Overview: The TROVIS 5757-7 is an electric actuator combined with a digital process controller, designed for use with specific SAMSON valves. It is suitable for heating and cooling applications, particularly in small to medium-sized buildings.
Special Features:
  • Outdoor-temperature-compensated control: Adjusts flow temperature based on outdoor temperature with options for rated, reduced, or stand-by operation.
  • Fixed set point control: Maintains a constant temperature, with optional room sensor adjustments.
  • Return flow temperature limitation: Monitors and adjusts flow temperature to prevent exceeding set limits.
  • Compatibility with Type 5257-7 Room Panel for mode settings and remote switchover.
  • Frost monitoring and anti-blocking function for pump protection.
Applications: Suitable for positioning force-locking valves (DN 15 to 25) in heating and cooling systems, with options for outdoor-temperature-compensated control or fixed set point control.
Configuration and Monitoring: The TROVIS-VIEW software allows for configuration, parameterization, and diagnostics, with data transmission via cable or memory pen.
Accessories:
  • TROVIS-VIEW software and hardware package.
  • Various sensors including Type 5267-2 Contact Sensor, Type 5257-7 Room Panel, and Type 5227-2 Outdoor Sensor.
Principle of Operation: The actuator and controller work together to adjust valve positions based on sensor inputs, with manual override available via a handwheel. The system can be configured for different control modes and settings using the TROVIS-VIEW software.
Digital Controller Settings: Various settings are available for control modes, sensor selection, potentiometer input, and more, with default settings provided for each parameter.
Technical Data:
  • Temperature sensor input: Max. 3 x Pt 1000.
  • Operating temperature range: -40 to 150 °C.
  • Power supply: 230 V (±10%)/50 Hz.
  • Degree of protection: IP 42.
Installation and Electrical Connection: The actuator can be mounted in any position except suspended, with specific instructions for electrical connections provided.
Dimensions: Detailed dimensions for the actuator and associated sensors are provided for installation purposes.
See more

Catalog excerpts

TROVIS 5757-7 Electric Actuator with Process Controller-1

TROVIS 5757-7 Electric Actuator with Process Controller for heating and cooling applications Application Electric actuator with integrated digital controller used to position force-locking valves in nominal sizes DN 15 to 25. Designed for installations in small to medium-sized buildings for outdoor-temperature-compensated control, fixed set point control or fixed set point control with room temperature sensors. The TROVIS 5757-7 is a combination of an electric actuator and an integrated digital controller. It is particularly suitable for mounting to SAMSON Types 3222, 3222 N, 2488, and 3267 Valves (DN 15 to 25) as well as to special versions of Type 3226 and Type 3260 Valves. Special features •• Outdoor-temperature-compensated control of a heating circuit: The flow temperature is controlled based on the outdoor temperature over an adjustable heating characteristic. A binary input allows switching between rated and reduced operation or between rated and stand-by operation with frost monitoring. As an alternative to the binary input, the gradient or a level displacement of the heating characteristic can be changed by the adjustment knob of a room sensor. •• Fixed set point control · This function is used to control the heating circuit to a fixed set point. Fig. 1: TROVIS 5757-7 Electric Actuator with Process Controller •• Configuration, parameterization, diagnostic function and direct connection for monitoring using the TROVIS-VIEW software –– Direct data transmission using a connecting cable (direct connection to computer) •• Fixed set point control with room sensor · The set point is changed by the room temperature. A permanently active flash adaptation adapts the supply of heat to the required demand by changing the flow temperature. •• Return flow temperature limitation · The temperature of the return flow is monitored. When an adjustable maximum limit is exceeded, the flow temperature is reduced until it remains below the limit. –– TROVIS-VIEW configuration software for TROVIS 5757-7 Electric Actuator with Process Controller –– Hardware package with a memory pen-64, a connecting cable, and a modular adapter (order no. 1400-9998) •• Type 5257-7 Room Panel can be connected: –– Data transmission using a memory pen –– Convenient room panel with various operating mode settings (Day mode · Night mode · OFF/frost protection) –– Type 5267-2 Contact Sensor (Pt 1000) (Var.-ID: 1058683) –– Binary input on room panel for remote switchover –– Type 5227-2 Outdoor Sensor (Pt 1000) (Var.-ID: 1043862) –– Possible override of the flash adaptation based on the room temperature or heating characteristic (gradient or level with outdoor-temperature-compensated control) implemented by the electric actuator with process controller –– Type 5257-7 Room Panel (Pt 1000) with potentiometer and mode selector switch (Var.-ID: 1180319) Note: Details on Type 3222, Type 3222 N, Type 3267, Type 3226, and Type 3260 Valves can be found in the Data Sheets u T 5866, u T 5867, u T 5894, u T 5863, and u T 5861. •• Frost monitoring and automatic initiation of protective action •• Automatic anti

 Open the catalog to page 1
TROVIS 5757-7 Electric Actuator with Process Controller-2

Principle of operation (Fig. 3) The TROVIS 5757-7 is a combination of an electric actuator and an integrated digital controller. The digital controller is connected to a flow sensor on the input side, which can be optionally upgraded by a return flow, outdoor or room sensor. In addition to the temperature sensor input to measure the flow temperature, the digital controller has a potentiometer input (1000 to 1100 Q or 1000 to 2000 Q). This input influences the heating characteristic in the case of outdoor-temperature-compensated control and the room temperature set point in the case of fixed set...

 Open the catalog to page 2
TROVIS 5757-7 Electric Actuator with Process Controller-3

Digital controller settings The digital controller settings can be changed in the TROVIS-VIEW Configuration and Operator Interface. 11 The default setting F13 - 1 applies for level #2.

 Open the catalog to page 3
TROVIS 5757-7 Electric Actuator with Process Controller-4

Installation Before mounting the actuator on the valve, retract the actuator stem. Hold the actuator stem in this position, while tightening the coupling nut. Any mounting position may be used, however, the actuator may not be installed in a suspended position. Electrical connection Two cables both 2.5 m in length; cable ends fitted with wire-end ferrules Ordering text TROVIS 5757-7 Electric Actuator with Process Controller Technical data TROVIS 5757-7 Electric Actuator with Process Controller TROVIS 5757-7 Electric Actuator with Process Controller 1 Recommendation: use devices with gold contacts...

 Open the catalog to page 4
TROVIS 5757-7 Electric Actuator with Process Controller-5

Electrical connection Application with flow sensor (VS), return flow sensor (RüS) and outdoor sensor (AS) and potentiometer functioning as set point adjuster NOTICE Live wires Note: Terminals at point of installation not included in the scope of delivery. Application with flow sensor (VS), return flow sensor (RüS) and outdoor sensor (AS) and binary input to switch between operating modes Type 5257-7 Room Panel 2 NOTICE Live wires Application with flow sensor (VS), return flow sensor (RüS) and room sensor with mode selector switch and room set point adjuster NOTICE Live wires Application with...

 Open the catalog to page 5
TROVIS 5757-7 Electric Actuator with Process Controller-6

eL Stem retracts aL Stem extends TROVIS 5757-7 Electric Actuator with Process Controller Accessories for heating control Type 5227-2 Outdoor Sensor (Pt 1000) Color: RAL 9016 Type 5267-2 Contact Sensor (Pt 1000) (flow and return flow temperature measurement) Type 5257-7 Room Panel (Pt 1000) Continuous day mode (rated operation) Continuous night mode (reduced operation) Off/frost protection

 Open the catalog to page 6
TROVIS 5757-7 Electric Actuator with Process Controller-8

SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 [email protected] · www.samson.de Specifications subject to change without

 Open the catalog to page 8

All SAMSON catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.