Catalog excerpts
The sprinklers spray pendent (SSP) and spray upright (SSU) have a parabolic water distribution directed towards the ground on a specific area. A spray sprinkler discharges from 80 to 100 % of the total water flow in a downward direction. Conventional sprinklers have a spherical water distribution directed towards the ground and the ceiling over a specific area. It discharges from 40 to 60 % of the total water flow in the downward direction. The deflector’s shape allows either an upright or pendent installation with the same water distribution. Technical specifications Maximum operating pressure: 12 bars Maximum factory pressure test: 35 bars (made on each sprinkler) Packing: Polystyrene box of 20 units, Dim. 0.25x0.205x0.08 m., Weight = 1.6 kg Accessory: Sprinkler Neptune spanner Conventional Cu/p brass Chrome White** Brass Chrome White** Brass Chrome White** Brass Chrome White** Brass Chrome White** Brass Chrome White** Finish Approval * BSP as standard, NPT on request ** White only CE-APSAD; other colour, advise RAL for pricing. Bulb colour Temperature (°C-°F) Action Standard—> S Quick response —> F Open—> O finish Brass—>L Chrome —> C White—>B Painted—> R* Type SSU—> U SSP—> P Cu/p —> C ROLLAND SPRINKLERS 235 route de la Biolle—ZA Le sauvage—73410 Mognard—FRANCE Tel. 33.(0)4.79.54.72.50 / Fax. 33.(0)4.79.54.72.48 — info@rolland-sprinklers.com
Open the catalog to page 1All ROLLAND catalogs and technical brochures
-
KOFULSO ® /Easyflex ®
6 Pages
-
K115 sprinklers SSP - SSU FM