General Presentation
The Evolis circuit breakers are designed for medium voltage applications ranging from 7.2 kV to 24 kV. They are available in fixed and withdrawable versions, suitable for various installation requirements. The circuit breakers operate via a spring mechanism, ensuring consistent operation speed without the need for auxiliary power. Motorized versions support telecontrol functions and rapid reclosing cycles.
Applications
Evolis circuit breakers are used in medium voltage networks for utilities, infrastructure, process industries, and the tertiary sector. They provide protection for cables, overhead lines, motors, capacitors, transformers, and busbar sections.
Vacuum Technology
Schneider Electric employs advanced vacuum technology in Evolis circuit breakers, utilizing Axial Magnetic Field (AMF) techniques to maintain low contact erosion and high electrical endurance. The vacuum interrupters are manufactured with precision to ensure long-term reliability.
Compliance and Testing
Evolis circuit breakers comply with IEC 62271-100 standards and are produced in ISO 9001 and ISO 14001 certified facilities. Each unit undergoes rigorous testing, including vacuum level testing using the magnetron discharge method.
Product Range
The Evolis range includes fixed, frontal or lateral versions, withdrawable frontal versions with NEX cradle or MC cassette, and fixed lateral versions with integrated protection chain (EVOset). Accessories and additional components are available to customize installations.
Technical Specifications
Key specifications include rated voltages up to 24 kV, short circuit breaking capacities from 25 to 50 kA, and rated currents from 630 to 3150 A. The circuit breakers are designed for high electrical endurance and minimal maintenance.
Environmental Considerations
The design of Evolis circuit breakers considers environmental impacts, with a Product Environment Profile (PEP) and end-of-life processing guidelines provided.
Conclusion
Evolis circuit breakers offer a reliable and adaptable solution for medium voltage distribution, combining advanced vacuum technology with robust design and compliance with international standards.
Main Characteristics
The Evolis 17.5 kV fixed version circuit breaker is designed according to IEC 62271-100 standards. It features a rated switching sequence of O-3 min-CO-3 min-CO and various operating times: opening < 50 ms, breaking < 60 ms, and closing < 65 ms. The service temperature ranges from -25°C to +40°C, with mechanical endurance classified as M1(2) - M2, supporting 2000(2) to 10,000 switching operations. Electrical endurance is classified as E2, with specific switching operations at full Isc value: 25 kA (100 operations), 31.5 kA (50 operations), and 40 kA (30 operations).
Electrical Characteristics
The circuit breaker supports phase-to-phase distances of 145, 185, and 240 mm, with rated voltages of 7.2, 12, and 17.5 kV at 50/60 Hz. Insulation levels include power frequency withstand Ud kV at 50 Hz for 1 min and lightning impulse withstand Up kV peak. Rated currents are available in various configurations, with short circuit currents Isc kA ranging from 25 to 40 kA.
Composition and Connection
The circuit breaker is equipped with drilled copper connection terminals and offers several connector variants, including fixed, horizontal, vertical, and mixed connectors. Adjustable connectors allow for increased vertical distance and rotation. The connectors support unplated or tin-plated copper and aluminium conductors.
Functions and Mechanisms
The Evolis circuit breaker includes MV and LV connection options, with LV connections available directly on the terminal block or via LV plugs (18-pin and 24-pin versions). The P2 stored energy operating mechanism ensures independent opening and closing speeds, with electrical and manual control options. The opening circuit includes shunt opening releases (MX1 and MX2), undervoltage releases (MN), and low energy releases (Mitop).
Remote Control and Indication
Remote control is facilitated by an electrical motor (MCH) and shunt closing release (XF), allowing for remote opening and closing. Indication features include rotary type contacts for "open/closed" positions and a "ready to close" PF contact. The operation counter (CDM) tracks usage, and auxiliary contacts provide additional control and indication capabilities.
