1. Catalogs
  2. Schweitzer Engineering Laboratories
  3. SEL-734B Advanced Monitoring and Control System

SEL-734B Advanced Monitoring and Control System

SEL-734B Advanced Monitoring and Control System
1 / 12 PagesView full catalog

SEL-734B Advanced Monitoring and Control System

Product catalog summary
Major Features and Benefits
The SEL-734B integrates volt/VAR based capacitor bank control with power quality monitoring and advanced reporting. It features low-energy analog inputs for voltage and current sensing, adaptable for various applications. Preconfigured control strategies and plug-and-play configurations enhance usability. Advanced power quality monitoring includes harmonic measurements, load profile trending, and waveform capture.
Enclosure Options
Compact Enclosure: Provides single-phase monitoring and three-pole control in a small outdoor enclosure, supporting various control strategies such as voltage, kVAR, power factor, and current. Features include SCADA, auto, and manual control modes, adaptive processing, and a neutral unbalance alarm.
Full-Size Enclosure: Allows three-phase monitoring and control with options for ganged or individual phase control, additional space for accessories, and supports advanced control strategies.
Interface Options
Both compact and full-size enclosures offer multiple interface options for easy integration. The compact enclosure includes socket-based and connectorized options, while the full-size enclosure offers combined and individual sensor connectors.
Specifications
The SEL-734B is designed under an ISO 9001 certified system, complying with various safety and emissions standards. It provides accurate instantaneous metering and monitoring, with specific accuracy levels for power, reactive power, and harmonic measurements. The device operates within a wide temperature range and supports high durability and safety standards.
Control Features
Control strategies vary by enclosure type, with options for ganged and individual phase control, voltage and kVAR control, and more. Features include adaptive processing, fault detection, and integrated power supply options.
Physical and Environmental Specifications
The device is designed to operate in harsh environments, with high humidity and altitude limits. It is available in different sizes and weights depending on the enclosure model, and it meets rigorous dielectric and processing specifications.
Type Tests
The SEL-734B has undergone extensive electromagnetic compatibility and immunity testing, ensuring robust performance in various electrical environments.
Electromagnetic Compatibility
  • Electrostatic Discharge Immunity: Complies with IEC 61000-4-2:2008 and IEC 60255-22-2:2008, Severity Level 4 for both polarities at Levels 1, 2, 3, and 4.
  • Radiated Radio Frequency Immunity: Meets IEC 61000-4-3:2010 at Severity Level X (15 V/m) and IEC 60255-22-3:2007 at Severity Level 3 (10 V/m). ANSI C12.20 (1998) specifies Severity Level 15 V/m.
  • Conducted Radio Frequency Immunity: IEC 61000-4-6:2008, Severity Level 3.
  • Fast Transient/Burst Immunity: IEC 61000-4-4:2011, Severity Level 4.
Environmental Tests
  • Cold: IEC 60068-2-1:2007, 16 hours at –40°C.
  • Dry Heat: IEC 60068-2-2:2007, 16 hours at +85°C for SEL-734B device, and 16 hours at +70°C for device in cabinet.
  • Damp Heat, Cyclic: IEC 60068-2-30:2005, 25° to 55°C, 6 cycles, 95% humidity.
  • Enclosure Protection: IEC 60529:2001, IP45.
  • Seismic: IEC 60255-21-3:1993, Class 2 Response (Method A).
Safety
  • Dielectric Strength/Impulse: IEC 60255-5:2000, 2.5 kVac on ac current inputs, contact inputs, and contact outputs; 3.1 kVdc on power supply; 2.2 kVdc on EIA-485 port for 60 sec.
  • High-Voltage Line Surges: IEC 61000-4-5:2005, Level 4 (4 kV) on LEA voltage measurement inputs and power supply inputs; Level 2 (1 kV) on LEA current measurement inputs and auxiliary circuits.
  • Impulse Voltage Test: IEC 60060-1, 4 kV on power supply, ac current inputs, and voltage inputs.
Additional Information
  • All ratings apply to the SEL-734B device unless specified otherwise.
  • Product covered by the standard SEL 10-year warranty.
See more

Catalog excerpts

SEL-734B Advanced Monitoring and Control System-1

SEL-734B Data Sheet Advanced Monitoring and Control System Compact Enclosure Full-Size Enclosure Major Features and Benefits The SEL-734B combines volt/VAR based capacitor bank control with power quality monitoring and advanced reporting through Ethernet and multiple serial ports. The standard SEL-734B includes low-energy analog (LEA) inputs for voltage and current sensing. ➤ One Controller, Many Applications. The SEL-734B adapts to multiple applications ranging from basic three-pole control to intelligent single-pole control. Configurable logic and integrated communications ensure that the SEL-734B supports future system demands. ➤ Preconfigured Control Strategies. SEL offers a selection of ACSELERATOR QuickSet® SEL-5030 Software templates that support control strategies from basic voltage-based control to advanced singlepole kVAR control with voltage override. ➤ Plug-and-Play Configurations. SEL offers full-size and compact enclosures which install in many types of sites. Rugged military-grade cables allow direct connections from the SEL-734B controller to line-post sensors and capacitor switches. ➤ Advanced Power Quality Monitoring and Trending. All SEL-734B models include harmonic measurements, load profile trending, voltage sag/swell/interruption (VSSI) recording, and waveform capture. The Advanced Power Quality and Monitoring option measures harmonics to the 50th order, captures waveforms at 8 kHz, and offers 192 channels of profile trending. ➤ SEL DNA™ (Distribution Network Automation) Ready. Capacitor controls are integral to systemwide volt/VAR control schemes. The SEL-734B integrates seamlessly into system-wide distribution control schemes to linearize voltage profiles and minimize VAR-induced I2R losses. Schweitzer Engineering Laboratories, Inc.

