SEL-2245-42 AC Protection Module The SEL-2245-42 provides ac analog inputs for the SEL Axion®. Install as many as nine SEL-2245-42 modules within an Axion node and as many as sixteen SEL-2245-42 modules per system in any combination you want. Front Panel Mechanical Installation Each SEL-2242 chassis/backplane has four or ten slots, labeled A–J. Slots B–J support the SEL-2245-42 modules. Schweitzer Engineering Laboratories, Inc. Notch for Module Alignment To install an SEL-2245-42 module, tip the top of the module away from the chassis, align the notch on the bottom of the module (shown in Figure 2) with the slot you want on the chassis, and place the module on the bottom lip of the chassis, as Figure 3 illustrates. The module is aligned properly when it rests entirely on the lip of the chassis.
Open the catalog to page 1Input Connections The SEL-2245-42 CT/PT analog inputs include a dot next to the terminal number to indicate the positive connection. Refer to Specifications for ac analog input ratings and to Figure 5 for terminal assignments. You can configure potential transformer (PT) inputs for 6-300 V and current transformer (CT) inputs for 0-20 A. Configure inputs by adding a Fieldbus I/O connection for each module in acSELerator RTAC® SEL-5033 Software. See the EtherCAT® portion in Section 2: Communications in the SEL-5033 Software Instruction Manual for details. Figure 5 CT/PT Analog Inputs LED Indicators The...
Open the catalog to page 2Pollution Degree: Overvoltage Category: Insulation Class: Relative Humidity: Maximum Altitude: Accuracy: Synchrophasors Conformance: Compliance Designed and manufactured under an ISO 9001 certified quality management system UL Listed to U.S. and Canadian safety standards (File E220228; NRAQ, NRAQ7) CE Mark General Frequency Rated: Range: Typical Accuracy: Worst Case Accuracy: Phase Rotation: Input Configuration: Update Intervals Fundamental Metering: RMS: Nominal Current: 1 ARMS or 5 ARMS (no setting required) Rated Insulation Voltage: 300 VL-N continuous 600 Vl-N for ten seconds Galvanic...
Open the catalog to page 3Enclosure Protection: IEC 60255-27:2013 (Type 1 enclosure required for full compliance to IEC 60255-27) IEC 60529:1989 + A1:1999 + A2:2013 IP4X, excluding the terminal blocks Electrostatic Discharge IEC 60255-26:2013 Severity Level: 6 kV contact discharge 8 kV air discharge IEEE C37.90.3-2001 Severity Level: 8 kV contact discharge 15 kV air discharge Vibration Resistance: Shock Resistance: IEC 60255-21-1:1988 Vibration Endurance, Severity: Class 2 Vibration Response, Severity: Class 2 IEC 60255-21-2:1988 Bump Test, Severity: Class 1 Shock Withstand, Severity: Class 1 Shock Response, Severity:...
Open the catalog to page 41 Page
248 Pages
374 Pages
20 Pages
28 Pages
12 Pages
28 Pages
12 Pages
373 Pages
12 Pages
12 Pages
20 Pages
8 Pages
4 Pages
8 Pages
32 Pages
12 Pages
331 Pages
44 Pages