Overview
The document provides detailed technical specifications and operational guidelines for the Evolis 17.5 kV circuit breaker, available in both fixed and withdrawable versions. It covers various aspects such as mechanical indicators, locking mechanisms, electrical characteristics, and installation instructions.
Specifications
The circuit breaker is designed to indicate readiness to close through a mechanical indicator and a PF changeover contact. Key conditions include the circuit breaker being open, energy springs armed, and no permanent closing or opening orders.
Electrical Characteristics- Breaking capacity: Standard minimum load is 100 mA/24 V with various voltage and current ratings for AC and DC.
- Low-level minimum load: 2 mA/15 V DC with specified ratings for AC and DC.
- Rated voltage (Ur): 7.2, 12, and 17.5 kV with corresponding insulation levels and short-circuit currents.
Locking and Interlocking
The circuit breaker can be locked in the open position using padlocks or keylocks. The locking mechanism can be achieved through screws, padlocks, or lead seals. Keylocks are available in Profalux or Ronis types.
Operation and Control- Operation counter visible on the front panel records the number of switching cycles.
- Remote control and opening mechanisms include shunt releases and electrical motors.
Installation and Dimensions
Detailed installation instructions are provided in the Evolis Installation Guide. The document specifies phase-to-phase distances and weights for different configurations.
Order and Configuration
The document includes an order form with options for rated voltage, short-circuit current, and various locking and control mechanisms. It also outlines the structure for ordering separated components and accessories.
Safety and Standards
The circuit breaker complies with IEC 62271-100 standards, ensuring safety and reliability in operation. It includes safety interlocking systems and is suitable for switching and protection of capacitor banks.
Conclusion
The Evolis 17.5 kV circuit breaker is a versatile and reliable solution for medium voltage applications, offering comprehensive safety features and customizable options to meet specific operational needs.
Overview
The document provides a detailed technical description of the Evolis 17.5 kV withdrawable version in a NEX cradle, focusing on its components, functions, and safety features.
Specifications and Components
The cradle floor includes fixing holes for positioning the earthing switch control mechanism and power circuit, ensuring reliable operation and interlocking with the circuit breaker. Earthing is automatic when the truck is fully racked in, and protective shutters provide IP2X protection. Accessories include auxiliary contacts, a sliding copper contact for earthing, and a key locking system for safety.
Power Circuit
The power circuit consists of mobile contacts, disconnectable clusters, and arms mounted on the circuit breaker, with fingers attached to the cradle. This setup ensures dielectric strength, mechanical integrity, and temperature control, validated through tests.
Connection
Connections are made via vertical copper terminals and a connector set. For circuit breakers with a rated voltage of 17.5 kV, field deflectors enhance dielectric strength.
LV Connection
The LV wiring uses an LV plug with fixed and mobile parts, available in 18-pin and 42-pin versions, supporting various auxiliary contacts and control mechanisms. An interlocking function prevents racking in without the LV plug connected.
P2 Stored Energy Operating Mechanism
This mechanism provides independent opening and closing speeds, with automatic recharging by a geared motor. It includes manual and electrical control devices, an operation counter, and position indicators.
Opening Circuit
The opening circuit includes shunt opening releases, undervoltage releases, and a low energy release (Mitop). The undervoltage release opens the circuit breaker when voltage drops below a certain threshold.
Remote Control
Remote control allows for opening and closing the circuit breaker, with an anti-pumping function to prevent unwanted reclosing. It includes an electrical motor and a shunt closing release.
Indication and Safety Functions
Auxiliary contacts indicate the circuit breaker's position, and a "ready to close" contact provides status information. Safety features include locking mechanisms for the circuit breaker and cubicle door, ensuring operation only when the door is closed.
Locking/Interlocking
Various locking mechanisms are available, including padlocks and keylocks, to secure the circuit breaker in the open position and prevent unauthorized access.
Conclusion
The document outlines the comprehensive safety and operational features of the Evolis 17.5 kV withdrawable version, emphasizing its reliability and compliance with IEC standards.
