Fans with IEC standard motor

Product catalog summary
Safety
The document stresses the importance of following safety symbols and guidelines to prevent hazards such as electric shock, crushing, and falling loads. Although Rosenberg fans are manufactured to high standards, improper use can be dangerous.
Scope
This manual covers various types of radial and roof fans, including those with standard motors and different impeller designs.
Description
Rosenberg radial fans are designed for modern ventilation systems, featuring standard motors and the ability to rotate in 90° increments. They are balanced both statically and dynamically.
Condition of Use
Fans should be used within specified performance limits and are suitable for clean or slightly contaminated air, slightly aggressive gases, and mediums with specific temperature and humidity ranges. Compliance with DIN EN ISO standards is required.
Operation According to ErP-Directive
Fans must operate at least in a "3-Stage + OFF" mode as per EU regulations. Different motor types offer various control options, and the operator is responsible for compliant operation.
Maximum Speed
The maximum speed of fans is determined by motor specifications, and care must be taken not to exceed these limits to avoid overloading.
Accessories
Only authorized accessories should be used, and they must be maintained according to fan cleaning guidelines.
Storage and Transport
Fans should be stored in dry, weather-protected environments and transported using appropriate equipment to avoid damage.
Installation and Mounting
Installation should be performed by trained personnel, ensuring sufficient space for maintenance. Electrical work must comply with relevant regulations.
Specifications and Safety Measures
1. Ensure protection against foreign objects entering the fan using guards certified to DIN EN ISO 13857.
2. Check the fan for transport damages before installation; do not install damaged fans.
3. In hazardous areas, connect all conductive parts to a voltage equalizing system.
4. Radial fans should not be distorted; ensure no warping or shifting that could cause knocking or grinding of moving parts.
5. Handle the fan only by its base frame or designated lifting points.
6. Roof fans require airtight sealing on mounting surfaces to prevent deformation and ensure free rotation of the impeller.
7. Fans are designed for horizontal installation or up to a 5° incline; use a special inclined roof socket for greater inclines.
Installation and Connection Guidelines
1. Radial fans should operate with horizontal shafts; non-horizontal positions may reduce bearing life.
2. Use non-loosening screw connections for installation.
3. Electrical connections must comply with technical and local regulations.
4. Ensure proper grounding and equipotential bonding.
5. For roof fans, ensure the mains supply line is sealed properly and connected to the appropriate terminal box.
Operational Procedures
1. Remove foreign objects from the fan before checking the direction of rotation.
2. Install protection guards and check the impeller for smooth rotation.
3. Verify the direction of rotation using the direction arrow on the casing.
4. Adjust motor phases to change rotation direction if necessary.
Electrical Specifications
1. The DVNF fan operates via a frequency converter; observe special connection conditions.
2. Ground wire connections must match the power supply cross-section.
3. Fans must operate in neutral point earthed networks with permissible asymmetry less than 2%.
4. Total Harmonic Distortion (THD) must be less than 10%.
5. Follow EN 60204-1 for low-voltage system connections.
6. Use specified fuses for cable protection, not device protection.
Protection and Safety Devices
1. Motor protection switches are not allowed in the DVNF fan's mains supply circuit.
2. Earth leakage circuit breakers must handle leakage currents and be suitable for pulsating and smooth DC fault currents.
3. Ensure proper earth protection to avoid dangerous voltages on the unit's surface.
4. If leakage current exceeds 3.5 mA, connect a second earth protection cable.
Control Signal and Testing
1. Maintain a distance of more than 10 cm between main supply and control cables.
2. Control cable length should not exceed 30m; use shielded cables for lengths over 20m.
3. Insulation tests are only permitted for mains connections, not control terminals.
Specifications and Procedures
1. Insulation Test: Conducted using EN 60204-1 standards with a DC voltage of 500VDC. Ensure all connection cables are disconnected at the Controller to avoid high voltages.
2. Pin Connection: The motor PTC must be connected to contacts 11 and 12 for operation. Incorrect connections can damage electronics.
