Descriptive Bulletin 1024-30
4Pages

{{requestButtons}}

Catalog excerpts

Descriptive Bulletin 1024-30 - 1

S&C IntelliCap® 2000 Automatic Capacitor Controls

Open the catalog to page 1
Descriptive Bulletin 1024-30 - 2

S&C IntelliCap® 2000 Automatic Capacitor Controls: Intelligent Two-Way Communicating Controls for Smart Grid Applications IntelliCap 2000 Automatic Capacitor Controls are specifically designed to control pole-mounted and pad-mounted switched capacitor banks in electric distribution systems, to regulate reactive power or line voltage. These reliable, easy-to-use, microprocessor-based controls normally operate autonomously, based on the control strategy selected. With a one-way communication device installed, an IntelliCap 2000 Control can also operate in response to switching commands from...

Open the catalog to page 2
Descriptive Bulletin 1024-30 - 3

IntelliCap 2000 Controls accept a single-phase voltage signal from a voltage transformer, which is also used to derive control power. With the optional voltage sensing input feature, sensing and power can be derived from separate sources. Models with VAR and current control strategies additionally accept a single-phase current signal from an S&C CS Line Post Current Sensor or a current transformer. The neutral input sensing feature, when specified, accepts a signal from a voltage transformer, S&C Outdoor Voltage Sensor, Lindsey Voltage Sensor, or current sensor. Communication equipment...

Open the catalog to page 3
Descriptive Bulletin 1024-30 - 4

Specifications Electrical Operating Characteristics • Selectable Nominal Operating Voltage: 110, 115, 120, 127, 220, 230, or 240 Vac, 50 or 60 Hz Electrical Isolation/Protection • Insulation Withstand: 2.5 kV RMS • Surge Withstand: ANSI/IEEE C37.90.1, EN/IEC 61000-4-4 and -4-5 2004, and ANSI C62.41 Section 5.3.1 Categories C1 and C3 • ESD Protection: IEEE C37.90.3-2001 and IEC 61000-4-2:2008 • Radiated Emissions: FCC Part 15B, EN 55022B • Radiated Susceptibility: IEC 61000-4-3:2008 10 V/m and IEEE C37.90.2-2004 35 V/m Fuses • Control and Communication Device Fuse: Time-delayed GMD 2A, 250...

Open the catalog to page 4