1. Catalogs
  2. SAMSON
  3. Proportional Safety Valve Type 2302

Proportional Safety Valve Type 2302

Proportional Safety Valve Type 2302

Proportional Safety Valve Type 2302

Product catalog summary
Application
The Type 2302 Proportional Safety Valve is designed to maintain water pressure in heating installations, particularly when connected to a district heating system. It supports set points from 3.5 bar to 11 bar, with nominal inlet size DN 20 and outlet size DN 25, and operates under a nominal pressure of PN 16. The valve is suitable for temperatures up to 150 °C and opens when upstream pressure exceeds the response pressure.
Special Features
The valve features high responsiveness and low closing pressure due to a large effective area operating element made of stainless steel. The internal set point springs are isolated from the process medium.
Versions
The Type 2302 valve is available with a nominal pressure of PN 16, and various port configurations including welding end, threaded end, soldered end, or flange. Set point ranges include 3.5 to 5.5 bar, 5 to 7.5 bar, or 6 to 11 bar. A special version offers lead-sealed set point adjustment.
Principle of Operation
The valve operates by balancing the force from the liquid pressure against the closing force of the springs. Adjustments to the spring compression alter the regulating pressure. If the liquid pressure exceeds the set pressure, the valve opens until equilibrium is restored.
Technical Data
Nominal pressure is PN 16 with a maximum permissible temperature of 150 °C. The set point range varies from 3.5 to 11 bar, with a response pressure of ±0.1 bar of the adjusted pressure and a closing pressure approximately 0.1 bar below the adjusted pressure.
Materials
The body and seat are made from CC491K (Rg 5), the plug from 1.4101, with EPDM soft sealing and stainless steel 1.4571 metal bellows.
Discharging Capacity
The valve's discharging capacity varies with temperature and pressure, with specific mass flow rates provided for 20 °C, 120 °C, and 140 °C.
Typetesting
The valve is TÜV-typetested according to the VdTÜV Specification Sheet "Safety Valve 100".
Installation
The valve should be installed in the flow pipe of the heating system, with the flow direction indicated on the valve body. Ensure free discharge and sufficient space for venting.
Dimensions and Weight
The valve dimensions and weight are specified, with a weight of 2.5 kg.
See more

Catalog excerpts

Proportional Safety Valve Type 2302-1

Self-operated Pressure Regulators Proportional Safety Valve Type 2302 Application Valve used to maintain the water pressure in heating installations, especially when connected to a district heating system · Set points from 3.5 bar to 11 bar · Nominal inlet size DN 20 and nominal outlet size DN 25 · Nominal pressure PN 16 · Suitable for temperatures up to 150 °C The valve opens when the upstream pressure rises above the response pressure The direct-acting, spring-loaded safety valve contains a metal bellows and is characterized by its proportional opening and closing behavior. It has therefore been defined as a Safety Valve in accordance with DIN EN 764 and AD Merkblatt A2. Special features • High responsiveness and low closing pressure achieved by an operating element with a large effective area • Operating element (metal bellows) made of stainless steel • Internal set point springs that do not come into contact with the process medium Versions Type 2302 Proportional Safety Valve (Fig. 1) · Nominal pressure PN 16 · Inlet port with welding end in DN 20 (special threaded end or flange) · Outlet port with female thread G 1 and male thread G 1¼, optionally fitted with welding end, threaded end, soldered end or flange in DN 25 or G 1 · Set point ranges: 3.5 bar to 5.5 bar, 5 bar to 7.5 bar or 6 bar to 11 bar. Fig. 1 · Type 2302 Proportional Safety Valve Special version: lead-sealed set point adjustment 7 6 Principle of operation (Fig. 2) The process medium flows through the valve in the direction indicated by the arrow. The pressure of the process medium is applied to the effective area of the metal bellows (3). The force resulting from the liquid pressure p multiplied by the bellows area A is balanced by the closing force of the springs (4), determining the regulating pressure. This pressure can be adjusted by altering the spring compression by means of the set point adjustment (5). If the liquid pressure exceeds the adjusted pressure, the valve opens until the adjusted pressure is reached again and the seat and plug tightly close. The valve is relieved of pressure by turning the nut (6) against the set point adjustment (5), causing the pipe to vent. Associated Information Sheet

 Open the catalog to page 1
Proportional Safety Valve Type 2302-2

Table 1 • Technical data ■ All ^ pressures in bar (gauge) Typetesting The safety valve has been typetested by the German Technical Inspectorate (TUV) in accordance with the VdTUV Specification Sheet "Safety Valve 100". Type markings available on request. Ordering text Proportional Safety Valve Type 2302 Inlet port: Welding end Outlet port: Welding end, threaded end, soldered end/ flange Set point range ... bar Optionally adjusted/lead-sealed to ... bar Optional special version Installation - The safety valve must be located in the flow pipe of the heating or district heating system (pressure...

 Open the catalog to page 2

All SAMSON catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.