3. Power Supply: For 3-phase devices, mains terminals must be bridged. The power supply should be disconnected for at least two minutes before working on motor wiring.
Installation and Commissioning
1. Connection Terminals: Use core sleeves for multi-core cables. Terminals are spring-loaded for easy wire insertion. Stripped wire ends should be 8-15 mm long.
2. Junction Box Overview: Includes motor connection terminals, optional module connectors, and power terminals.
3. Initial Checks: Ensure installation is complete, safety devices are fitted, and no foreign particles are present. Verify connection data with the motor type plate.
4. Operation: Initiate by qualified personnel only. Check for correct rotation and operation.
Protective Features
1. Monitoring Functions: Includes under/over voltage, locked rotor, over temperature, current protection, and phase fault detection.
Troubleshooting
1. Common Issues: Includes missing power supply, poor electrical connections, and missing control signals. Ensure compliance with safety regulations during maintenance.
Alarm Relay and LED Indications
1. Alarm Relay: Switches from COM-NC to COM-NO if no fault is detected. Note relay status during startup.
2. LED Indications: Green light indicates no alarm, flashing green indicates active communication, flashing red indicates non-critical alarms, and constant red indicates critical alarms.
Specifications and Procedures
1. 0-10V Control Signal: Ensure the potentiometer's 0-10V control signal is correctly connected with a minimum internal resistance of 4 kΩ. Verify the alarm relay function.
2. Motor Protection: If the motor is stopped due to overload or alarm, reset by disconnecting the controller for 60 seconds. Check for blocked impeller and foreign objects.
3. Controller and Motor Issues: Replace defective controllers or motors. Ensure correct phase connections between controller and motor to avoid wrong rotation direction.
Standards and Recommendations
1. IEC Standard Motors: As per regulation 640/2009/EC, motors from 2015 must be IE3 or IE2 with a VSD for motors >=7.5kW, and from 2017 for motors >=0.75kW.
2. Maintenance: Conducted by qualified personnel. Fans are largely maintenance-free under normal conditions. Bearings designed for 20,000h lifespan, but should be replaced every 5 years due to grease aging.
Air Volume Measuring Device
1. Components: Consists of a circular lead with pressure measuring devices in the inlet cone.
2. Function: Measures air volume based on pressure difference between static pressures at the inlet cone and inlet area.
3. Calibration: Calibration factor k10 determined with at least 10% accuracy.
Disposal and Environmental Considerations
1. Disposal: Follow local regulations for disposal. Environmentally friendly design and safety considered in fan development.
2. Dismantling: Conducted by trained personnel. Prepare by contacting waste management, disconnecting power, and removing liquids.
General Maintenance Tips
1. Safety: Ensure fan impeller is stopped and electrical circuit is disconnected before maintenance.
2. Cleaning: Regular cleaning prevents distortions. Do not use high-pressure cleaners.
3. Inspection: Check for unusual noises, bearing clearance, and surface protection.
Safety Precautions
Ensure that machine parts are secured against falling before dismantling to prevent serious injury and property damage.
Component Disposal
The machine is primarily composed of metallic materials, which are fully recyclable. Components should be separated into categories such as steel and iron, aluminum, non-ferrous metals, insulating materials, cables and wires, electrical scrap, and plastics. Materials and chemicals should be disposed of according to local regulations, including fats and paint residues. Packaging materials like wood, foam, and cartons should be managed according to regional requirements, with contaminated materials directed to thermal utilization.
Customer Service and Manufacturer Information
Rosenberg products undergo continuous quality control and comply with current regulations. For inquiries, contact the air handling unit constructor, a Rosenberg branch, or directly at Rosenberg Ventilatoren GmbH.
CE Marking and Declarations
Rosenberg declares that its products meet applicable EC/EU directives. The declaration of conformity is available on the Rosenberg website and is valid for independently operated fans with sinusoidal current supply. The ErP directive compliance is valid only with ErP-related data on the product information and nameplate. The declaration of incorporation applies to products mentioned in the manual and serves as an assembly instruction under the machinery directive Annex XI.
See more

