SEL-387A Current Differential and Overcurrent Protection Relay

SEL-387A Current Differential and Overcurrent Protection Relay
1 / 16 PagesView full catalog

SEL-387A Current Differential and Overcurrent Protection Relay

Product catalog summary
Major Features and Benefits
The SEL-387A Relay offers differential protection for two terminals, incorporating harmonic elements for security during transformer energization and overexcitation. It includes overcurrent elements for backup protection, oscillographic event reports, and monitoring features such as a circuit breaker contact wear monitor and substation battery voltage monitor. The relay provides four communication ports, a local display panel, and optional expanded I/O and restricted earth fault elements for sensitive protection.
Protection
The relay protects transformers, buses, generators, and reactors using differential and overcurrent protection. It features single- or dual-slope percentage differential restraint characteristics for security during through-fault conditions.
Metering
The relay provides instantaneous measurements of phase and demand current, with recorded peak demand data for system EMS/SCADA applications.
Monitoring
Features include breaker maintenance scheduling, substation battery voltage monitoring, and critical operating temperature monitoring using the SEL-2600 RTD Module.
Automation
Automation features include local and remote control, latch control, and serial communications for efficient data transmission. Optional DNP3 Level 2 Slave protocol is available for SCADA system interface.
Relay and Logic Settings Software
The ACSELERATOR QuickSet® SEL-5030 Software reduces engineering costs for relay settings and logic programming, with a built-in HMI for commissioning and troubleshooting support.
Functional Overview
The SEL-387A includes protective elements and control logic for two-winding power transformers, reactors, and generators. It features current differential elements with percentage restraint and harmonic blocking elements, optional sensitive restricted earth fault elements, and overcurrent elements.
Current Differential Elements
The relay has three differential elements with single- or dual-slope percentage differential characteristics to handle CT errors and prevent undesired operation during heavy external faults.
Restricted Earth Fault Protection
Optional REF elements provide sensitive detection of internal ground faults, comparing neutral current and winding residual current directions.
Overcurrent Protection
The relay includes 11 overcurrent elements for each set of 3-phase current input windings, with torque-controlled and non-torque-controlled elements for phase identification and protection.
Temperature Measurement
The SEL-387A accepts up to 24 RTD inputs for temperature monitoring, with alarm thresholds for high temperature levels.
Metering and Monitoring
The relay offers fundamental frequency metering functions, including instantaneous, demand, and peak demand metering, with harmonic metering up to the 15th harmonic.
Event Reporting and Sequential Events Recorder (SER)
Event reports and SER features aid in post-fault analysis and relay settings testing. The relay stores event report data and provides detailed reports for winding, digital, differential, and raw events.
Substation Battery Monitor
The relay measures and reports substation battery voltage, with programmable threshold comparators for alarm and control.
Breaker Contact Wear Monitor
The relay monitors breaker wear by capturing interrupted current and operation count, initiating alarms when thresholds are exceeded.
Through-Fault Event Monitor
The relay monitors through faults, which are external overcurrent events, to assess stress on the apparatus.
Overview
The document provides detailed technical specifications and operational guidelines for the SEL-387A relay by Schweitzer Engineering Laboratories, Inc. It covers aspects such as through-fault monitoring, relay settings, automation, control logic, and communication protocols.
Through-Fault Monitoring
The SEL-387A relay monitors through-fault currents that can cause mechanical damage and thermal wear to transformers. It records current levels, duration, and timestamps for each event, calculating a cumulative I2t value per phase. This data aids in scheduling maintenance and justifying mitigation efforts.
Relay and Logic Setting Software
The ACSELERATOR QuickSet software, compatible with Microsoft Windows, facilitates the configuration and analysis of the SEL-387A relay. It allows offline settings development, online help for configuration, and event analysis with waveform and harmonic tools. The software also supports monitoring and testing of the relay.
Automation and Serial Communications
The SEL-387A features four serial ports for communication, supporting ASCII and binary protocols. It can connect to various devices like computers, modems, and SCADA systems, enabling remote and local communication.
Control Logic and Integration
The relay replaces traditional control switches and latching relays with programmable SELOGIC control equations. It includes 16 local and remote control switches, latch control switches, and programmable displays for system status and relay conditions.
Unique Capabilities
Advanced SELOGIC control equations allow for flexible relay output assignments. The relay supports six independent setting groups for operational flexibility, adapting to different system conditions and contingencies.
Front-Panel User Interface
The SEL-387A features a user interface with an LCD, LED indicators, and pushbuttons for local communication. The interface displays event, metering, and status information, with error messages taking precedence over default displays.
Specifications
The relay is designed under ISO 9001 standards, with UL and CE certifications. It includes detailed specifications for terminal connections, AC current inputs, power supply, and output contacts, ensuring reliable performance under various conditions.
Specifications
The document outlines the specifications for a high-current interrupting option with various voltage and current ratings. It includes details on make and carry capacities, MOV protection, pickup and dropout times, and breaking capacity for different voltages. The cyclic capacity is also specified, with a note on polarity dependence for high current interrupting output contacts.
Optoisolated Inputs
The document specifies the pickup and dropout voltage ranges for various Vdc inputs, along with the current draw at nominal input voltage.
Routine Dielectric Strength
AC current inputs are tested at 2500 Vac for 10 seconds, while power supply, optoisolated inputs, and output contacts are tested at 3100 Vdc for 10 seconds.
Frequency and Rotation
The system operates at 50 or 60 Hz with phase rotation options of ABC or ACB.
Communications Ports
The device includes EIA-232 and EIA-485 ports with specified isolation and baud rates.
Operating Temperature
The device operates within a temperature range of –40°C to +85°C.
Type Tests
The document lists various emissions, environmental, dielectric strength, impulse, electrostatic discharge, RFI, interference, vibration, and shock tests that the device complies with.
Processing Specifications
The device processes 64 samples per power system cycle with specified metering accuracy for different models.
Relay Elements
Details on differential elements, winding instantaneous/definite-time overcurrent elements, and winding time overcurrent elements are provided, including pickup ranges, accuracies, and time delay specifications.
Warranty and Contact Information
The product is covered by a standard SEL 10-year warranty, with contact information for Schweitzer Engineering Laboratories, Inc. provided.
See more

