1. Catalogs
  2. Schweitzer Engineering Laboratories
  3. SEL-2664S Stator Ground Protection Relay

SEL-2664S Stator Ground Protection Relay

SEL-2664S Stator Ground Protection Relay
1 / 16 PagesView full catalog

SEL-2664S Stator Ground Protection Relay

Product catalog summary
Overview: The SEL-2664S Stator Ground Protection Relay by Schweitzer Engineering Laboratories is designed to provide comprehensive protection, metering, monitoring, control, and communication for generators. It ensures 100% stator ground fault protection using a multifrequency injection method, applicable during all operational phases including startup and offline periods.
Major Features and Benefits:
  • Protection and Control: Offers protection against stator ground, neutral overvoltage, and grounding resistor faults. It also provides rotor field insulation fault protection when paired with the SEL-2664 Field Ground Module.
  • Operator Controls: Includes multiple access methods with eight status LEDs and a TARGET RESET pushbutton.
  • Software Integration: Utilizes ACSELERATOR QuickSet® SEL-5030 Software for efficient relay settings and logic programming.
  • Metering and Monitoring: Built-in functions eliminate the need for separate metering devices, offering detailed diagnostic reports.
  • Control Inputs and Outputs: Features two control inputs and four contact outputs for enhanced control and status indication.
  • Communications: Supports multiple protocols including Modbus, DNP3, and IEC 61850, with various communication ports.
Protection and Control Features:
  • 100% Stator Ground Protection: Utilizes multisine signal injection for comprehensive protection without blind periods.
  • Rotor Field Ground Protection: Detects field ground faults using a switched DC voltage injection method.
  • Neutral Overvoltage Protection: Provides two neutral overvoltage elements for comprehensive protection.
  • Neutral Ground Resistor Monitor: Monitors the generator neutral grounding resistor for faults.
Metering and Monitoring:
  • Provides detailed metering for neutral voltage, current, and insulation resistance.
  • Profile report monitoring offers periodic snapshots of up to 17 selectable analog quantities.
Automation and Integration:
  • Features flexible control logic with three serial ports and dual fiber Ethernet ports.
  • Supports various communication protocols for seamless integration with external systems.
Operator Controls and Software:
  • Multiple access methods with status LEDs and a reset button.
  • ACSELERATOR QuickSet software simplifies settings management and analysis.
Applications: The SEL-2664S can be used with or without a distribution transformer, with flexible CT connections for various configurations.
Technical Specifications: The document provides detailed technical specifications and connection diagrams for the SEL-2664S relay, including AC and DC connections, protection features, automation capabilities, communication protocols, and hardware specifications.
AC Connections: Describes configurations for AC connections, including the use of neutral ground resistors and current transformers on both primary and secondary sides of grounding transformers.
Protection and Control: Offers fundamental and RMS neutral overvoltage protection, neutral ground resistance monitoring, and stator and rotor field ground protection using a four-frequency injection source.
Automation and Communication: Supports eight remote control logic points, SELOGIC control equations, and various communication protocols with multiple communication ports.
Monitoring and Reporting: Provides profile report monitoring, event summaries, and detailed event reports, including a sequential events recorder (SER) with data storage in nonvolatile flash memory.
Hardware Specifications: Operates within a temperature range of -40°C to +85°C and supports power supply voltages of 120/240 Vac or 125/250 Vdc. Includes eight target LEDs and a front-panel interface for operator control.
Environmental and Compliance: Meets various environmental and compliance standards, including IP65 enclosure protection, vibration and shock resistance, and EMC immunity. Manufactured under an ISO 9001 certified quality management system.
Dimensions and Mounting: Provides dimensions and mounting options for wall, panel, and rack installations, along with weight specifications for each configuration.
Digital Filtering and Oscillography: Analog quantities are calculated every 1/4 cycle over 640 samples, with protection and control processing occurring four times per power system cycle. The system records 180 cycles at a sampling rate of 32 samples per cycle.
Relay Elements: Includes specifications for stator ground, neutral grounding resistor, neutral fundamental overvoltage, neutral RMS overvoltage, and rotor field ground protection.
Metering: Specifies accuracies for various parameters including injection source current, neutral current, stator ground insulation resistance, rotor field insulation resistance, and neutral voltage.
Legal and Warranty Information: The document is © 2014 by Schweitzer Engineering Laboratories, Inc. All rights reserved. The product is covered by the standard SEL 10-year warranty.
See more

Catalog excerpts

SEL-2664S Stator Ground Protection Relay-1

SEL-2664S Stator Ground Protection Relay 100% Stator Ground Fault Protection 100% of the Time Major Features and Benefits The SEL-2664S Stator Ground Protection Relay provides an exceptional combination of protection, metering, monitoring, control, and communications in a compact industrial package. ➤ Standard Protection and Control Features. Protect your generator against stator ground, neutral overvoltage, and grounding resistor faults. When used with an SEL-2664 Field Ground Module, the SEL-2664S Relay protects against rotor field insulation faults to ground. The stator ground protection works for 100 percent of the stator winding and for all operating conditions, including when the generator is starting, ramping, or offline using a novel multifrequency injection method in conjunction with the neutral overvoltage elements. Operator Controls. Take advantage of multiple methods for accessing and using the operator interface of the relay. The front and side panels have eight LEDs that indicate the ENABLED, TRIP, WARNING, 64S, 64F, 59N, 64F MODULE FAIL, 64S INJECT ON status of the relay. The front panel also provides a TARGET RESET pushbutton for resetting the relay and the targets. Relay and Logic Settings Software. Use ACSELERATOR QuickSet® SEL-5030 Software to reduce your engineering costs for relay settings and logic programming and simplify development of SELOGIC® control equations. Metering and Monitoring. Use built-in metering functions to eliminate separately mounted metering devices. Analyze SER reports and oscillographic event reports for rapid commissioning, testing, and post-fault diagnostics. Additional monitoring functions include the Profile Report. Control Inputs and Outputs. Take advantage of two internally wetted control inputs and four contact outputs (one Form C and three Form A) for control and status indication. Schweitzer Engineering Laboratories, Inc.