Catalog excerpts

Fans with IEC standard motor-1

Betriebsanleitung Operating instruction Radialventilatoren mit Normmotor direktgetrieben / Direct-driven radial fans with IEC motor Rosenberg Ventilatoren GmbH · Maybachstraße 1 · 74653 Künzelsau-Gaisbach Tel.: +49(0)7940/142-0 · Fax.: +49(0)7940/142-125 · Email: [email protected] · www.rosenberg-gmbh

 Open the catalog to page 1
Fans with IEC standard motor-2

4.1 Betrieb gemaB ErP-Richtlinie 6 4.4 Hinweis zum Betrieb mit einem Controller (Frequenzumrichter) 7 6.2.3 Schutz durch FI-Schutzschalter 12

 Open the catalog to page 2
Fans with IEC standard motor-3

4.1 Operation according to ErP-Directive 6 4.3 Accessories / attachment parts 7 4.4 Note on operation with a controller frequency converter 7 6.1 Main supply DVNF 10 6.2.1 Mains fuse protection 11 6.2.2 Using motor protection switches 12 6.4 High potential test 13 6.7 Characteristics of the alarm relay 19 9.1 Air volume measuring device 24 12 Service, Address of producer 29

 Open the catalog to page 3
Fans with IEC standard motor-4

1 Sicherheit Safety Folgende Symbole weisen Sie auf bestimmte Gefährdungen hin oder geben Ihnen Hinweise zum sicheren Betrieb. The following symbols refer to particular dangers or give advice for save operation. Achtung! Gefahrenstelle! Sicherheitshinweis! Gefahr durch elektrischen Strom oder hohe Spannung! Danger from electric current or high voltage! Crush danger! Lebensgefahr! Nicht unter schwebende Last treten! Danger! Do not step under hanging load! Wichtige Hinweise, Informationen Important information Rosenberg-Ventilatoren sind nach dem Stand der Technik zum Zeitpunkt der Auslieferung...

 Open the catalog to page 4
Fans with IEC standard motor-5

3 Beschreibung Description Rosenberg Radialventilatoren wurden speziell für den Einsatz in modernen Lüftungs- und Klimaanlagen entwickelt. Zum Antrieb werden Normmotoren (Schutzart IP 54 / Isolierstoffklasse B) in Flanschausführung oder Fußausführung eingesetzt. Die Gehäuse-Ventilatoren (ERND / EHND) sind rechts- sowie linksdrehend lieferbar und die Gehäuse können in 90° -Schritten verdreht werden. Alle Ventilatoren werden in Werk statisch und dynamisch ausgewuchtet. Rosenberg radial fans are especially developed and manufactured for the use in modern ventilation systems and air handling units....

 Open the catalog to page 5
Fans with IEC standard motor-6

4.1 Betrieb gemaft ErP-Richtlinie Operation according to ErP-Directive_ According to the regulation 1253/2014/EU the fans in the scope of application must be operated at least „3-Stage + OFF“. Depending on the motor 3 variants are possible for the Rosenberg Fans - Fans with AC External rotor-motor: optional control unit - Fans with EC-External rotor motor: speed control integrated, no additional device necessary - Fan with IEC Standard motor: optional (Controller) frequency inverter Responsible for the compliant, multi-stage operation is the operator. Appropriate switching device are available...

 Open the catalog to page 6
Fans with IEC standard motor-7

Radial-Ventilatoren Typ EHND radial fans type EHND 4.3 Zubehor / Anbauteile Accessories / attachment parts_ Verwenden Sie nur von Rosenberg Ventilato-ren GmbH freigegebene Zubehor- oder Ersatzteile. Use only accessories or spare parts authorized by Rosenberg Ventilatoren GmbH. Zubehorteile sind entsprechend den Reini-gungshinweisen des Ventilators sauber zu halten. Verwendung elektrischer Zubehorteile, wie z. B. Klemmkasten, GS-Schalter, Motor-schutzschaltgerate und Controller unter Be-achtung der zutreffenden Vorschriften! Accessories should be also cleaned regularly same as the fan. Usage of...

