1. Catalogs
  2. SATEC
  3. PM135 Datasheet

PM135 Datasheet

PM135 Datasheet

PM135 Datasheet

Product catalog summary
Overview: The PM135 is a versatile three-phase power meter suitable for industrial, commercial, and utility applications. It combines revenue metering, power quality, and harmonics analysis, offering a cost-effective alternative to multiple analog meters. Compatible with panel boards and SCADA systems, it supports various communication protocols, making it ideal for utility substation automation.
Models and Features: The PM135 series includes three models: PM135P (basic power meter), PM135E (includes revenue metering), and PM135EH (adds power quality control). It measures over 100 electrical parameters, features a backlit LCD display, and a bar graph loading indicator. It supports frequencies of 25, 50, 60, and 400 Hz and can connect directly up to 690V L-L.
Measurement and Communication: The PM135 measures frequency, voltages, currents, power, energy, and harmonics. It includes an RS-485 communication port and supports Modbus, DNP 3.0, and IEC 60870 protocols. Expansion modules offer additional communication ports, including Ethernet and GPRS.
Power Quality and Revenue Metering (EH Model): The EH model provides advanced features like individual voltage and current harmonics analysis up to the 40th order, THD, TDD, K-Factor, and real-time waveform capture. It exceeds accuracy class 0.5S and supports Time Of Use (TOU) tariffs.
Event and Data Recording: The PM135 includes non-volatile memory for long-term event and data recording, with capabilities for logging system events, data logs, and automatic daily energy profiles.
I/O Options: Various modules are available, including digital inputs, relay outputs, and analog outputs, allowing for extensive customization and integration into different systems.
Technical Specifications: The PM135 operates in temperatures from -30°C to 60°C and supports a wide range of power supply options. It features robust construction with a plastic enclosure and complies with multiple international standards for accuracy, electromagnetic immunity, and safety.
Ordering Information: Detailed ordering options are provided for different configurations, including current inputs, calibration frequencies, power supply options, communication protocols, and mounting preferences.
Specifications:
  • Repeaters and Antennas: Options for antennas without cables, with 2M cables, and external antennas for modules or concentrators are specified for ETC2002 configurations.
  • High Accuracy Current Sensors (HACS): SATEC's proprietary HACS are designed for use with HACS-ready meters and analyzers, offering high accuracy, wide bandwidth for harmonic measurement, safety without shorting bars, and long cable lengths up to 200m without performance degradation.
Product Variants:
  • 100A HACS: Available in solid core with Φ12mm and Φ23mm holes, and split core with Φ16mm hole.
  • 200A HACS: Available in split core with 26x23.8mm and 23×33mm holes.
  • 400A HACS: Available in solid core with Φ26mm hole and split core with 23×33mm hole.
  • 800A HACS: Available in solid core with 100×32mm / Φ62mm hole and split core with 80×50mm hole.
  • 1200A HACS: Available in split core with 80×121mm hole.
Notes:
  • RF modules and accessories are region-specific; consultation with local suppliers is recommended.
See more

Catalog excerpts

PM135 Datasheet-1

The PM135 is a multi-functional three-phase power meter with basic revenue metering, power quality and harmonics analysis. The PM135 provides a cost-effective substitute for numerous analog meters used by industrial, commercial and utility customers for basic power metering. The PM135 is widely integrated in panel boards and SCADA systems. With the addition of the unique TOU module, the EH model answers the needs of revenue metering applications. It is also suitable for utility substation automation with its support of the industry standard DNP 3.0, Modbus RTU and IEC 60870-5101/104 protocols, as well as its I/O capabilities (using the Digital Input/Output modules). The PM135 series consists of two basic models providing digital measurements of more than 80 electrical parameters locally, and more than 100 electrical parameters via RS-485 interface. The PM135 has a 3x2” / 76x49mm backlit LCD display as well as SATEC's unique bar graph loading indicator. Measurement & Communication The PM135 accurately measures over 100 parameters from basic frequency, voltages and currents, to all power parameters, four quadrant active, reactive and apparent energies, harmonics and time of use (TOU). Measurement Features The PM135 has an integral RS-485 communication port for a wide range of protocols—Modbus, DNP 3.0 and IEC 60870. Its expansion module allows connection of a second communication port, including Ethernet, Profibus, RF or GPRS, as well as second RS-485 and RS-232 ports. Multi-functional 3-phase power meter functionality (see Features) PM135E All the features of the P model plus Revenue Meter (see Features) PM135EH All the features of the E model plus Power Quality control (see Features) Current Inputs 1A 5A RS5 HACS Standard 1A CT Standard 5A CT Remote Split Core for Standard 5A CT High Accuracy Current Sensors Specifications are subject to change without notice. Copyright © 2011-13 SATEC Ltd.

