Overview: The PXP AC UPS System is designed for both single-phase (PXP 1000) and three-phase (PXP 3000) applications, offering a power range of 5-160 kVA. It provides reliable power protection with advanced features and customizable options.
Specifications:
  • Rectifier Input: Voltage options include 3x380/400/415 V with a tolerance of -10/+15%. Frequency range is 41-70 Hz with auto-detection. Total harmonic distortion is less than 5% at full load, and the power factor is typically between 0.96 and 0.98.
  • Bypass Input: For PXP 1000, voltage is 1x220/230/240 V, and for PXP 3000, it is 3x380/400/415 V, both with a +/-10% tolerance. Frequency is 50/60 Hz with an 8% tolerance.
  • Battery Circuit: Operates at 400 VDC with a range of 335-540 VDC. Charging parameters are programmable, including float and boost voltages, charge time, and current limitation.
  • Output: Voltage options for PXP 1000 are 1x220/230/240 V and for PXP 3000 are 3x380/400/415 V. Voltage tolerance is +/-1% static and +/-5% dynamic. Overload capabilities vary by duration and percentage.
  • General Data: Operating temperature ranges from -10 to +40°C, with storage from -30 to +80°C. Altitude is up to 1000 m without de-rating, and humidity is less than 95% non-condensing. Noise levels range from 55-65 dBA.
Standards and Compliance: The system complies with IEC/EN 62040 standards for safety, EMC, and performance, and holds a CE label. It is classified as VFI-SS-111 according to IEC 62040-3.
Optional Features: Includes various input and output voltage options, battery circuit enhancements, communication interfaces like MODBUS, and additional alarms and environmental protections.
Human-Machine Interface: The front panel features an LC display, LEDs for operating modes, and push buttons for navigation. It provides access to measurement data, system information, and logs. Settings and measurements are accessible via display menus, including auto start, charge modes, and runtime statistics.
See more

Catalog excerpts

Technical Data Sheet_PXP-1

Technical Data Sheet PXP AC UPS System > PXP 1000 5-160 kVA single phase >PXP 3000 5-160 kVAthree phase GUTOR by schneider Electric

 Open the catalog to page 1
Technical Data Sheet_PXP-2

Technical data PXP Rectifier input voltage_3x380/ 400 /415 V Rectifier input voltage tolerance -10 /+15 % Rectifier input frequency 41 - 70 Hz (auto detection) Rectifier current total harmonic distortion <5 % @ 100 % load Rectifier input power factor typical 0.96 - 0.98 Inrush current <8 - 10In Bypass input voltage PXP 1000 1x220/ 230 / 240 V +/-10 % PXP 3000 3x380/ 400 /415 V+/-10 % Bypass input frequency 50 / 60 Hz + / -8 % Battery voltage 400 VDC Battery operating range 335 - 540 VDC Float voltage at -10 % line power programmable within battery operating range Boost voltage at nominal line...

 Open the catalog to page 2
Technical Data Sheet_PXP-3

Spcification PXP Battery asymmetry supervision Typical single-line drawing Diode for reverse polarity protection Up to 3 sensors for temperature dependent battery charging voltage (recommended for Valve Regulated Lead Acid (VRLA) battery) Optional features - UPS output Other output voltages: 1x110, 115, 120, 127, 254, 265, 277 V 3x190, 200, 208, 220, 230, 440, 460, 480, 500, 525, 600, 660, 690V_ Without isolation transformer on inverter output " T002 Analog meters 72x72 mm or 96x96 mm (directly beside of HMI): Rectifier mains (voltage, current, frequency) Bypass mains (voltage, current, frequency)...

 Open the catalog to page 3
Technical Data Sheet_PXP-4

Human-machine interface (front panel) The front panel includes a comprehensive and flexible human-machine interface. It is divided into three sections: Control and display consists of an LC display, i ndication LEDs for operating modes, and push buttons to navigate through the display menus and control the UPS. The user can access measurement data and system information via display menus, including the event and alarm logs. Mimic indicates the current operational status of the system and its components. It clearly shows the power path currently supplying the load and the availability of the other...