SEL-2245-22 Analog Input Extended Range Module

SEL-2245-22 Analog Input Extended Range Module

SEL-2245-22 Analog Input Extended Range Module

Product catalog summary
Overview
The SEL-2245-22 module provides extended range DC analog inputs for the SEL Axion system, allowing installation of up to sixteen modules in various combinations within an Axion system.

Mechanical Installation
The SEL-2245-22 modules can be installed in slots B–J of the SEL-2242 chassis/backplane. Proper alignment and secure placement are crucial for installation.

Input Connections
The module supports a DC input range of 0–300 Vdc. Configuration is done via the ACSELERATOR RTAC® SEL-5033 Software, with specific instructions available in the software manual.

LED Indicators
The module features ENABLED and ALARM LEDs for network operation status, with further details available in the SEL-2240 Instruction Manual.

Specifications
  • Operating Temperature: –40° to +85°C
  • Input Impedance: >7 MΩ
  • Sampling Rate: 1 ksps
  • Isolation: 2500 Vrms between inputs and to chassis
  • Accuracy: 0.25% of full-scale typical at 25°C

Type Tests
The module has undergone various environmental, dielectric strength, and RFI tests, meeting standards such as IEC 60529, IEC 60255, and IEEE C37.90.

Certifications
The product is designed and manufactured under an ISO 9001 certified quality management system.

Warranty
The SEL-2245-22 is covered by a standard SEL 10-year warranty.
See more

Catalog excerpts

SEL-2245-22 Analog Input Extended Range Module-1

SEL-2245-22 Analog Input Extended Range Module The SEL-2245-22 provides extended range dc analog inputs for the SEL Axion®. Within an Axion system, install as many as sixteen SEL-2245-22 modules in any combination you want. Front Panel Mechanical Installation Each SEL-2242 chassis/backplane has four or ten slots, labeled A–J. Slots B–J support the SEL-2245-22 modules. Figure 1 SEL-2245-22 DC Analog Input Extended Range Module Schweitzer Engineering Laboratories, Inc. Notch for Module Alignment To install an SEL-2245-22 module, tip the top of the module away from the chassis, align the notch on the bottom of the module (shown in Figure 2) with the slot you want on the chassis, and place the module on the bottom lip of the chassis as Figure 3 illustrates. The module is aligned properly when it rests entirely on the lip of the chassis.

 Open the catalog to page 1
SEL-2245-22 Analog Input Extended Range Module-2

Input Connections The SEL-2245-22 dc analog inputs include a plus sign to indicate the positive convention. Refer to Specifications for analog input ratings and to Figure 1 for terminal assignments. Input range is 0–300 Vdc. Configure inputs by adding a Fieldbus I/O connection for each module in ACSELERATOR RTAC® SEL-5033 Software. See the EtherCAT® portion in Section 2: Communications in the SEL-5033 software manual for details. Proper Module Placement Next, carefully rotate the module into the chassis, making sure that the alignment tab fits into the corresponding slot at the top of the chassis...

 Open the catalog to page 2
SEL-2245-22 Analog Input Extended Range Module-3

Record Pretrigger: General Operating Temperature Range –40° to +85°C (–40° to +185°F) Note: Not applicable to UL applications. Operating Environment 0.05 s minimum to a maximum of (record length minus 0.05) s Waveform File Format: COMTRADE (IEEE C37.111-1999 compliant) Type Tests Environmental Tests Pollution Degree: Overvoltage Category: Relative Humidity: Maximum Altitude: Type Test Acceptance Criteria Enclosure Protection: IEC 60529:2001 + CRGD:2003 IP3X excluding the terminal blocks Vibration Resistance: IEC 60255-21-1:1988 Vibration Endurance, Severity: Class 1 Vibration Response, Severity:...

 Open the catalog to page 3
SEL-2245-22 Analog Input Extended Range Module-4

Magnetic Field Immunity: IEC 61000-4-8:2009 Severity Level: 1000 A/m for 3 seconds, 100 A/m for 1 minute IEC 61000-4-9:2001 Severity Level: 1000 A/m IEC 61000-4-10:2001 Severity Level: 100 A/m Surge Withstand Capability Immunity: IEC 60255-22-1:2007 Severity Level: 2.5 kV common-mode 1.0 kV differential-mode IEEE C37.90.12002 Severity Level: 2.5 kV Oscillatory 4.0 kV Fast Transient Oscillatory Waves Immunity: IEC 61000-4-12:2006 Severity Level: Ring Wave: 2 kV common, 1.0 kV differential Oscillatory: 2.5 kV common, 1.0 kV differential Common Mode IEC 61000-4-16:2002 Disturbance Immunity: Frequency:...

 Open the catalog to page 4