Symmetra MW Scalable from 400 kW to 1600 kW Parallel-capable up to 6.4 MW Ultra energy efficient, modular, scalable, three-phase power protection with industry-leading performance for large data centers and mission-critical environments • Ultra-high efficiency (97%) in full protection mode • Scalable power protection — pay as you grow • Up to 97% efficient in 2N configurations with Efficiency Booster Mode • Modular design provides inherent redundancy • Now with Integrated Parallel up to 1 MW • Unity input power factor corrected • Low total cost of ownership • Fault-tolerant, robust platform design • Robust design protects a broad range of load types • Parallel capable for capacity or redundancy • Network manageable
Open the catalog to page 1Features and benefits Think big, think scalable — The world’s largest modular UPS modular, fault-tolerant UPS in the 400 – 1600 kW range. As the only UPS capable of scaling up to 1.6 MW in a single module and paralleling UPSs to provide up to 6.4 MW of power, Symmetra MW is ideal for large data centers or complete buildings. Symmetra Symmetra™ MW redefines high-power UPS technology as a MW is also ideally suited for healthcare and other critical facility protection requirements with rigorous and changing electrical demands. Setting a new standard for low cost of ownership, Curve fit to measured...
Open the catalog to page 2Ultra-high efficiency in full protection mode With over 97% efficiency at full load, 96.6% efficiency at 50% load, and above 94% efficiency at 25% load, Symmetra MW delivers significant electrical cost savings without putting the load at risk. Built-in redundancies prevent individual component failures from affecting the load; standardized power modules ensure robust performance, easy maintenance, and rapid repairs without jeopardizing the critical load. Modular design • High overload capability (200% for 60 seconds, 125% for 10 minutes, 150% on battery for 30 seconds) • High fault-clearing capability...
Open the catalog to page 3Technical specifications 400 V Symmetra MW (kW/kVA) Input Integrated parallel, 400 – 1000 kVA Nominal input voltage Grid system Voltage range Frequency range Nominal input current Maximum input current Maximum short circuit withstand (kA) Output Integrated bypass for 400-1000 kva Power rating External bypass under 800 -1600 1000 kVA Voltage (nominal) Nominal output current (A) Overload (normal and battery operation) 200% for 60 seconds 125% for 10 minutes On battery: 150% for 30 seconds Efficiency AC–AC at nominal mains Environmental Storage temperature, UPS, and batteries Operating temperature*...
Open the catalog to page 43 Pages
4 Pages
4 Pages
12 Pages
8 Pages
4 Pages
4 Pages
4 Pages
4 Pages
8 Pages
6 Pages
4 Pages
4 Pages
23 Pages
5 Pages