Conventional Light Fittings Explosion-Proof Light Fittings Dust- and Waterproof Light Fittings PRODUCT CATALOGUE
Open the catalog to page 1Explosion Protected Fittings Zone 1/21 6-10 Light fittings with diffusers 8-10 Explosion Protected Fittings Zone 2/22 11-12 Light fittings with diffusers 11-12 Ex-Protected Installation Components 13-16 Dust-/Waterproof Light Fittings 18-41 Light fittings with diffusers 20-32 Light fittings without diffusers 33-35 Oval shaped light fitting 36 Vandal proof light fittings 38-39 Mounting rails/through wiring systems 40-41 Subject to technical changes, misprints and errors. SlSCHUCHl Catalogue conventional 2021/22
Open the catalog to page 3Explosion-Protected Light FittingsImpressive innovation strength in extreme conditions HIGHLIGHTS OF TECHNOLOGICAL DEVELOPMENT For more than one hundred years SCHUCH has been considered as an expert in lighting in extreme environments. Applications in explosive gases and dust environments set stringent requirements. With the results of its own intensive research and design work, as well as more than 100-year experience, SCHUCH still acts as an innovator in this challenging field. Thus, SCHUCH has decisively influenced much on the development of conventional explosion-protected linear light fittings,...
Open the catalog to page 4Product Series Page Light Fittings for Zone 1/21 Light Fittings with Diffuser with central locking system e840... 8-10 group battery systems • pole mounted light fitting e840... PM 9 Light Fittings for Zone 2/22 Light Fittings with Diffuser nD161/162... 11-12 Ex-Installation material carrier rail systems TRS 2000 13 Through wiring systems DV 14 Built-in Disconnect Switch LS 32-20 15 LED technology 2011 SCHUCH brought the first EX-protected LED headlights, emergency and compact light fittings to market maturity. 2014 First approval of explosion-protected linear LED light fittings, high bay LED...
Open the catalog to page 5Explosion-Protected Light Fittings Series e840... Application: Hazardous areas of zones 1, 21 and 2, 22. Design: Housing: Glass fibre reinforced polyester resin. Cover: Clear polycarbonate with internal prisms, hinged. Gasket: Silicone, foamed. Reflector: Glass fibre reinforced polyester, hinged and removable. Central locking system: Operated by a hexagonal socket key 13mm. Isolating switch: Switching off all poles when the light fitting is opened. Note: Wiring: Electronic ballast with “end-oflife switching-off system”. Connection: Prepared for looping the mains cable on one small side. Terminal...
Open the catalog to page 6EC-Type Examination Certificate: Marking: PTB 09 ATEX 2031,2039 II 2 D Ex tb IIIC T80°C Db (Zone 21) Ignition protection: e (increased safety) 1) A climatic breather may reduce the IP rating (depending on the orientation of the breather) for connection to central or group battery systems Application: Emergency light fittings powered by central- or group battery systems. Design: Same as type e840 but with DC-detection and change-over to 1-lamp operation (emergency mode). Explosion protected Light Fittings 84000 0303 1) A climatic breather may reduce the IP rating (depending on the orientation...
Open the catalog to page 7Further accessories such as carrier rail systems please see installation material in this catalogue. Accessories / Spare Parts Subject to technical changes, misprints and errors. 10 SSCHUCHi Catalogue conventional 2021/22
Open the catalog to page 8Explosion-Protected Light Fitting for Zone 2/22 Series nD161/162... Applications: Hazardous locations of zones 2 (gas) and 22 (dust). Design: Housing: Glass fibre reinforced polyester resin. Cover: Injected clear polycarbonate (PC) with internal prisms. Closure: Stainless steel clips (KE), one of them as safety clip (KES), to be opened with screwdriver only. Stainless steel hinges (SC) on the opposite side. Reflector: Suspendable, glass fibre reinforced polyester, carrying the electrical Options: - for connection to group or central battery (light fittings of version ZB only) - with monitoring...
Open the catalog to page 9EC-Type Examination Certificate: TUV 00 ATEX 1541 Ignition protection: nA Rated voltage: 230 V, 50Hz (VVG) II 3 D Ex tc IIIC T80°C Dc ( Zone 22) Permissible ambient temperature: Subject to technical changes, misprints and errors.
Open the catalog to page 10Aluminium Carrier Rails for Continuous Row Installation Series TRS 2000... and AL... TRS 2000... Application: For rows of light fittings suspended from the ceiling, allowing an easy installation and assembly. Design: Aluminium profiled carrier rails (AL / TRS 2000) Lengths: 2, 3 or 5 m. Additional covering strip (TRS A) for series TRS. Mounting accessories: For each length of a light fitting only one suspension point is required. Connection brackets (TRS V) - to be ordered separately - allow joining the individual rails up to any length wanted. The carrier rails can either be mounted directly...
Open the catalog to page 11Through wiring Systems for Explosion-Protected Light Fittings For all fittings installed in a continuous row. Through wiring system with 2 multipole terminals which are fixed inside the light fitting. (Since retrofitting the through wiring system on site is subject to special regulations in regard to hazardous areas, we do recommend a factory-made through-wiring system.) Note: With the “variable cable entries” most of our explosion-protected fluorescent fittings are well suited for looping the cable at one end of the fitting. This allows a perfect adaptation to the local conditions and moreover...
Open the catalog to page 12Explosion-Protected Built-in Disconnect Switch Series LS 32-20 Applications: As (spare) disconnect switch in Ex light fittings for isolation of all poles when opening the fitting. Design: Housing: With contact carrier, operating hood, 2 N/O contacts. With heat resistant moulded wire tails. EC-Type Examination Certificate: BVS 12 ATEX E055 U Type of protection: d (flameproof enclosure) Marking: II 2 G Ex db IIC Gb or I M 2 Ex db I Mb for use in Group I light fittings. Rating: 300V/2A (AC-5a, DC-12). Explosion protected Light Fittings Subject to technical changes, misprints and errors. MschuchJ...
Open the catalog to page 13Explosion-Protected Lamp Holder G13/G5 for Bi-Pin Fluorescent Lamps Series e2412.. / e8901.. / e8911.. / e8912 Application: As (spare) lamp holder in explosion-protected light fittings for fluorescent lamps with bi-pin lamp holders G13/G5. Design: White compression-moulded housing, spring brass contacts, silver-plated. Scope of supply: e2412/1 P without carrier e8901 without carrier e8901 FH/.. with holders Certificates PTB 00 ATEX 2126 U (e2412) PTB 09 ATEX 2007 U (e8901 / e8911 / e8912) Type of protection: e (increased safety) Marking: II 2 G Ex e II (Ex II) (e2412) I M 2 Ex e I (Ex I) (e2412)...
Open the catalog to page 14207 Pages
48 Pages
2 Pages
2 Pages
1 Page
2 Pages
7 Pages