1. Catalogs
  2. Schneider Electric
  3. Technical Data Sheet_SDC
video corpo

Technical Data Sheet_SDC

Technical Data Sheet_SDC

Technical Data Sheet_SDC

Product catalog summary
Technical Specifications
The SDC Rectifier/Battery Charger operates with input voltages of 3x380/400/415V and tolerates a DC input voltage variation of +/-10%. It functions within a frequency range of 50/60 Hz with a tolerance of +/-8%. The power factor varies with line power and float voltage, ranging from 0.75 to 0.90. Output voltages are available at 24, 48, 110, 125, and 220 VDC, with a setting range for float and boost voltages. The DC voltage tolerance is +/-1%, and the system can handle dynamic load changes with a regulation time of less than 100 ms.
Performance and Efficiency
The rectifier achieves up to 94% efficiency depending on the type. It features a DC overcurrent capability of 150% for 2 seconds and maintains a DC ripple voltage of ≤2% rms with a parallel battery. The system is designed to operate in ambient temperatures from -10 to +40 °C and at altitudes up to 1000 m.
Standards and Safety
The SDC Rectifier complies with safety standards IEC/EN 62040-1-2, EMC standards IEC 62040-2, EN 50091-2, and performance standards IEC/EN 62040-3, IEC 60146-1-1. It carries a CE label for conformity.
System Configuration and Options
The standard configuration includes a 6-pulse rectifier with an isolation transformer, an LCD display unit with a keyboard, and various input/output connections for alarms and remote operations. Optional features include parallel redundant configurations, additional ripple filters, 12-pulse rectifiers, and advanced battery monitoring systems. The system supports RS-232 and RS-485 interfaces for communication and monitoring.
Human-Machine Interface
The front panel provides a comprehensive interface with operational parameters, selectable display languages, and charge modes. It includes an LC display, alarm LEDs, and a keypad for setting parameters and accessing logs. The panel indicates the system's operational state and potential faults through LEDs and acoustic alarms.
See more

Catalog excerpts

Technical Data Sheet_SDC-1

echnical Data Sheet SDC Rectifier / Battery Charger >24-220V >25-1200 A H la-s y I i i GUTOR Schneider Electric

 Open the catalog to page 1
Technical Data Sheet_SDC-2

Technical data SDC Voltage 3x380/400/415V Input voltage tolrance: DC in tolrance +/-10 % for function +15 %/-25 % (below -15 % the battery might begin to discharge) Frequency 50 / 60 Hz Frequency tolerance +/- 8 % Power factor: at nominal line power and float voltage ~ 0.83 at -10 % line power and float voltage ~ 0.90 at +10 % line power and float voltage ~ 0.75 Rectifier input Voltage 24/48/110/125/220VDC Setting range: Float voltage at -10 /+10 % line power voltage 100-120 % Float voltage at 0 /+10 % line power voltage 100-130 % Boost voltage at nominal line power voltage 100-130 % Initial...

 Open the catalog to page 2
Technical Data Sheet_SDC-3

Cat Gen GB 2004 table.main {} tr.row {} td.cell {} div.block {} div.paragraph {} .font0 { font:12.00pt "Arial", sans-serif; } .font1 { font:13.00pt "Arial", sans-serif; } .font2 { font:32.00pt "Arial", sans-serif; } .font3 { font:4.00pt "Lucida Sans Unicode", sans-serif; } .font4 { font:5.00pt "Lucida Sans Unicode", sans-serif; } .font5 { font:6.00pt "Lucida Sans Unicode", sans-serif; } .font6 { font:8.00pt "Lucida Sans Unicode", sans-serif; } .font7 { font:13.00pt "Lucida Sans Unicode", sans-serif; } Spcification SDC Bottom cable entry Typical single-line drawing Ground terminal rWI MEffiUREMENTS...

 Open the catalog to page 3
Technical Data Sheet_SDC-4

Human-machine interface (front panel) The front panel, which is identical for both AC and DC Systems, includes a comprehensive and flexible human-machine i nterface. It is divided into four sections: The system panel shows the system's current state of operation (which part of the system is currently supplying the load and which is in stand-by mode). LEDs also indicate possible faults. Oprations for turning on and off the system and a lamp test button for checking whether all LED indications are functioning properly. To shut down the system, you have to press the ON and OFF buttons at the same...