Fire Fighting Pumps
6Pages

{{requestButtons}}

Catalog excerpts

Fire Fighting Pumps - 2

• What isNFPA? NFPA (National Fire Protection Association); it is the American Fire Protection Association that our company is located in the membership. It's the world's most cited and respected institution when compared to other standards. To minimize the effects of fire and other risks, occured more than 300 codes and standards. NFPA (National Fire Protection Association); firmamizin da uyeliginin bulundugu Amerikan Yangtndan Korunma Kurumu'dur. Diger standartlarla kar§iSa§tmldiginda diinyada en fazla kaynak gdsterilen ve itibar edilen kurulu$tur. Yangin ve diger risklerin etkilerini en...

Open the catalog to page 2
Fire Fighting Pumps - 3

• Performance Features of Fire Fighting Pumps According to NFPA 20 ♦ According to NFPA 20 fire pump characteristic curve is determined by three points: 1 - Closed discharge pressure (Shut-off): The pump's off discharge pressure (zero flow valve turned off status) must not more than 140% of the rated pressure. 2- Nominal value (Rated): The pump characteristic curve must pass the intersection point or upside that point of nominal flow rate and nominal pressure. 3- Maximum Load (Overload): If required, pump capacity must be reach to %150 of operated capacity. In %150 of operated capacity,...

Open the catalog to page 3
Fire Fighting Pumps - 4

Used Pumps on Fire Figh In a fire fighting system, pumps can be different types: • Multi Stage Pumps (ARS, ARS-D) • Single Stage Pumps (TKF) • Single Stage In-Line Pumps (TKF-I) ■ Double Suction Pumps (SCE) ■ Boosters (SPL,SPS) Ya ng i n Pom pasinda Ku llamlabilen Pom pa I a r • Tek Kademeli In-Line Pompalar(TKF-l) • £ift Emi§li Pompalar (SCE) - Hidrofor (SPL, SPS) Type Tip • Jockey pump capacity must be at least 1 gpm or allowable leakage should be meet the required level pressure * within 10 minutes. • Should not be lower than the required minimum pressure for fire fighting system.

Open the catalog to page 4
Fire Fighting Pumps - 5

rj SEMPA • ElektrikMotorlari • Motors shall comply with NEMA MG-1 standards. • Motors should be designed for continuous duty. • Motor service factor should be less than 1.15 according to NEMA MG-1 standard. • In place where the risk of water splatter exist, motors shall be totally closed. • Even if the power supply fails, there must be safety power line for supply electric to motor. • If the system electric supply from Generator, it must be designed according to NFPA37 and NFPA110 Type 10. • NEMA MG-1 standartlarina uygun olmalidir. • Motorlar surekli ?ali$ma kojullarina gore tasarlanmi§...

Open the catalog to page 5
Fire Fighting Pumps - 6

rj SEMPA • Dizel Motorlari • Fire pump diesel engine should be compression-ignition type. Spark-ignition (natural gas, propane, fuel, etc.) internal-combustion engines are not used. • Reliable, first-class and must be designed for fire extinguishing systems. • Reference level: 100 m height from sea-level and 25 C ambient temperature. • Height; 3% power drop for every 300 m. above from reference height. • Ambient temperature, 3% power drop for every 5 °C above from reference temperature. • Diesel motor power must be at least 10% overload-reserved. • Pump and engine shall be coupled viia...

Open the catalog to page 6