1. Catalogs
  2. Rotork Schischek
  3. ATEX Labelling of Electric Equipment - DIN-A2 Poster

ATEX Labelling of Electric Equipment - DIN-A2 Poster

ATEX Labelling of Electric Equipment - DIN-A2 Poster

Product catalog summary

Overview of Countries and Regions

The document lists numerous countries and regions worldwide, indicating a global scope or market presence relevant to the product or standards discussed.

Explosion Protection Standards and Classifications

The document extensively covers explosion protection classifications according to ATEX and EN standards, focusing on hazardous locations and equipment certification.

Explosion Groups and Temperature Classes

  • Explosion groups are categorized for gases, mists, vapours, and dusts, with examples such as Ammonia, Methane, Propane, Petrol, Diesel, Hydrogen, and Acetylene.
  • Temperature classes (T1 to T6) define the maximum surface temperature of equipment to prevent ignition, ranging from T1 (<450°C) to T6 (<85°C).

Zones and Equipment Protection Levels (EPL)

  • Hazardous locations are classified into zones based on the probability and duration of explosive atmospheres: Zone 0, 1, 2 for gases; Zone 20, 21, 22 for dusts.
  • Equipment is categorized for use in these zones with corresponding EPLs such as Ga, Gb, Gc for gases and Da, Db, Dc for dusts.

Types of Protection and Codes

  • Protection principles include flameproof enclosure (Exd), increased safety (Exe), intrinsic safety (Exi), pressurized apparatus (Exp), encapsulation (Exm), oil immersion (Exo), powder filling (Exq), and protection type “n”.
  • Each protection type is associated with specific EN 60079 series standards (e.g., EN 60079-0, -1, -5, -6, -7, -11, -18, -31, -152).
  • Notified Bodies (NB) issue certification codes (e.g., PTB Germany 0102, EXAM Germany 0158).

Ingress Protection (IP) Ratings

  • Ingress Protection is defined according to EN 60529, detailing protection against solids (dust, objects) and water (sprays, jets, immersion).
  • IP ratings such as IP66 indicate dust-tight and protection against powerful water jets.

Labelling and Marking of Explosion Proof Equipment

Equipment is labelled according to ATEX 2014/34/EU directives, indicating explosion group, temperature class, zone suitability, and protection type to ensure compliance and safe use in hazardous environments.

Product Examples and Specifications

  • ExMax Series: ¼ turn actuators with torque 5–150 Nm, voltage 24–240 VAC/DC, optional spring return.
  • ExMax+LIN: Linear valve units with force 500–3,000 N, stroke 7.5–42 mm, with spring return.
  • ExRun: Valve actuators with force 500–10,000 N, stroke 5–60 mm, without spring return.
  • ExCos: Analog sensors operating from −40 to +125 °C, humidity 0–100% rH, pressure ±100 to ±7,500 Pa.
  • ExReg: Compact controllers for temperature −40 to +125 °C, humidity 0–100% rH, pressure up to 300 Pa (VAV).
  • ExBin: Binary sensors with temperature −40 to +125 °C, humidity 0–100% rH, pressure 0–5,000 Pa, frost protection −10 to +15 °C, and fan belt monitoring up to 10,000 min-1.

Key Recommendations and Best Practices

  • Selection of equipment must consider explosion group, temperature class, and zone classification to ensure safety and compliance.
  • Proper labelling and certification by recognized Notified Bodies are essential for legal and operational safety.
  • Ingress protection ratings must be matched to environmental conditions to prevent dust and water ingress that could compromise explosion protection.
  • Use of appropriate protection principles (e.g., intrinsic safety, flameproof enclosure) depending on the hazardous area classification.

Contact and Manufacturer Information

Rotork GmbH, located in Langenzenn, Germany, is the manufacturer, providing a range of explosion-proof actuators, sensors, and controllers compliant with ATEX and EN standards.

Contact details: phone +49 9101 9081-0, fax +49 9101 9081-77, email [email protected], website www.schischek.com.