Catalog excerpts

SEL-387A Current Differential and Overcurrent Protection Relay-1

SEL-387A Current Differential and Overcurrent Protection Relay Versatile Solution for Power Apparatus Protection Major Features and Benefits The SEL-387A Relay offers restrained and unrestrained differential protection for two terminals. Second-, fourth-, and fifth-harmonic elements, augmented by the dc element, provide security during transformer energization and overexcitation conditions in a user-defined choice of either harmonic restraint or harmonic blocking. Overcurrent elements provide backup protection that contributes to the versatility of the SEL-387A. Oscillographic event reports, Sequential Events Recorder (SER), circuit breaker contact wear monitor, and substation battery voltage monitor are all standard features. Four communications ports, local display panel, and extensive automation features are also standard. Expanded I/O is available as an option. Two optional restricted earth fault elements provide sensitive protection against earth faults for wye-connected transformers. ➤ Protection. Protect transformers, buses, generators, reactors, and other apparatus with a combination of differential and overcurrent protection. The differential element is set with either a single- or dual-slope percentage differential restraint characteristic for increased security during through-fault conditions. ➤ Metering. Interrogate the relay for instantaneous measurements of phase and demand current. The recorded peak demand, including the date and time of occurrence, is provided. Use accurate metering data for system EMS/SCADA applications. ➤ Monitoring. Schedule breaker maintenance when breaker monitor indicates. Notify personnel of substation battery voltage problems. Monitor critical operating temperatures using the SEL-2600 RTD Module. Use the SEL-387A through-fault event monitor for information on system through faults and resulting cumulative I2t wear on transformer banks. Monitor critical operating temperatures through use of the SEL-2600. ➤ Automation. Take advantage of automation features that include 16 elements for each of the following: local control and local indication with front-panel LCD and pushbuttons, remote control, and latch control. Use the serial communications ports for efficient transmission of key information including metering data, protection elements and contact I/O status, SER reports, breaker contact wear monitor, relay summary event reports, and time synchronization. Select optional DNP3 Level 2 Slave protocol with virtual terminal support for SCADA system interface capability. ➤ Relay and Logic Settings Software. ACSELERATOR QuickSet® SEL-5030 Software reduces engineering costs for relay settings and logic programming. The built-in Human Machine Interface (HMI) provides phasor diagrams that help support commissioning and troubleshooting. Schweitzer Engineering Laboratories, Inc.