Overview
The document provides a detailed technical description of the Evolis 17.5 kV withdrawable circuit breaker, specifically its version in the NEX cradle and MC cassette. It outlines the safety functions, electrical characteristics, and operational procedures associated with the device.
Specifications
The Evolis circuit breaker is designed for medium voltage (MV) applications, with a rated voltage range of 7.2 to 17.5 kV. It supports various phase distances (145 mm, 185 mm, 240 mm) and rated currents (630 A, 1250 A, 2500 A). The short-time withstand current ranges from 25 kA to 40 kA, with a making capacity of 2.5 to 2.6 times the short-circuit current.
Safety Functions
The circuit breaker includes several safety interlocks to prevent improper operations. These include mechanisms to prevent closing when the breaker is open, racking-in when the door is open, and earthing switch closure when the breaker is closed. Interlocking devices ensure that the circuit breaker cannot be racked in or out unless it is in the open position.
Operational Procedures
The circuit breaker can be operated in three positions: service, test, and disconnected. The racking mechanism uses a threaded shaft for ease of operation. The device includes a test position contact and optional earthing systems.
Electrical Characteristics
The document specifies the electrical characteristics according to IEC 62271-100 standards, including insulation levels, rated currents, and short-circuit capacities. The circuit breaker is suitable for switching and protection of capacitor banks with installed power up to 2 Mvar.
Components and Accessories
The document lists various components and accessories available for the Evolis circuit breaker, including remote control mechanisms, shunt releases, undervoltage releases, and auxiliary contacts. It also details the offer structure for ordering separate components and services.
Installation and Maintenance
Detailed installation instructions are provided in the Evolis Installation Guide. The document emphasizes that certain components can only be adapted or replaced by trained personnel.
Conclusion
The Evolis 17.5 kV withdrawable circuit breaker is a robust and versatile device designed for medium voltage applications, offering comprehensive safety features and operational flexibility.
Overview: This document provides a detailed technical description of the Evolis 17.5 kV withdrawable circuit breaker in an MC cassette. It outlines the specifications, safety functions, interlocking mechanisms, and operational procedures associated with the device.
Specifications: The Evolis circuit breaker is designed for use in medium voltage (MV) applications and is housed in an MC cassette. It includes components such as guide rails, fixed connection fingers, and metal shutters for safety. The device is compliant with IEC standard 62271-200.
Safety Functions: The MC cassette includes several safety features:
- Metal shutters to prevent access to live parts when the circuit breaker is extracted.
- Safety interlocking systems to padlock shutters and unlock access mechanisms.
- An anti-drop function to ensure operator safety during extraction.
Interlocking Mechanisms: The circuit breaker can only be racked in if the cubicle door is closed and can only be opened if the circuit breaker is racked out. This interlocking function is crucial for safety and must be disabled if not present.
Operating Positions: The document describes various operating positions such as test, disconnected, and service positions, each with specific safety and operational requirements.
Connection Details: - MV connections are made at the rear of the cassette.
- LV connections use a Harting connector system, ensuring secure and reliable connections.
Operating Mechanism: The P2 stored energy operating mechanism allows for independent opening and closing speeds. It includes a gear motor for automatic recharging and manual operation options.
Opening Circuit: The opening circuit includes shunt opening releases, undervoltage releases, and a low energy release (Mitop). These components ensure the circuit breaker opens under specific conditions, such as voltage drops.
Remote Control: The circuit breaker supports remote control operations, prioritizing opening orders over closing orders. It includes an electrical motor for automatic spring rearming and a shunt closing release for remote operations.
Indication and Monitoring: The device features auxiliary contacts for position indication, a "ready to close" contact, and an operation counter to track switching cycles.
Dimensions and Weight: The document provides detailed dimensions and weight specifications for different cassette models (MC1, MC2, MC3).
Overview
The document provides detailed technical specifications and operational guidelines for the Evolis HP circuit breaker, specifically the withdrawable version in an MC cassette. It outlines the components, functions, and safety features of the circuit breaker, as well as the options available for customization and the standards it complies with.