 Open the catalog to page 1
PM135 Datasheet-2

erful Solutions ■» Voltage, current (including neutral current), power, energy, power factor, frequency, voltage/current unbalance Basic Power Quality Control ■» Individual voltage and current harmonics (up to Voltage and current THD, TDD & K-Factor ■» Time stamped max/min values ■» Waveforms 128 samples/cycle (via comm.) Revenue Meter (EH Model) ■» Exceeds accuracy class 0.5S ■» System events & data logging Harmonic Analyzer (EH Model) ■» Voltage and current THD, current TDD and K-Factor, up to 40th order harmonic ■» Voltage and current harmonic spectrum and Real-time Waveform Capture ■» Real-time...

 Open the catalog to page 2
PM135 Datasheet-3

PM135 Event and Data Recording (E & EH) Non-volatile memory for long-term event and data recording Event recorder for logging internal diagnostic events and setup changes Two data recorders; programmable data logs on a periodic basis; automatic daily energy and maximum demand profile log TOU+4DI module – four digital inputs with 1ms scan time and battery backup for the real time clock; automatic recording of last five digital input change events with timestamps (see the PM135 Modbus Reference Guide) 4DIO – four digital inputs and two relay outputs with 1-cycle update time; unlatched, latched,...

 Open the catalog to page 3
PM135 Datasheet-4

PM135 Technical Specifications ENVIRONMENTAL CONDITIONS INPUT RATINGS Operating temperature VOLTAGE INPUTS Storage temperature Dimensions [H×W×D] MATERIALS Case enclosure plastic PC/ABS blend Front panel Connectors-Plugin type Packaging case Carton and Stratocell® (Polyethylene Foam) brackets Wire size CURRENT INPUTS (Via CT) Wire size Galvanic isolation 5A SECONDARY or 5A REMOTE SENSOR (RS5) Operating range < 0.2 VA @ In=5A (with 12AWG wire and 1 m long) Overload withstand 15A RMS continuous, 300A RMS for 1 second (with 12AWG section wire) POWER SUPPLY 120/230V AC-DC Option Direct input and...

 Open the catalog to page 4
PM135 Datasheet-5

OPTIONAL RELAY OUTPUTS OPTIONAL ANALOG OUTPUTS ELECTROMECHANICAL RELAY Dry Contact, Option (4DI/DO or 12DI/DO Optional module) 4 Analog Outputs optically isolated (AO Optional module) 2 or 4 relays rated at 5A/250 VAC; 5A/30 VDC, 1 contact (SPST Form A) Ranges (upon order) Power supply Update time Connector type 2 relays rated at 0.15A/250 V AC/DC, 1 contact (SPST Form A) Wire size Galvanic isolation Operate time RS-485 optically isolated port Release time Update time Baud rate Connector type Wire size Supported protocols Modbus RTU, DNP3, and SATEC ASCII OPTIONAL DIGITAL INPUTS Connector type...

 Open the catalog to page 5
PM135 Datasheet-6

REAL-TIME CLOCK RS-485 optically isoated Profibus interface Standard Meter Clock Connector type Baud rate 9600 bit/s – 12 Mbit/s (auto detection) 32 bytes input, 32 bytes output Supported protocols TOU Module Meter Clock Non-backed clock Accuracy: typical error 1 minute per month @ 25C Typical clock retention time: 30 seconds Battery-backed clock Accuracy: typical error 7 seconds per month @ 25C (±2.5ppm) Typical clock retention time: 36 months RS-232 or RS-422/485 optically isolated port DISPLAY MODULE Baud rate 3.5" LCD Monochrome Display, 240 x 128 dots resolution Supported protocols Modbus...

 Open the catalog to page 6
PM135 Datasheet-7

PM135 PM135 Order String MODEL Power Version Energy and Harmonic Version Energy Only OPTIONS Current Inputs 5 Ampere 1 Ampere 5A split core remote high accuracy current sensor (HACS) High Accuracy Current Sensors (HACS). Requires ordering of 3 HACS (see HACS Order String on next page) Calibration at Frequency 25 Hz 50 Hz 60 Hz 400 Hz Resolution Low Resolution 1A, 1V High Resolution 0.01A, 0.1V Power Supply 85-265V AC and 85-290V DC 9.5-18V DC 18.5-58V DC (24VDC, 48VDC) Communication Protocol Modbus and DNP 3.0 Modbus and IEC 60870-101/104 Display Language English Russian Spanish Mounting Panel...

 Open the catalog to page 7
PM135 Datasheet-8

PM135 RF Accessories (see note) Concentrator - ROW Concentrator External for 2 x ETC2002 Repeater Antenna 1: without cable (module or concentrator) Antenna 2: with 2M cable (module or concentrator) Antenna 3: external for concentrator only Antenna 4: external for module or concentrator Note: RF module and accessories are available in certain regions only. Please consult your local supplier. HACS (High Accuracy Current Sensors) Order String High Accuracy Current Sensors SATEC Proprietary High Accuracy Current Sensors (HACS) designed to be used with our HACS-ready meters and analyzers. SATEC current...

 Open the catalog to page 8

Archived catalogs

  1. PM175 Specs

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.