 Open the catalog to page 1
SEL-387A Current Differential and Overcurrent Protection Relay-2

Overcurrent ■ Phase • Ground • Neg. Seq. 51G -Overcurrent • Phase • Ground • Neg. Seq. Overcurrent • Ground -Overcurrent Fault (REF)* • Ground Overcurrent • Phase ■ Ground • Neg. Seq. Time-Overcurrent • Phase • Ground • Neg. Seq. • SELogic® Control Equations • Event Reports • Sequential Events Recorder • Breaker Wear Monitor • Station Battery Monitor • ASCII, Binary, and Distributed Port Switch Communication • Remote and Local Control Switches • Phase, Ground, Neg. Seq., Differential, and Harmonic Metering • Restrained and Unrestrained Differential Elements • Second- and Fourth-Harmonic Blocking...

 Open the catalog to page 2
SEL-387A Current Differential and Overcurrent Protection Relay-3

overexcitation conditions. Even-harmonic elements (second and fourth harmonic) provide security against inrush currents during transformer energization, complemented by the dc element, which measures the dc offset. The even-harmonic element offers the choice between harmonic blocking and harmonic restraint. In the blocking mode, the user selects either blocking on an individual phase basis or on a common basis, as per application and philosophy. The second-, fourth-, and fifth-harmonic thresholds are set independently, and the dc blocking and harmonic restraint features are enabled independently. An...

 Open the catalog to page 3
SEL-387A Current Differential and Overcurrent Protection Relay-4

Table 2 Metering Capabilities Metering Capabilities The SEL-387A provides three types of fundamental frequency metering functions: instantaneous, demand (thermal), and peak demand. Metered quantities shown in Table 2 include phase currents for both winding inputs; positive-, negative-, and zero-sequence (residual) currents for both winding inputs; and operate, restraint, second-harmonic, and fifth-harmonic currents for the three differential elements. Harmonic metering provides a snapshot of harmonic current magnitudes in the phase currents, including the fundamental and harmonic components through...

 Open the catalog to page 4
SEL-387A Current Differential and Overcurrent Protection Relay-5

The typical settings shown in Figure 4 are Set Point 1, Set Point 2, and Set Point 3. Set Point 1 approximates the continuous load current rating of the breaker. Set Point 3 is the maximum rated interrupting current for the particular breaker. Set Point 2 is some intermediate current value that provides the closest visual “fit” to the manufacturer’s curve. Figure 3 Transformer Energizing Inrush Current Plotted From Event Report Substation Battery Monitor for DC Quality Assurance The SEL-387A measures and reports the substation battery voltage presented to its power supply terminals. The relay...

 Open the catalog to page 5
SEL-387A Current Differential and Overcurrent Protection Relay-6

Relay and Logic Setting Software The ACSELERATOR QuickSet software uses the Microsoft® Windows® operating system to simplify settings and provide analysis support for the SEL-387A. One can, for instance, open an ACSELERATOR HMI screen and obtain phasor information similar to that shown in Figure 5. SEL-5030 HMI Screen Showing SEL-387 Phasor Information Use the ACSELERATOR QuickSet software to create and manage relay settings: ➤ Develop settings off-line with an intelligent settings editor that only allows valid settings. ➤ Use on-line help to assist with configuration of proper settings. ➤ Organize...

 Open the catalog to page 6