Catalog excerpts
T 2171 EN Type 43-1 and Type 43-2 Temperature Regulators Series 43 Self-operated Temperature Regulators Application Regulators for district heating systems, heat generators, heat exchangers and other HVAC and industrial applications. Temperature set points from 0 to 150 °C · G ½ to G 1 · DN 15 to 50 · Pressure rating PN 25 · Suitable for liquids up to 150 °C and non-flammable gases up to 80 °C · The valves close when the temperature rises. Note Typetested temperature regulators (TR), safety temperature monitors (STM) and safety temperature limiters (STL) are available. Special features •• Low-maintenance proportional regulators requiring no auxiliary energy •• Temperature sensor suitable for installation in any desired position and for operation at high excess temperatures (50 K above the set point), designed for operating pressures up to 40 bar (u EB 2430) •• Globe valves with plug balanced by a piston •• Particularly suitable for district heating supply networks •• Suitable for gases and liquids •• Special version: fast-responding thermostats for instantaneous water heater (u EB 2430-3) Versions (Fig. 1 to Fig. 2) Fig. 2: Type 43-2 with flanged body made of spheroidal graphite iron, DN 40 (special version) With body of red brass CCC499K With body stainless steel 1.4408 The regulators consist of a valve and control thermostat with set point adjuster, a capillary tube and temperature sensor operating according to the adsorption principle. Valve body made of red brass, spheroidal graphite iron or stainless steel. See Data Sheet u T 2176 for versions with double adapter or manual adjuster for the attachment of additional control thermostats –– Type 43-1 · Temperature regulator with Type 2431 Valve G ½ to G 1 female thread · Type 2430 Control Thermostat Sensor optionally with or without thermowell –– Type 43-2 · Temperature regulator with Type 2432 Valve DN 15 to 50 · With welding ends (special version with threaded ends, flanges or with flanged body) · Type 2430 Control Thermostat · Sensor optionally with or without thermowell Typetested safety devices The register number is available on request. The following versions are available: Type 43-1 and Type 43-2 Temperature Regulators (TR) for which the maximum operating pressure must not exceed the maximum permissible differential pressure Δp specified in the Fig. 3: Type 43-1 Temperature Regulators technical data. Only SAMSON thermowells can be used for sensors with thermowells. Further details on the selection application of typetested equipment can be found in Information Sheet u T 2181. SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone
Open the catalog to page 1Additionally, the safety temperature monitors (STM) and safety temperature limiters (STL) are available. For more details refer to Data Sheets u T 2183 and u T 2185. Female thread Accessories –– Thermowell made of: Copper, PN 40 CrNiMo steel, PN 40 –– Double adapter Do3 or manual adjuster Ba43 –– Intermediate insulating piece for insulated pipes or medium temperatures down to –15 °C Special versions –– 5 m capillary tube –– Small KVS in DN 15 or G ½ –– Oil-resistant internal parts –– Fast-response thermostats (u EB 2430-3) on request –– ANSI version (u T 2175) –– Stainless steel body for...
Open the catalog to page 2Table 1: Technical data · All pressures in bar (gauge) Type 2431 Valve (Type 43-1) | Type 2432 Valve (Type 43-2) Type 43-1 Type 43-1 · Type 43-2 Pressure rating Max. perm. differential pressure Δp Max. permissible valve temperature Type 2430 Control Thermostat Continuously adjustable: 0 to 35 °C, 25 to 70 °C, 40 to 100 °C, 50 to 120 °C or 70 to 150 °C Set point range 2) Capillary tube Max. perm. temperature at the sensor 50 K above the adjusted set point Permissible ambient temperature range Permissible pressure at sensor/thermowell Special version with KVS 0.4, 1.0 or 2.5 Further set...
Open the catalog to page 3Type 43-1 Temperature Regulator 1 Version without thermowell: minus 0.2 kg 3) Flanged body 2) Valve also with flanged body 4) Flanged body of stainless steel 1.4408
Open the catalog to page 4Special version: vapor pressure thermostats Fast-responding temperature regulators Application The temperature sensors operating according to the vapor pressure principle are particularly suitable for use in plate heat exchangers 1) due to the fast response time of approx. 3 s. Temperature set points from 45 to 65 °C (55 to 75 °C) 2) Type 2430 Control Thermostat in combination with Type 2431 Valve (Type 43-1) or Type 2432 Valve (Type 43-2) · G ½ to G 1 · DN 15 to DN 50 · Pressure rating PN 25 · Copper or CrNiMo steel sensor · Observe mounting position of the sensor. 1) 2) Cold water Fig. 7:...
Open the catalog to page 5Ordering text Type 43-1 Temperature Regulator G ... Set point range ... °C Stainless steel or red brass body Optionally, special version Optionally, accessories ... Type 43-2 Temperature Regulator DN ... With welding ends, threaded ends, flanges or with flanged body Set point range ... °C Optionally, special version Optionally, accessories ...
Open the catalog to page 6Specifications subject to change without notice
Open the catalog to page 8All SAMSON catalogs and technical brochures
-
TROVIS 5590 Web Module
2 Pages
-
Room Controller TROVIS 5572
2 Pages
-
Room Panel TROVIS 5570
2 Pages
-
Line Splitter TROVIS 5486
2 Pages
-
Type 9 Temperature Regulator
6 Pages
-
Type 8 Temperature Regulator
6 Pages
-
Type 5 D Boiler Controller
2 Pages
-
Rotary Plug Valve Type 62.7
7 Pages
-
Actuator Type S
3 Pages
-
Actuator Type MZ
4 Pages
-
Actuator Type MN
3 Pages
-
Actuator Type MD
3 Pages
-
Actuator Type R
3 Pages
-
Actuator Type AT
4 Pages
-
Rotary Plug Valve Type 82.7
7 Pages
-
Rotary Plug Valve Type 73.7
7 Pages
-
Rotary Plug Valve Type 73.3
7 Pages
-
Rotary Plug Valve Type 72.4
7 Pages
-
Rotary Plug Valve Type 72.3
8 Pages
-
SAMSON Positioners
28 Pages
Archived catalogs
-
T21 11
6 Pages