T 5579 EN TROVIS 5579 Heating and District Heating Controller Application Control of max. three control circuits. To control more circuits, several controllers can be linked by a device bus. The controller can communicate with up to six heat meters using the retrofittable meter bus plug-in module. The TROVIS 5579 Heating and District Heating Controller is used to control max. three control circuits: –– Control of a primary heat exchanger or boiler with max. two mixing and one non-mixing heating circuit. Control of a DHW heating in the secondary or primary domestic hot water control circuit Electronics from SAMSON –– Control of two outdoor-temperature-compensated heating circuits and a DHW heating with three valves in the primary circuit –– Control of three outdoor-temperature-compensated heating circuits with three valves in the primary circuit Special features •• Rotary switches for direct access to the operating modes and essential parameters of the control circuits •• Intuitive data retrieval and input by pressing and turning the pushbutton •• Illuminated display •• 365-day clock with max. four time schedules and automatic summer time/winter time changeover; maximum three times-of-use per day (input in steps of 15 minutes) •• Room panels may be connected for each heating circuit: –– Convenient room panels for adjustment of the operating mode, the day and night set points, the times-ofuse for heating, the controller clock and party mode. Additional outdoor and room temperature readings. Connection via device bus –– Room panel to override operating mode and rated room temperature •• Demand-driven control by set point demand by subsequent controllers over a device bus or 0 to 10 V signal. The primary circuit controls the maximum flow temperature demanded plus adjustable boost. •• Applications with solar hot water system available Fig. 1: TROVIS 5579 Heating and District Heating Controller SAMSON AKTIENGESELLSCHAFT · Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507

Open the catalog to page 1
TROVIS 5579 Heating and District Heating Controller - 2

•• Instantaneous heating systems with water flow sensor configurable •• Heating characteristics optionally based on the gradient or based on four points; variable return flow temperature limitation •• Adaptation: automatic adaptation of the heating characteristic (room temperature sensor required) •• Optimization: calculation of the best possible activation and deactivation times for the heating (room temperature sensor required) •• Drying of jointless floors function with adjustable parameter settings •• Pump management function: speed changeover for a heating circulation pump available ••...

Open the catalog to page 2
TROVIS 5579 Heating and District Heating Controller - 3

Electrical connection and installation The controller consists of the housing containing the electronics and a separate terminal board for electrical connection. Two wires of max. 1.5 mm2 may be connected to each terminal. The sensor connection lines must be installed separately from the lines carrying the power supply. For wall mounting, screw the terminal board to the wall. After wiring the controller, place the controller housing onto the terminal board and fasten it with two screws. Two fastening elements for panel mounting are included.

Open the catalog to page 3
TROVIS 5579 Heating and District Heating Controller - 4

Terminal assignment 17 + WMZ/Bed Y COM Y1 19 - (20 mA/10 V)*2 Y2 Y3 Pump management - COM UP on/off UP Speed + Operating voltage - for TROVIS 5570*1 Device bus Meter bus*1 27 Meter bus*1 28 Device bus If the controller is equipped with a meter bus plug-in module, the TROVIS 5570 Room Panel cannot be supplied by the controller. A 50 Ω resistor is required between terminals 17 and 19 for applying a 20 mA signal. Fig. 3: Terminal assignment of the TROVIS 5579 Heating and District Heating Controller Ordering text TROVIS 5579 Heating and District Heating Controller with RS232 system bus...

Open the catalog to page 4