Specifications
The Evolis HP circuit breaker is designed for medium voltage (MV) applications, with a rated voltage of up to 15 kV and a rated current of up to 3150 A. It complies with IEC 62271-100 standards, ensuring high electrical and mechanical endurance. The circuit breaker can withstand short-circuit currents up to 50 kA and has a service temperature range of -5 to +40°C.
Components and Features
The circuit breaker includes a vacuum interrupter, an RI stored energy operating mechanism, and a front panel with manual controls and indicators. It is equipped with racking arms and contact fingers for easy installation and removal. Optional features include key locks for securing the breaker in open or racked-out positions, and various cassette options for enhanced safety and functionality.
Operating Mechanism
The RI stored energy operating mechanism allows for independent opening and closing speeds, whether operated manually or electrically. It includes a manual lever and an optional geared motor for automatic recharging. The mechanism supports remote control operations and includes various release units such as shunt opening, undervoltage, and low energy Mitop releases.
Safety and Interlocking
The circuit breaker features multiple safety interlocks to prevent incorrect operations, such as racking in or out when the breaker is not in the open position. The MC cassette includes metal shutters and safety interlocking systems to protect against accidental contact with high voltage parts. An anti-drop function ensures operator safety during extraction.
Connection and Installation
MV connections are made at the rear of the cassette, while LV connections use a Harting connector system. The document provides guidelines for proper installation and maintenance, emphasizing the importance of trained personnel for on-site adaptations.
Accessories and Options
Various accessories are available, including additional auxiliary contacts, a racking handle, and an extraction tool. The document also details optional features like a mechanical circuit breaker racked-in lock and an equipped MV access door.
Conclusion
The Evolis HP circuit breaker is a robust and versatile solution for MV applications, offering high performance and safety features. Its modular design allows for customization to meet specific operational needs, making it suitable for a wide range of industrial and distribution network applications.
Overview: This document provides technical specifications and operational details for the Evolis HP withdrawable circuit breaker in an MC cassette. It includes information on various release mechanisms, remote control functions, safety features, and ordering options.
Release Mechanisms:- Shunt Opening Release (YO1 and YO2): Energizing these units causes instant opening of the circuit breaker. They operate within a voltage threshold of 0.85 to 1.1 Ur for AC and 0.7 to 1.1 Ur for DC, with consumption rates of 160 VA for AC and 50 W for DC.
- Undervoltage Release (YM): This unit opens the circuit breaker when voltage drops below 35% of the rated voltage. It prevents closing until voltage reaches 85% of the rated value. Consumption is 400 VA for AC and 100 W for DC during triggering.
- Low Energy Release (Mitop): Designed for Sepam 100LA relays, it operates with a current threshold between 0.6 A and 3 A.
Remote Control Functions:- Electrical Motor with Gearing: Automatically rearms the stored energy unit for instant reclosing. Operates within a voltage threshold of 0.85 to 1.1 Ur for both AC and DC, with a consumption of 380 VA/W.
- Shunt Closing Release (YF): Allows remote closing of the circuit breaker when armed, with an anti-pumping relay to prevent uncontrolled cycles.
- Operation Counter: Displays the number of switching cycles on the front panel.
Safety Features: The document outlines safety functions for various circuit breaker positions, including insertion, extraction, and racking operations. It includes fool-proof protection, anti-drop mechanisms, and interlocking devices to ensure safe operation.
Dimensions and Weight: The Evolis HP circuit breaker in an MC cassette has dimensions of 886 mm (W) x 980 mm (H) x 902 mm (D) and weighs 338 kg.
Ordering Information: The document provides a detailed order form with options for different release mechanisms, remote control configurations, and MC cassette types. It also lists separate components and accessories that can be ordered and replaced by trained personnel.
Additional Notes: The document emphasizes the importance of confirming specifications as standards and designs may change over time. It is published by Schneider Electric Industries SAS.