video corpo

Symmetra MW
1 /4Pages

Symmetra MW

Symmetra MW
1 /4Pages

Catalog excerpts

Symmetra MW-1

Symmetra MW Scalable from 400 kW to 1600 kW Parallel-capable up to 6.4 MW Ultra energy efficient, modular, scalable, three-phase power protection with industry-leading performance for large data centers and mission-critical environments • Ultra-high efficiency (97%) in full protection mode • Scalable power protection — pay as you grow • Up to 97% efficient in 2N configurations with Efficiency Booster Mode • Modular design provides inherent redundancy • Now with Integrated Parallel up to 1 MW • Unity input power factor corrected • Low total cost of ownership • Fault-tolerant, robust platform design • Robust design protects a broad range of load types • Parallel capable for capacity or redundancy • Network manageable

 Open the catalog to page 1
Symmetra MW-2

Features and benefits Think big, think scalable — The world’s largest modular UPS modular, fault-tolerant UPS in the 400 – 1600 kW range. As the only UPS capable of scaling up to 1.6 MW in a single module and paralleling UPSs to provide up to 6.4 MW of power, Symmetra MW is ideal for large data centers or complete buildings. Symmetra Symmetra™ MW redefines high-power UPS technology as a MW is also ideally suited for healthcare and other critical facility protection requirements with rigorous and changing electrical demands. Setting a new standard for low cost of ownership, Curve fit to measured...

 Open the catalog to page 2
Symmetra MW-3

Ultra-high efficiency in full protection mode With over 97% efficiency at full load, 96.6% efficiency at 50% load, and above 94% efficiency at 25% load, Symmetra MW delivers significant electrical cost savings without putting the load at risk. Built-in redundancies prevent individual component failures from affecting the load; standardized power modules ensure robust performance, easy maintenance, and rapid repairs without jeopardizing the critical load. Modular design • High overload capability (200% for 60 seconds, 125% for 10 minutes, 150% on battery for 30 seconds) • High fault-clearing capability...

 Open the catalog to page 3
Symmetra MW-4

Technical specifications 400 V Symmetra MW (kW/kVA) Input Integrated parallel, 400 – 1000 kVA Nominal input voltage Grid system Voltage range Frequency range Nominal input current Maximum input current Maximum short circuit withstand (kA) Output Integrated bypass for 400-1000 kva Power rating External bypass under 800 -1600 1000 kVA Voltage (nominal) Nominal output current (A) Overload (normal and battery operation) 200% for 60 seconds 125% for 10 minutes On battery: 150% for 30 seconds Efficiency AC–AC at nominal mains Environmental Storage temperature, UPS, and batteries Operating temperature*...

 Open the catalog to page 4

All Schneider Electric catalogs and technical brochures

  1. Smart-UPS VT

    4  Pages

  2. flyer_PXP

    4  Pages

  3. flyer_PxW

    4  Pages

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.