Overview: The Armstrong IPC 9511 is a pre-programmed controller designed for automating air-cooled variable primary chiller plants. It sequences chillers and optimizes pump operations to enhance efficiency. The controller is field-configurable via on-board setup screens and integrates with building management systems for reporting and remote control.
Specifications: The IPC 9511 can manage up to five air-cooled chillers and five variable speed primary pumps. It offers three pump control options: parallel sensorless for headered Design Envelope pumps, zone dP sensors, or zone temperature sensors. The power supply ranges from 100V-240V AC at 50-60 Hz.
Features: The controller includes a 10" HMI PLC screen and web-based access, with enclosures rated NEMA 12, 3R, 4, IP54, and IP55. Communication options include Modbus RTU, Bacnet MS/TP, Bacnet IP, Lonworks, and hardwired connections.
Control Options: The IPC 9511 supports variable primary systems with pump speed control, zone dP sensors, sensorless operation, and zone temperature sensors. It also manages bypass valve control for low load conditions and monitors chiller supply/return temperature, flow, and kW.
Interface: The HMI provides a plant overview with a multi-color schematic display, multi-language support, zone setup, pump configuration, alarm history, and event review. It includes Hand-Off-Auto control for zones, pumps, and events.
Additional Options: The controller supports variable secondary systems and offers pony panels like IPS 3000 and IPS 4000, along with parallel sensorless pump control.
See more

Catalog excerpts

IPC 11550-1

File No: 90.401 Date: december 18, 2013 Supersedes: new Date: new ipc controller 9511 air cooled chiller plant controller The Armstrong ipc 9511 is a pre-programmed controller, designed for the automation of an air cooled variable primary chiller plant. The ipc 9511 sequences the chillers and optimizes the pump operation for better efficiency of your chiller plant. The controller is fully field configurable through on-board set up screens. This plant automation solution can also be seamlessly integrated with the reporting and remote read-write capabilities of any building management system. The ipc 9511 is capable of automating a chiller plant with up to five air cooled chillers and five variable speed primary pumps in a number of configurations. The ipc 9511 offers three options for pump control: stand alone (optional with vfd and rack assembly) power supply: 100v-240v ac / 50-60 hz • Parallel sensorless for headered Design Envelope pumps • or Zone dP sensors (up to 5 zones) • or Zone temperature sensors (up to 5 zones) ipc 9511 feature matrix: model 10" hmi plc screen and web-based access screens • Single • DualArm • Twin Communication (standard) • nema 12 • nema 3r • nema 4 Serial interface or hardwired • Serial Modbus with the VFDs Serial communication protocol (optional) Modbus rtu Bacnet ms/tp Bacnet ip Lonworks Hardwired 0-10V Hardwired 4-20 mA Modbus rtu Bacnet ms/tp Bacnet ip Lonworks

 Open the catalog to page 1
IPC 11550-2

control options Or Zone dP sensor with field adjustable set-point reset based on the most open valve position (as per ashrae 90.1). Pump speed control Or Sensorless Or Zone temperature sensor (for systems with 3-way valves) Bypass valve control to continue operation at very low load Supply and return temperature Variable primary system Variable secondary system Pony panel available Plant overview with a multi-color schematic active display of mechanical room hydronic circuit indicating operating status. • Multi-language • Zone set up • Pump configuration • Alarm history and event review • Zones,...