SEL-2411 Programmable Automation Controller
24Pages

{{requestButtons}}

Catalog excerpts

SEL-2411 Programmable Automation Controller - 1

Programmable Automation Controller Complete System for Control and Monitoring SELECT I/O Family of Cards High Reliability, Low Price ➤ ➤ ➤ ➤ Ten-Year, Worldwide Warranty –40° to +85°C Operating Temperature Ruggedized to Meet Industrial and Utility Standards Class 1, Division 2 Hazardous Location Approval Flexible Input, Output, and Logic Choices ➤ Powerful Logic, Math, and Timer Functions ➤ Fast 4 ms Logic Loop Time ➤ Single or Dual Ethernet, Fiber-Optic Serial, EIA-232, ➤ Modbus® RTU, Modbus TCP, DNP3, DNP3 LAN/WAN, MIRRORED BITS®, SEL ASCII and Binary Communications, and IEC 61850 Critical Reporting and Logging ➤ ➤ ➤ ➤ 1 ms Accurate Sequential Events Recorder Trending Event Recording IRIG-B Satellite Time Synchronization AC Metering Capabilities Digital I/O ➤ Voltage, Current, Power ➤ Demand, Energy Simple Commissioning Tools ➤ Front-Panel Configuration and Measurement Display ➤ Local LCD Display of Settings, Calculated Values, and ➤ Programmable Front-Panel Indication and Control ➤ Simple Programming With ACSELERATOR QuickSet® Schweitzer Engineering Laboratories, Inc.

Open the catalog to page 1
SEL-2411 Programmable Automation Controller - 2

Product Summary The SEL-2411 Programmable Automation Controller (SEL-PAC) automates continuous and discrete processes. A standalone SEL-PAC is a simple solution to monitor and control small waste water plants or small substations. Combine multiple SEL-PACs for applications such as industrial powerhouse DCS, chemical plant automation systems, and large substation SCADA. Functional Block Diagram Front Port DI Communications Modbus / Modbus TCP DNP3 / DNP3 LAN/WAN SEL ASCII & Binary SEL MIRRORED BITS FTP / Telnet IEC 61850 Port 2 Fiber-optic Port 3 EIA-232 Logic Processor AND OR NOT Rising...

Open the catalog to page 2
SEL-2411 Programmable Automation Controller - 3

Automation and Control Features Standard Features ➤ Chassis ➤ Front panel ➤ LCD display ➢ 4 programmable pushbuttons with LEDs ➢ 6 programmable LEDs ➢ Operator control interface ➢ EIA-232 port ➤ Main board ➢ EIA-232 port ➢ IRIG-B time-code input ➤ Power supply 2 DI, 3 DO on power supply board ACSELERATOR QuickSet software Instruction manual, printed or on CD-ROM Protocols ➢ Modbus RTU ➢ SEL MIRRORED BITS ➢ SEL ASCII and Compressed ASCII ➢ SEL Fast Meter, Fast Operate, Fast SER ➢ SEL Fast Message ➢ Ymodem file transfer Additional Ordering Options The following options can be ordered for any...

Open the catalog to page 3
SEL-2411 Programmable Automation Controller - 4

Replaces Traditional Panel Control Switches Eliminates External Timers Eliminate traditional panel control switches with operator control pushbuttons or the 32 local bits, available through the menu system. Program the four conveniently sized operator pushbuttons to control fan banks and fan lockout. Set, clear, or pulse local bits with the front-panel pushbuttons and display. Program the local bits into your control scheme with SELogic control equations. Use the local bits to perform functions such as breaker trip/close. Eliminate external timers for custom protection or control schemes...

