Low-voltage machines IP55, EExd(e), Frame size 63-450
72Pages

{{requestButtons}}

Catalog excerpts

Low-voltage machines IP55, EExd(e), Frame size 63-450 - 1

ELECTRICAL MACHINES, DRIVE SYSTEMS AND SYSTEM ENGINEERING IP55 > Frame size 63-450 55 > II 2 G EExd(e) IIC(B) T4 55 > Explosion-protectedThree-Phase Low-Voltage Squirrel-CageMotors, flameproof enclosurefrom 0.12 to 630 kWM1.23e 2001 size="-2">

Open the catalog to page 1
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 2

■ Single speed motors ■ Change pole motors ■ Motors for frequency converter supply > Supersedes: ■ Technische Liste M1.23 e ✦ 2000 Revisions All technical data, outputs, dimensions and weights, stated in this catalogue, are subject to change without notice. Illustrations do not purport to show constructional details.08.01 >

Open the catalog to page 2
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 3

PageGeneral Information Page Inverter operation 50 Hz, n 39Mains operation60 Hz, n Standards of several EU and non-EU countries 2Explosion protection > s = 750 rpm, 2p = 8 40Mains operation60 Hz, n 4Explosion protection types of electrical machines > s = 3600 rpm, 2p = 2 41Mains operation60 Hz, n 4Validity of European standards EN 50... > s = 1800 rpm, 2p = 4 42Mains operation60 Hz, n 7 > s = 1200 rpm, 2p = 6 43Mains operation, increased output50 Hz, n Design Types > s = 900 rpm, 2p = 8 Construction types 8Materials, plates and labelling 44Mains operation, increased output50 Hz, n > General...

Open the catalog to page 3
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 4

Country International Europe Germany Great Britain Title IEC International Electrotechnical Commission EN ֖ CENELEC European Committee forElectrotechnical Standardisation DIN/VDE GermanIndustrial Standard/Association of German Electrotechni- cians BS ֖ British Standards Electrical rotating machines Rated operation and technical data IEC 60034-1, IEC 60085 EN 60034-1 DINEN 60034-1/ VDE0530 Part 1 BS 4999: P1 BS 4999: P69 Protection types of rotating electrical machines IEC 60034-5 EN 60034-5 DINIEC 34 Part 5/ VDE0530 Part 5 BS 4999: P20 > General Information Cooling methods of rotating...

Open the catalog to page 4
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 5

France Italy Belgium Switzerland Austria USA NF Norme Fran֧ais CEI Comitato Elettrattecnico Italiano NBN ֖ Norme Belge SEV Schweizerischer Electrotechnical Board ֖VE Austrian Association forElectrotechnology NEMA/NEC ֖ National MG.- ... Electric Code NF C 51-100 NF C 51-111 CEI 2-3355 NBN C 51-101 NBN C 51-102 SEV 3009, 1978 VE-M 10, Part 1 ֖VE-M 10, Part 2 MG 1-1.65 MG 10-10.37 NF C 51-115 CEI 70-1519 NBN C 51-105 UNEL 05515 SEV 3009-6 MG 1-1.25 MG 1-1.26 IEC-34, Part 6 CEI 2-/No. 454 NBN C 51-106 SEV 3009-6 - MG 1-1.25 MG 1-1.26 > General Information NF C 51-117 CEI-UNEL 05513 NBN C...

Open the catalog to page 5
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 6

Protection typeletter symbol Constructional requirements Protection concept Application for type of electrical machine Flameproof enclosure dӔ DIN EN 50 018 VDE 0170/0171 Part 5 Apparatus for zones 1 and 2 All potential ignition sources are housed inside a flameproof enclosure. Unavoid-able sealing surfaces are therefore designed as flameproof joints, so that, in case of ignition of an explosive atmosphere inside the enclosure, the explosive atmosphere is not transferred to the potentially explosive atmosphere surrounding the enclosure. All types of motors, e.g. squirrel-cage...

Open the catalog to page 6
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 7

Permissible temperatures for electrical apparatus DIN EN 50014; VDE 0170/0171Explosion protection groups IIA, IIB, IIC Ignition temperature of medium relative to temperature limit Temperature class Permissible surface temperature of apparatus incl. ambient temperature of 40C (temperature limit) above 450аC T1 450C > General Information above 300 Ж 450C T2 300аC above 200 300ְC T3 200C above 135 Ж 200C T4 135аC 100 135ְC T5 100C 85 Ж 100C T6 85аC > Permissible use of motors according to their classification by zone division Group Cate-gory Zone classification Definition acc. to ElexV...

Open the catalog to page 7
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 8

Examples of the classification of flammable gases and vapours according to temperature class and explosion group to DINVDE0165 Group Temperature classes T1 T2 T3 T4 T5 T6 Firedamp protection I Methane (firedamp) Note about the table:Additional examples are provided in the publication ғSafety engineering characteristics of combustible gas-es and vapours by Nabert/SchԶn, Deutscher Eichver-lag, Berlin. > General Information Explosion protection IIA Acetone AmmoniaBenzolAcetic acid EthaneEthyl acetateEthyl chloride Carbon monoxideMethane MethanolMethyl chloride PropaneToluene I amyl acetate n...

Open the catalog to page 8
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 9

General Information EU Countries Approved EU Ex testing authorities Germany PTB/BVS/IBExU/... According to the Treaty of Rome and the Maastricht Treaty, EN regulations must be valid in all EU member states, and the conformity certificates issued by EU-approved testing authorities must therefore be recognized by all EU members. Accordingly, electrical apparatus approved for use on the basis of conformity and EC type testing certificates can be supplied without restriction to the countries mentioned in the first column. Greece Luxembourg SEE Portugal Iceland Great Britain & Northern Ireland...

Open the catalog to page 9
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 10

tr.row {} td.cell {} div.block {} div.paragraph {} .font0 { font:6.00pt "Arial", sans-serif; } .font1 { font:7.00pt "Arial", sans-serif; } .font2 { font:10.00pt "Arial", sans-serif; } 8 Construction Types Up to frame size 355 - any number of poles - IM B3 as IM B6, IM B7, IM B8, IM V5*, IM V6* Exception: For the vertical design types marked the motor bearings are designed so that they IM B5 as IM V1 *, IM V3* *, protective devices must be fitted to provide can be used as described below without modifi- IM B35 as IM V15*, IM V36* protection against dripping water and to prevent cation. IM...

Open the catalog to page 10
Low-voltage machines IP55, EExd(e), Frame size 63-450 - 11

Design Types Materials for casings, end shields, terminal boxes and fans Frame size Housing type End shield Terminal box Fan cowl Radial-flow fan Axial-flow fan Material Feet EEx e EEx d 2-pole 4, 6, 8-pole 63 Grey cast iron Grey cast iron, bolted Grey cast iron Grey cast iron, bolted Grey cast iron, bolted n/a n/a n/a 71 Sheet steel Plastic > 1) Plastic > 1) 80 90 100 112 132 Plastic 160 180 200 225 Cast alumini- um alloyHub in grey cast iron 20 Cast alumini-um alloyHub in grey cast iron 20 250 280 315 355 Steel, welded Steel, welded Steel, welded 400 Steel, welded Steel, welded 450 Notes...

Open the catalog to page 11