Catalog excerpts
T 2546 EN Type 36-3 Safety Shut-off Valve (SSV) with Pressure Reducing Valve Type 36-8 Safety Excess Pressure Valve (SEV) Self-operated Pressure Regulators Typetested by TÜV (for water) Application Pressure regulators for set points from 2 to 11 bar · Valve sizes DN 15 to 100 · Pressure rating PN 16 to 40 Suitable for water and liquids up to 150 °C Special features •• Low-maintenance proportional regulators requiring no auxiliary energy •• Spring-loaded, single-seated valve with balanced plug •• Frictionless plug stem seal with stainless steel bellows •• Actuator with two independent operating diaphragms, permitting continued operation of the valve even if one diaphragm fails. An indicator at the actuator shows that the actuator is damaged. •• The regulators comply with AGFW (German District Heating Association) regulations. Versions (see Fig. 2 and Fig. 3) Type 36-3 · Safety shut-off valve (SSV) with integrated pressure reducing valve (Fig. 1) · The regulator controls the downstream pressure p2 to the adjusted set point · The regulator continues to operate in the event of an operating diaphragm rupture · Typetested according to AGFW document FW 504 Fig. 1: Type 36-3 Pressure Reducing Valve Type 36-8 · Safety excess pressure valve (SEV) (Fig. 2) · The regulator controls the upstream pressure p1 to the adjusted set point · The regulator continues to operate in the event of an operating diaphragm rupture · Typetested according to AGFW document FW 506 Ordering text Type 36-3 Safety Shut-off Valve with pressure reducing valve or Type 36-8 Safety Excess Pressure Valve DN ... Body material ..., PN ..., Set point range ... bar Fig. 2: Type 36-8 Excess Pressure Valve SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009
Open the catalog to page 1Principle of operation The medium flows through the valve in the direction indicated by the arrow. The position of the plug determines the flow rate across the area released between plug (3) and seat (2). The pressure to be controlled is transmitted to the diaphragm (9) over a control line (12) and converted into a positioning force. This force moves the plug stem (4) and the valve plug (3) with it, opposing the force of the set point springs (7). The spring force (pressure set point) can be adjusted at the set point adjuster (6). The regulators are equipped with two independent operating...
Open the catalog to page 2Table 1: Technical data ■ All pressures in bar (gauge) 1 +10 % for spheroidal graphite iron EN-GJS-400-18-LT (PN 25) and cast steel 1.0619 (PN 40)
Open the catalog to page 3Specifications subject to change without notice
Open the catalog to page 4All SAMSON catalogs and technical brochures
-
TROVIS 5590 Web Module
2 Pages
-
Room Controller TROVIS 5572
2 Pages
-
Room Panel TROVIS 5570
2 Pages
-
Line Splitter TROVIS 5486
2 Pages
-
Type 9 Temperature Regulator
6 Pages
-
Type 8 Temperature Regulator
6 Pages
-
Type 5 D Boiler Controller
2 Pages
-
Rotary Plug Valve Type 62.7
7 Pages
-
Actuator Type S
3 Pages
-
Actuator Type MZ
4 Pages
-
Actuator Type MN
3 Pages
-
Actuator Type MD
3 Pages
-
Actuator Type R
3 Pages
-
Actuator Type AT
4 Pages
-
Rotary Plug Valve Type 82.7
7 Pages
-
Rotary Plug Valve Type 73.7
7 Pages
-
Rotary Plug Valve Type 73.3
7 Pages
-
Rotary Plug Valve Type 72.4
7 Pages
-
Rotary Plug Valve Type 72.3
8 Pages
-
SAMSON Positioners
28 Pages
Archived catalogs
-
T21 11
6 Pages