 Open the catalog to page 1
SEL-734B Advanced Monitoring and Control System-2

SEL-734B Compact Enclosure Applications The compact enclosure provides single-phase monitoring and three-pole control in a small 12" x 10" outdoor fiberglass enclosure. The socket-based enclosure is available in two different 6-jaw form factors and one 4-jaw form factor. The Connectorized® enclosure has a 7-pin circular connector on the bottom for a control and measurement cable connection to a junction box. Control Strategies The compact enclosure supports the following capacitor bank control strategies: ➤ Voltage ➤ kVAR* ➤ Power Factor* ➤ Current* ➤ Time of Day SCADA, Auto, and Manual control...

 Open the catalog to page 2
SEL-734B Advanced Monitoring and Control System-3

Figure 2 Compact Enclosure Rear Plug and Meter Socket Table 1 Socket Stab Configurationsa Socket Stab Number and Function

 Open the catalog to page 3
SEL-734B Advanced Monitoring and Control System-4

SEL-734B Full-Size Enclosure Applications The full-size enclosure allows three-phase monitoring and ganged three-phase or individual phase control. Two enclosure styles offer flexibility: a combined sensor connector option and an individual sensor connector option. The combined sensor connector is intended for threephase monitoring. Individual sensor connectors provide the option of single-phase monitoring or three-phase monitoring. Control Strategies SCADA, Auto, and Manual control modes Front-panel control and indicators Hunting prevention DC backup UPS Sensor phase and magnitude correction...

 Open the catalog to page 4
SEL-734B Advanced Monitoring and Control System-5

Interface Options The following field interfaces are available in the full-size enclosure: > Combined sensor connector > Individual sensor connectors Combined Sensor Connector The enclosure contains one 14-pin connector for all sensors and one 19-pin connector for three control switches. The 14-pin connector connects to three primary current/voltage sensors and one neutral current sensor. The 19-pin connector connects to three capacitor bank switches. Table 3 14-Pin Sensor Connector Assignment Pin Number Description Keyed Connectors Reserved Reserved Neutral Sensor, Positive Polarity Neutral...

 Open the catalog to page 5
SEL-734B Advanced Monitoring and Control System-6

Individual Sensor Connectors Three 4-pin connectors, located on the bottom of the enclosure, route each measurement signal to the SEL-734B. Operators can choose to use one, two, or all three sensor inputs. Settings allow you to configure the SEL-734B for a different number of sensors. The enclosure contains the following connectors: ► Three 4-pin connectors connect to each primary sensor ► One 4-pin connector connects to a neutral current sensor and a 120 Vac control power transformer (CPT) ► One 19-pin connector connects to three capacitor bank switches Schweitzer Engineering Laboratories, Inc....

 Open the catalog to page 6
SEL-734B Advanced Monitoring and Control System-7

Table 8 provides a complete reference about the available options. Table 8 Control Features of Enclosure Models Schweitzer Engineering Laboratories, Inc.

 Open the catalog to page 7
SEL-734B Advanced Monitoring and Control System-8

Compliance Designed and manufactured under an ISO 9001 certified quality management system Radiated Emissions: FCC Part 15; Class A SEL-734B Device: UL Listed to U.S. and Canadian safety standards (File E212775, File E220228; NRAQ, NRAQ7, File E475839; NRAG, NRAG7, File E470448) Instantaneous Metering/Monitoring Instantaneous (25 ms): Accuracies are specified at 23°C and at nominal system frequency unless noted otherwise. Frequency: ±0.01 Hz 15 Vdc Integrated Power Supply Continuous Operating Limits Rated Input Voltage: Input Voltage Range: Input Current: Output Voltage: Output Current:...

 Open the catalog to page 8
SEL-734B Advanced Monitoring and Control System-9

Rated Insulation Voltage: 300 V Type TestsElectromagnetic Compatibility Immunity Surge Withstand Capability: (-4° to +158°F) Device in Compact Enclosure With Integrated 15 Vdc Power Supply 0 W of Accessories: -40° to +65°C (^0° to +149°F) Without Direct Sunlight: Increase max. temperatures by 15°C (27°F) Device in Full-Size Enclosure 0 W of Accessories: -40° to +70°C (^0° to +158°F) With UPS (Supercapacitor): Decrease max. temperatures by 10°C (18°F) Without Direct Sunlight: Increase max. temperatures by 15°C (27°F) Operating Environment Pollution Degree: 2 (SEL-734B Device) Surge...

 Open the catalog to page 9
SEL-734B Advanced Monitoring and Control System-10

Safety Dielectric Strength/Impulse: IEEE C62.41:2002 Location Category B (6 kV) on LEA voltage measurement inputs and power supply inputs IEC 61000-4-5:2005 Level 2 (1 kV) on LEA current measurement inputs and auxiliary circuits IEC 60060-1 4 kV on power supply, ac current inputs, and voltage inputs Elec. relays, Part 5: Insulation, Section 6: 2.5 kVac on ac current inputs, contact inputs, and contact outputs 3.1 kVdc on power supply 2.2 kVdc on EIA-485 port for 60 sec. Severity: 2500 Vac on analog inputs, contact Impulse Voltage Test: inputs, and contact outputs 3100 Vdc on power supply IEC...