Open the catalog to page 1
Universal Converter-2

TECHNICAL FEATURES GENERAL FEATURES Power supply 7..30 Vdc Channels number 1 input, 1 outputs Galvanic isolation 1.5 kVac, 2 ways Power supply on side terminals Yes Power consumption < 660 mW SCHEMES, PROGRAMMING Dimensions (wxhxd) 6.2 x 93.1 x 102,5 mm Operating temperature -20..+65°C Connections Spring clamps (EN 60175) Approvals CE, EN 61000-6-4, EN 64000-6-2, EN 61010-1 INPUT Channels 1 Potentiometer From 500 to 10 K, Input impedance 10 M INPUTS Type J,K,R,S,T,B,E,N, Input impedance 10 M, cold junction compensation -40 ..65 ± 1,5°C Settable, fault sensor detection settable Thermocouple Type...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.