 Open the catalog to page 7
Fans with IEC standard motor-8

5 Lagerung, Transport Storage, Transport - Lagern Sie den Ventilator in seiner Originalverpackung trocken und wettergeschützt. Decken Sie offene Paletten mit Planen ab und schützen Sie die Ventilatoren vor Schmutzeinwirkung (z.B. Späne, Steine, Draht usw.). Store the fan on a dry place and weather protected in its original packing. Cover open palettes with a tarpaulin and protect the fans against influence of dirt (i.e. stones, splinters, wires, etc.). Storage temperatures between - 20 °C and + 40 °C. With storage times of more than 1 year please check the bearings on soft running before mounting...

 Open the catalog to page 8
Fans with IEC standard motor-9

Keine Gewalt (hebeln, biegen) anwenden. Der ausgepackte Ventilator ist nur am Grundrahmen, den Trageösen oder sonstigen dafür vorgesehenen Aufnahemepunkten anzuheben. Ausreichende Standsicherheit des Ventilators durch Montage an den Winkelrahmen oder den dafür vorgesehenen Fußwinkeln. ⇒ Ventilatoren nicht verspannen! Bei dem Aufsetzen des Dachventilators auf dem Dachsockel oder dem Sockelschalldämpfer ist die Auflagefläche mit Moosgummi oder einem dauerelastischen Schaumstoffband luftdicht zur Ventilatorgrundplatte abzudichten. Bei bauseitig erstellten Sockeln ist unbedingt darauf zu achten,...

 Open the catalog to page 9
Fans with IEC standard motor-10

gaben des Motorherstellers ordnungsgemäß anschließen ! ating instruction of the manufacturer of the motor ! Please notice when mounting a roof fan: Die Netzzuleitung kann außen, über oder unter dem Dach verlegt oder durch den Luftkanal geführt werden. Im letzteren Fall ist sie mittels Kabelverschraubung durch die in der Grundplatte vorhandene Bohrung zu führen. ⇒ Die Kabeldurchführung muss immer gründlich abgedichtet werden! ⇒ Cable lead-in always has to be sealed properly! - Die Zuleitung ist an den unter der Regenschutzhaube angebrachten Anschlusskasten oder, wenn vorhanden, an den außen angebrachten...

 Open the catalog to page 10
Fans with IEC standard motor-11

Cable definition: Fittings M20 Cable diameter 6 -12 mm Wire diameter 1,5 mm2 - 4 mm2 The ground wire connection must be absolutely connected at ground potential. The ground wire connection must have at least the same cross section as the power supply! Der Schutzleiteranschluss muss zwingend angeschlossen und auf Erdpotential gefuhrt werden. Der Schutzleiteranschluss muss min-destens den gleichen Querschnitt als die Netz-zuleitung aufweisen! Die Ventilatoren durfen nur in symmetri-schen (zulassige Asymmetrie kleiner 2%) und im Sternpunkt geerdeten Netzen betrie-ben werden. z.B. TN-S, TN-C, TN-C-S,...

 Open the catalog to page 11
Fans with IEC standard motor-12

6.2.2 Verwendung von Motorschutzschaltern Using motor protection switches_ The use of motor protection switches in the mains supply circuit of the DVNF fan is not permitted. To ensure the mains line protection, see section 6.1.1 for the use of the right fuses. Die Verwendung von Motorschutzschaltern im Netzspannungsstromkreis des DVNF, ist nicht zulassig. Zur Gewahrleistung des Leitungs-schutzes sind die im Abschnitt 6.2.1 angegebe-nen Sicherungen zu Verwenden. 6.2.3 Schutz durch Fl-Schutzschalter Additional protection_ Sollte, bedingt durch Netzform oder Forderung des EVU, die SchutzmaBnahme...

 Open the catalog to page 12