Open the catalog to page 4
SEL-2411 Programmable Automation Controller - 5

Communications Architectures DCS or SCADA Master Ethernet Switch PROGRAMMABLE AUTOMATION CONTROLLER PROGRAMMABLE AUTOMATION CONTROLLER 10/100BASE-T Ethernet Port - Modbus TCP - DNP3 LAN/WAN - Telnet - FTP - IEC 61850 PROGRAMMABLE AUTOMATION CONTROLLER PROGRAMMABLE AUTOMATION CONTROLLER PROGRAMMABLE AUTOMATION CONTROLLER PROGRAMMABLE AUTOMATION CONTROLLER PROGRAMMABLE AUTOMATION CONTROLLER Typical Ethernet and EIA-485 Communications Architectures Metallic or Fiber-Optic Serial Cable EIA-232 or Fiber Optic - Modbus RTU - DNP3 Level 2 Slave - SEL ASCII - SEL Fast Message, Fast SER - SEL Fast...

Open the catalog to page 5
SEL-2411 Programmable Automation Controller - 6

Simplify Your Setup and Commissioning The SEL-2411 front panel simplifies commissioning and troubleshooting: ➤ View field data and calculated values ➤ Diagnose data flow problems in seconds instead of hours ➤ Dramatically reduce troubleshooting time ➤ Eliminate the need for out-of-service time Front-Panel Visualization and Control Ambient Temperature 24.0 deg C Build your own custom displays. Rotating displays show device measurement and settings information based on user-configured display points. Large temperature range for installing in outdoor cabinets +85°C PROGRAMMABLE AUTOMATION...

Open the catalog to page 6
SEL-2411 Programmable Automation Controller - 7

Configuration Software ^ AcSFLerator© QuickSet - C:\Docurrient& and Setting&\kitri&VApplication Data\... [-JLpJEJ Edit Commun z~.; ons Leg '-.'.'indcv, S Settings Editor - New Settings 1 (SEL-2411 002 Settings Driver) Global Settings Device Settings • Analog Settings O Internal FITD Settings External FlTD Settings + O Front Panel Settings SDHP Maps Programmable Automation Controller L-2411002 Settings Driver [Driver Version: 4.1.15.18 Date: 5/17/2007 10:22:38AM |Part #: 241101A 2X9 * j3§ AcSELerator® QuickSet - C:\Documents and SattingsUdtriApplication Data\SEL\AcSEL... (_ □ [X] i Edit...

Open the catalog to page 7
SEL-2411 Programmable Automation Controller - 8

Monitoring and Metering Analyze Sequence–of–Events Record sequence-of-events related to process control with the Sequential Events Recorder (SER) function. With this function, you can analyze assertions and deassertions of digital inputs and outputs; up to 512 state changes to the millisecond for as many as 96 different digital points. The function also captures when the device powers up and a settings change occurs. SEL-2411 DEVICE # 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ELEMENT RB01 OUT102 RB01 OUT102 Device Powered Up OUT101 OUT101 Device Settings Changed FAN BANK #2 OFF OUT101 FAN...

Open the catalog to page 8
SEL-2411 Programmable Automation Controller - 9

Analyze Event Waveforms Record analog and digital waveforms at 32 samples/cycle for up to 64 power system cycles, approximately 1 s. Use the event report to move the oscillographic data to your PC. You can plot your event report data with the SEL-5601 Analytic Assistant software or with Microsoft® Excel. Event reports contain ac currents, ac voltages, and digital inputs and outputs. The report automatically adjusts content to the I/O cards you use. Reports are stored in nonvolatile memory to protect your data even if power is lost. Event reports are optimized for recording power...

Open the catalog to page 9
SEL-2411 Programmable Automation Controller - 10

Metering The SEL-2411 provides extensive metering capabilities. See Specifications for metering and power measurement accuracies. As shown in Table 1, metering includes current and voltage-based metering and analog input, math variable and remote analog metering. Fundamental, maximum and minimum, and demand metering typically includes phase voltages and currents; sequence voltages and currents; and power, frequency, and energy. Table 1 Metering Types Real, Reactive, Apparent (In and Out) Frequency, Voltages (VA, VB, VC), Currents (IA, IB, IC, 3I2), Apparent, Reactive, and Real Power Demand...

Open the catalog to page 10

All Schweitzer Engineering Laboratories catalogs and technical brochures

  1. SEL-C662

    1 Pages

  2. 2019 CATALOG

    248 Pages

  3. 2018 CATALOG

    374 Pages

Archived catalogs