 Open the catalog to page 1
SEL-2664S Stator Ground Protection Relay-2

Port 1 with dual fiber-optic Ethernet ports Port 2 with an ST® fiber-optic EIA-232 serial port Front port and Port 3 with an EIA-232 configurable serial port ➤ Communications Protocols. Modbus® RTU, Modbus TCP/IP DNP3 serial and LAN/WAN IEC 61850 Simple Network Time Protocol (SNTP) File Transfer Protocol (FTP) Telnet (SEL ASCII) SEL protocols, including MIRRORED BITS® communications ➤ Conformally Coated. ➣ ➣ ➣ ➣ ➣ ➣ ➣ 59N1 Neutral Fundamental Overvoltage Stator Ground Event Reports Operator Interface Sequential Events Recorder Profile Report Monitoring * Neutral Grounding Resistor ‡ Neutral Grounding...

 Open the catalog to page 2
SEL-2664S Stator Ground Protection Relay-3

Protection and Control Features ➤ 100% Stator Ground Protection. The SEL-2664S uses multisine signal injection to provide 100 percent stator ground protection 100 percent of the time. The relay works with the generator in or outof-service, including the generator ramp-up with no blind period. Two levels of 64S (stator ground) elements provide warning and trip along with delay and torque control settings. The 64S elements together with the 59N elements detect faults between ground and any location, including the neutral point on the stator winding of synchronous generators. Redundant protection...

 Open the catalog to page 3
SEL-2664S Stator Ground Protection Relay-4

Metered Quantities (Sheet 2 of 2) Magnitude of neutral currents at the injected frequencies in secondary amperes Stator Insulation (kOhms) Resistance of the stator insulation to ground at the injected frequencies in kilohms Secondary and Primary are in reference to the Neutral Grounding Transformer (NGT), not CTN. Neutral rms current (A sec) is shown if CTN_LOC := SEC; otherwise, it is hidden. Profile Report Monitoring Profile report monitoring provides a periodic snapshot (selectable rate of every 1, 5, 15, 30, or 60 minutes) of as many as 17 selectable analog quantities from the complete list...

 Open the catalog to page 4
SEL-2664S Stator Ground Protection Relay-5

Apply an SEL communications processor as the hub of a star network, with point-to-point connection between the hub and the SEL-2664S (see Figure 3). The communications processor supports external communications links including the public switched telephone network for engineering access to dial-out alerts and private line connections of the SCADA system. Dial-Up ASCII Link SCADA Link ASCII Reports Plus Interleaved Binary Data IED Example Communications System SEL manufactures a variety of standard cables for connecting this and other relays to a variety of external devices. Consult your SEL representative...

 Open the catalog to page 5
SEL-2664S Stator Ground Protection Relay-6

Ethernet Network Architectures Cat 5 shielded twisted pair (STP) cables for copper Ethernet ports Fiber-optic Ethernet cables with fiber-optic Ethernet ports Fiber only Figure 6 Simple Ethernet Network Configuration With Ring Structure (Switched Mode) Schweitzer Engineering Laboratories, Inc.

 Open the catalog to page 6
SEL-2664S Stator Ground Protection Relay-7

Operator Controls There are multiple methods for accessing the operator interface of the relay. As shown in Figure 18, the front and side panels have eight LEDs that indicate the ENABLED, TRIP, WARNING, 64S, 64F, 59N, 64F MODULE FAIL, 64S INJECT ON status of the relay. The front panel also provides a TARGET RESET pushbutton for resetting the relay and the targets. Relay and Logic Settings Software ACSELERATOR QuickSet simplifies settings and provides analysis support for the SEL-2664S. Create and manage relay settings with ACSELERATOR QuickSet in the following ways: ➤ Develop settings offline...

 Open the catalog to page 7
SEL-2664S Stator Ground Protection Relay-8

Figure 9 shows the ac connections for the SEL-2664S with the neutral ground resistor (NGR) and CTN on the primary side and a neutral voltage transformer. Relay 1 SEL-2664S I_SRC Neutral Voltage Transformer Relay 2 2-C Twisted Pair. Do not ground the CTN leads. C01 2-C Twisted Pair. Do not ground the CTN leads. Figure 9 AC Connections With Neutral CT on the Primary Side and Neutral Voltage Transformer Figure 10 shows the ac connections with NGR in the secondary side of a wye-broken delta grounding transformer on the generator terminals. NGT SEL-2664S I_SRC NGR Figure 11 AC Connections for Protection...

 Open the catalog to page 8
SEL-2664S Stator Ground Protection Relay-9

Guideform Specification One-hundred percent stator ground protection shall be provided by a microprocessor-based relay equipped with the following protection, monitoring, control, automation, and reporting functions. Self-checking functions shall be included. Specific requirements shall be as follows. Protection and Control ➤ Fundamental and rms neutral overvoltage (59N1, 59NRMS) ➤ Neutral ground resistance (NGR) monitor function to detect open or short conditions. ➤ Stator ground protection (64S) using four frequency injection source ➤ Rotor field ground protection (64F) when used with an SEL-2664...