SEL-2245-2 Analog Input Module
4Pages

{{requestButtons}}

Catalog excerpts

SEL-2245-2 Analog Input Module - 1

SEL-2245-2 Analog Input Module The SEL-2245-2 provides dc analog inputs for the SEL Axion®. Within an Axion system, install as many as sixteen SEL-2245-2 modules in any combination you want. Front Panel Mechanical Installation Each SEL-2242 chassis/backplane has four or ten slots, labeled A–J. Slots B–J support the SEL-2245-2 modules. SEL-2245-2 DC Analog Input Module Schweitzer Engineering Laboratories, Inc. Notch for Module Alignment To install an SEL-2245-2 module, tip the top of the module away from the chassis, align the notch on the bottom of the module (shown in Figure 2) with the slot you want on the chassis, and place the module on the bottom lip of the chassis as Figure 3 illustrates. The module is aligned properly when it rests entirely on the lip of the chassis.

Open the catalog to page 1
SEL-2245-2 Analog Input Module - 2

Proper Module Placement Next, carefully rotate the module into the chassis, making sure that the alignment tab fits into the corresponding slot at the top of the chassis (refer to Figure 4). Finally, press the module firmly into the chassis and tighten the chassis retaining screw. Final Module Alignment Input Connections The SEL-2245-2 dc analog inputs include a plus sign to indicate the positive convention. Refer to Specifications for analog input ratings and to Figure 1 for terminal assignments. You can configure inputs to measure ±20 mA, ±2 mA, or ±10 V signals. Configure inputs by...

Open the catalog to page 2
SEL-2245-2 Analog Input Module - 3

Accuracy Variation With Temperature Operating Temperature Range –40° to +85°C (–40° to +185°F) Note: Not applicable to UL applications. Triggered Waveform Recording Operating Environment Pollution Degree: Overvoltage Category: Relative Humidity: Maximum Altitude: Sampling Rate: Record Duration: 0.1 second increments from 0.5 s to 144 s Record Pretrigger 0.05 s minimum to a maximum of (record length minus 0.05) s Waveform File Format: COMTRADE (IEEE C37.111-1999 compliant) DC Transducer (Analog) Inputs (SEL-2245-2) Type Tests Input Impedance Current Mode: Voltage Mode: Environmental Tests 10...

Open the catalog to page 3
SEL-2245-2 Analog Input Module - 4

Digital Radio Telephone RF Immunity: Conducted RF Immunity: IEC 60255-22-6:2001 IEC 61000-4-6:2008 Severity Level: 10 Vrms Surge Immunity: IEC 60255-22-5:2008 IEC 61000-4-5:2005 Severity Level: 1 kV Line to Line, 2 kV Line to Earth (8 ms filter voltage mode, 6 ms filter high-current mode, 4 ms filter low-current mode) Fast Transient, Burst Immunity: IEC 60255-22-4:2008 IEC 61000-4-4:2011 Severity Level: Class A: 4 kV, 5 kHz; 2 kV, 5 kHz on communications ports Magnetic Field Immunity: Radiated and Conducted Emissions: IEC 60255-25:2000 Severity Level: Class A This product was designed and...

Open the catalog to page 4