1. Catalogs
  2. SCAME PARRE S.p.A.
  3. ADVANCE GRP 125A Series

ADVANCE GRP 125A Series

ADVANCE GRP 125A Series
1 / 12 PagesView full catalog

ADVANCE GRP 125A Series

Product catalog summary
Overview: The ADVANCE GRP Series 125A is a range of switched interlocked socket outlets designed for industrial use, particularly in environments with potential explosive risks (Zone 22). These products comply with the ATEX Directive and various EN and IEC standards.
Specifications: The series includes versions with switch-disconnectors, contactors, fuses, and molded case circuit breakers with thermal magnetic and residual current release trip units. Rated current is 125A, with a voltage range of 100-690V and frequency of 50-60Hz. The protection degree is IP66, and the operating temperature ranges from -25°C to +60°C.
Standards and Compliance: The products adhere to EN 60309-1, EN 60309-2, EN 60309-4, IEC 61241-0, and IEC 61241-1 standards, ensuring safety and compatibility for industrial applications.
Technical Characteristics: The socket outlets feature a high degree of impact resistance (IK10), are made from thermoset material, and have a self-extinguishing capability tested at 850°C/960°C. They are equipped with ABB OT 160 switch-disconnectors and ABB Tmax T1B circuit breakers.
Interlock Versions: Available in mechanical and electrical interlock versions, ensuring safety by preventing disconnection under load. The interlocked sockets are monitored electronically to indicate power status and fuse conditions.
Applications: Suitable for use in potentially explosive environments, these socket outlets are designed for easy installation with features like ample wiring space, outdoor wall fastening, and self-centering punch marks for drilling.
Complementary Products: The OPTIMA-EX Series plugs are compatible with these socket outlets, offering IP66/IP67 protection.
Dimensions: Detailed dimensions are provided for various configurations, ensuring compatibility with installation requirements.
See more

Catalog excerpts

ADVANCE GRP 125A Series-1

ADVANCE GRP Series 125A Switched Interlocked socket outlets

 Open the catalog to page 1
ADVANCE GRP 125A Series-2

ADVANCE GRP Series 125A > SWITCHED INTERLOCKED SOCKET OUTLETS EN 60309-1 Plugs, socket outlets and couples for industrial purposes. Part 1: general requirements. EN 60309-2 Plugs, socket outlets and couples for industrial purposes. Part 2: dimensional interchangeability requirements for pin and contact-tube accessories of harmonised configurations. EN 60309-4 Plugs, socket-outlets and couplers for industrial purposes. Part 4: Switched socket-outlets and connectors with or without interlock. > VERSIONS WITH MECHANICAL INTERLOCK With switch-disconnector IEC 61241-0 / EN 61241-0 Electrical apparatus...

 Open the catalog to page 2
ADVANCE GRP 125A Series-3

Saline solution Concentrated Resistant Limited Resistance Limited Resistance Limited Resistance Limited Resistance Limited Resistance > BEHAVIOUR WITH CHEMICAL AND ATMOSPHERIC AGENTS For specific substances please contact our technical service > TECHNICAL CHARACTERISTICS Rated current: Rated voltage: Frequency: Insulating voltage: Protection degree: Operating temperature according to the reference standard: Max. operating temperature: Self-extinguishing GW test: Self-extinguishing UL94: Material: IK degree at 20°C: Cable inlets: 60°C 850°C/960°C V0 Thermoset IK10 Top side max 3xM63 Bottom side...

 Open the catalog to page 3
ADVANCE GRP 125A Series-4

ADVANCE GRP Series 125A > APPLICATION EXAMPLES

 Open the catalog to page 4
ADVANCE GRP 125A Series-5

> TECHNICAL DATA SWITCH DISCONNECTORS Rated impulse withstand voltage Uimp Thermal current Ithe Rated insulation voltage Ui AC21A Resistite loads, inluding moderate overloads Nominal current rating Ie Mixed resistite and inductive loads, AC22A including moderate overloads Switching off motor loads or other AC23A highly inductive loads (3 phase/3 pole) Squirrel-cage motor: starting, switching off motor during running (3 phase/ 3 pole) Resistite loads, including Moderate overloads Mixed resistite and inductive loads, including moderate overloads Short-circuit protection Rated short-time withstand...

 Open the catalog to page 5
ADVANCE GRP 125A Series-6

Outdoor wall fastening Ample space for easy wiring Under-plate cable runway Switchdisconnector with mechanical lock that can be accessorized with auxiliary contacts Threaded metal inserts Punched marks for easy closure of the cover Easily extractable bottom plate Possibility to assemble microswitch BOTTOM VIEW Module in hightemperature glassfibre filled engineering polymer Possible entry from bottom side (input-output also) Self-centering punch marks to facilitate drilling

 Open the catalog to page 6
ADVANCE GRP 125A Series-7

Single-piece waterproof gasket Rating on metal plate Captive stainless steel closing screws Lockable Switch in position 0 and 1 High-strength material with superior UV and chemical resistance Double mechanical lock and metal levers Residual current release trip units test push button Cover entirely separate from the base for easy installation An electronic device controls the status of the interlocked socket, monitoring the electrical functionality: - operation of the signalling and control card is guaranteed even when the load is not connected; - indicates that the fuses are not open and all...

 Open the catalog to page 7
ADVANCE GRP 125A Series-8

ADVANCE GRP Series 125A > MECHANICALLY INTERLOCKED SOCKET OUTLETS - IP66 Molded case 2P+E 125A 50/60 circuit breaker 3P+E 125A 50/60 with thermal magnetic trip unit 3P+N+E 125A 50/60 Molded case 2P+E 125A 50/60 circuit breaker with thermal magnetic 3P+E 125A 50/60 and residual current release trip units 3P+N+E 125A 50/60 (*) Fuses not included

 Open the catalog to page 8
ADVANCE GRP 125A Series-9

> ELECTRICALLY INTERLOCKED SOCKET OUTLETS - IP66 (*) Microswitch already provided. Contactor operated by microswitch. Microswitch kit 400V 10A 1NO+1NC (microswitch + terminal block) For products with mechanical interlock. > COMPLEMENTARY PRODUCTS - OPTIMA-EX SERIES - PLUGS IP66/IP67

 Open the catalog to page 9
ADVANCE GRP 125A Series-10

ADVANCE GRP Series 125A > DIMENSIONS

 Open the catalog to page 10
ADVANCE GRP 125A Series-11

Molded case circuit breaker with thermal magnetic trip unit Molded case circuit breaker with thermal magnetic and residual current release trip units

 Open the catalog to page 11
ADVANCE GRP 125A Series-12

electrical solutions

 Open the catalog to page 12