See more

Catalog excerpts

ATEX Labelling of Electric Equipment - DIN-A2 Poster-1

Protection of Life. Health. Assets. Labelling of explosion proof equipment Labelling of Explosion Proof Equipment According to ATEX 2014/34/EU Classification and Labelling and labelling ofLocations locations Classification of Hazardous hazardous Flammable medium Explosion Groups & groups & Temperature classes (gases, mists, vapours) Classification Explosion Temperature Classes (Gases, Mists, Vapours) Hazardous locations Classification Product classification of hazardous Probability of a potentially explosive locations Product Product atmosphere occuring group category Continuously, for long periods or frequently Equipment protection level (EPL) Explosion group ExMax-.. ¼ turn actuators • 5…150 Nm • 24…240 VAC/DC • with or w/o spring return Continuously, for long periods or frequently II 2 G Ex db IIC T6 Gb II 2 D Ex tb IIIC T80°C Db flameproof enclosure increased safety intrinsic safety pressurised apparatus Positive pressure device Parts immersed in oil to isolate from explosive atmosphere Prevents transmission of explosion outside powder filling Dust explosion proof Protection principle Schischek Colour Code Sweden United Kingdom Licht. Switz. Belize Guatemala El Salvador Jamaica Honduras Cape Verde Guyana Suriname French Guiana Gambia Guinea-Bissau Trinidad & Tobago Venezuela Colombia Guinea Sierra Leone Liberia Burkina Faso Benin Togo Cote d'Ivoire Bolivia Chile Kuwait Bahrain Qatar U.A.E. Hong Kong For use under special conditions This part is an Ex component and certified as such and is therefore not suitable for use on its own conductive dust Dust classification totally protected against dust dust - limited ingress solids objects > 1 mm solids objects > 2,5 mm solids objects > 12,5 mm solids objects > 50 mm long periods of immersion the effects of temporary immersion strong jets of water low pressure jets from all directions sprays from all directions direct sprays up to 60° from vertical direct sprays up to 15° from vertical vertical falling drops of water IP Protection against solids /dust Protection against water Further information CE conformity is achieved by incorporation into equipment Equipment for safe areas Philippines Vietnam Palau Brunei Malaysia Singapore Solomon Islands East Timor Vanuatu Mauritius Zimbabwe Botswana IIIC non conductive dust flammable fibres Tanzania Angola Swaziland Lesotho Central African Republic Oman Eritrea Gabon Peru Mongolia Kyrgyzstan Ghana Equatorial Guinea Saudi Arabia Mauritania Costa Rica Cyprus Lebanon Israel Georgia Armenia Azerb. Ukraine Mold. Romania Bos. & Serb. Herz. Mont. Albania Mace. Western Sahara Slovenia Croatia United States Protection principle – Type of protection – EN 60079-0 General Requirements Attention: this list is only an extract of possible flammable mediums and does not claim to be complete! complet Carbon disulphide Temperature class emperature Low current /voltage supply ExReg-.. compact controllers • −40…+125 °C • 0…100 %rH • 0…300 Pa (VAV) PTB (Germany) EXAM (Germany) Prevents high temperatures and sparks ExBin-.. binary sensors • −40…+125 °C • 0…100 %rH • 0… 5.000 Pa • −10…+15 °C (frost prot.) • 0…10.000 min-1 (fan belt m.) Ethyl ether Prevents transmission of the explosion outside ExCos-.. analog sensors • −40…+125 °C • 0…100 %rH • ±100… ±7.500 Pa Ethyl glycol Carbon hydrogen Product use depending on temperature class (T1 - T6). The temperature class indicates the max. temperature of the exposed surface of the product. For dust explosion proof, the max. surface temperature is directly shown (e.g. T80°C). ExRun-.. valve actuators • 500…10.000 N • 5…60 mm stroke • w/o spring return Ethylene Ethylene oxide City gas Acrylic nitrile Notified bodies Code number 2D Infrequently and for short periods only Petrol Diesel fuel Fuel oil n-Hexane Ethanol Cyclohexene n-Butane Likely to occur Infrequently and for short periods only ExMax-..+LIN linear valve unit • 500…3.000 N • 7,5…42 mm stroke • with spring return Ammonia Methane Ethane Propane Gases, mists, vapours Examples depending on - explosion group - temperature class Somoa Fiji Tonga Gases, Mists, Vapours, Dust South Africa Rotork GmbH – Langenzenn / Germany Rotork - Schischek Sales Rotork GmbH • Mühlsteig 45 • 90579 Langenzenn, Germany

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.