SEL-2241 Real-Time Automation Controller (RTAC)
8Pages

{{requestButtons}}

Catalog excerpts

SEL-2241 Real-Time Automation Controller (RTAC) - 1

SEL-2241 Real-Time Automation Controller (RTAC) Each SEL Axion® system requires an RTAC module to serve as the system CPU. The SEL-2241 RTAC has all of the communications and custom logic capabilities of the stand-alone RTAC modules, but is mounted in and receives power from the Axion backplane. Mechanical Installation The following figure shows the RTAC status LEDs that aid system troubleshooting and the connectors for communications and wiring. Each SEL-2242 chassis/backplane has ten slots, labeled A through J. Only Slot A supports the SEL-2241 RTAC module. RTAC ENABLED ALARM 1 Notch for Module Alignment SEL-2241 RTAC Front Panel, Copper Ethernet Schweitzer Engineering Laboratories, Inc. To install the RTAC, tip the top of the module away from the chassis, align the notch on the bottom of the module (shown in Figure 2) with Slot A of the chassis, and place the module on the bottom lip of the chassis as Figure 3 illustrates. The module is aligned properly when it rests entirely on the lip of the chassis.

Open the catalog to page 1
SEL-2241 Real-Time Automation Controller (RTAC) - 2

Connections Communications Ports NOTE: Never connect two RTACs via USB to one PC. Proper Module Placement Next, carefully rotate the module into the chassis, making sure that the alignment pin fits into the corresponding slot at the top of the chassis (refer to Figure 4). Finally, press the module firmly into the chassis and tighten the chassis retaining screw. All web access, settings changes and ODBC connections use either the RTAC Ethernet ports or the front USB type B port. Until you have configured the Ethernet interfaces on the RTAC, you will need to use the supplied USB type B cable...

Open the catalog to page 2
SEL-2241 Real-Time Automation Controller (RTAC) - 3

Nonisolated Female DB-9 Ports Pin 1: N/C or +5 Vdc (also DCD input on COM 1 if +5 Vdc is disabled) Pin 1: N/C or +5 Vdc (also DCD input on COM 1 if +5 Vdc is disabled) Pin 4: +IRIG-B (DTR jumper option for COM 1) Pin 6: -IRIG-B (DSR jumper option for COM 1) Port Characteristics Port Interface IRIG-B INput IRIG-B OUTput Outputs Refer to Specifications on page 5 for output contact ratings and Figure 3 for terminal assignments. Configure the contact output under SystemTags (Contact Outputs Tab) in ACSELERATOR RTAC. You can change the name of the point, create an alias tag name, and initialize...

Open the catalog to page 3
SEL-2241 Real-Time Automation Controller (RTAC) - 4

Step 7. Make all necessary connections to the module according to the applicable connection instructions in this section. Step 8. Apply power to the Axion node. Step 9. Use IP address 172.29.131.1 to access the RTAC web interface through the supplied USB cable. See Section 6: Security in the ACSELERATOR RTAC SEL-5033 Instruction Manual for RTAC web password setup. Also enable all necessary communications ports. Jumpers The SEL-2241 RTAC jumpers come preset and should not be moved except as Section 3: Testing and Troubleshooting in the SEL-2240 Instruction Manual describes. Table 3 shows the...

Open the catalog to page 4
SEL-2241 Real-Time Automation Controller (RTAC) - 5

Specifications Time-Code Input (Demodulated IRIG-B) General Operating Temperature Range –40° to +85°C (–40° to +185°F) Operating Environment Time-Code Output (IRIG-B) Pollution Degree: Overvoltage Category: Relative Humidity: Maximum Altitude: Input Impedance: Accuracy: Note: Not applicable to UL applications. Network Time Protocol (NTP) Modes Dimensions Refer to Section 2: Installation for relay dimensions. Up to three configurable servers Weight (Fully Populated Node) 16 lbs Communications Ports Ethernet Ports (To Backplane) Ports: Processor Speed: Data Rate: Dedicated EtherCAT port User...

Open the catalog to page 5
SEL-2241 Real-Time Automation Controller (RTAC) - 6

Output Contact Mechanical Durability: Seismic: Cold: Damp Heat, Cyclic: IEC 60255-21-3:1993 Quake Response, Severity: Class 1 IEC 60068-2-30:2005 25°C to 55°C, 6 cycles, 95% relative humidity DC Output Ratings Rated Operational Voltage: Rated Voltage Range: Rated Insulation Voltage: 300 Vdc Make: Continuous Carry: Contact Protection: Operating Time (coil energization to contact closure, resistive load): IEC 60255-5:2000 Severity Level: 0.5 Joule, 5 kV IEEE C37.90:2005 Severity Level: 0.5 Joule, 5 kV Dielectric (HiPot): IEC 60255-5:2000 Severity Level: 2500 Vac on contact output for 1...

Open the catalog to page 6
SEL-2241 Real-Time Automation Controller (RTAC) - 7

Oscillatory Waves Immunity: IEC 61000-4-12:2006 Ring Wave: 2 kV common, 1.0 kV differential Oscillatory: 2.5 kV common, 1.0 kV differential Common Mode IEC 61000-4-16:2002 Disturbance Immunity: Frequency: 0 Hz to 150 Hz Severity: Level 4, segment 4: 30 Vrms open-circuit, 15 kHz–150 kHz Emissions Radiated and Conducted Emissions: This product was designed and manufactured under an ISO 9001 certified quality management system. Schweitzer Engineering Laboratories, Inc.

Open the catalog to page 7
SEL-2241 Real-Time Automation Controller (RTAC) - 8

© 2011–2013 by Schweitzer Engineering Laboratories, Inc. All rights reserved. All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No SEL trademarks may be used without written permission. SEL products appearing in this document may be covered by U.S. and Foreign patents. SCHWEITZER ENGINEERING LABORATORIES 2350 NE Hopkins Court • Pullman, WA 99163-5603 USA Phone: +1.509.332.1890 • Fax: +1.509.332.7990 Internet: www.selinc.com • E-mail: info@selinc.com Schweitzer Engineering Laboratories, Inc. reserves all rights and...

Open the catalog to page 8