RixenRingbalances RW65_EX_II indicator + transmitter for ex zone Measuring ranges from 0-40 Pa to 0-1.8 kPa (0.15"W.C. to 7"W.C.) For over 60 years, Rixen has manufactured low-range measuring instruments for draft, pressure and differential pressure of gaseous mediums. From the very beginning we made use of the Ringbalance measuring principle with its special advantages, and meanwhile we are the only manufacturer of Ringbalances, worldwide. Rixen Messtechnik GmbH & Co KG Kornweg 1 44805 Bochum GERMANY Phone: +49 (0)234 86790 Fax: +49 (0)234 850130 eMail: rixen@online.de

Open the catalog to page 1
Product catalog - 2

Measuring Principle A hollow ring, free to rotate on bearings and half filled with fluid,is divided by partition wall "A" into two chambers. Positive, and negative or differential pressure are applied to the ringbody chambers via flexible tubes "S". The pressure differential across the dividing wall "A" causes the ringbody to rotate until an equilibrium is reached with the counterweight "G". Excellent Long-Term-Accuracy The calibration of a Ringbalance is entirely determined by the mass of the counterweight "G". A weight cannot "age" or become "overloaded". The Filling Fluid Since the...

Open the catalog to page 2
Product catalog - 3

MU Digit al Ringbalance Differential Pressure Transmitter converts draft, pressure and differential pressure into standard signals of 0-20mA, 4-20mA and 0-10V Measuring System Ringbalance principle Measuring Pickup Magnetic "Hall" sensor Measuring Ranges from 0...40 Pa (+/-20 Pa) to 0...1.8 kPa - see page 8 Units Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C. Ambient Temp. for wall mounting IP42; Polycarbonate lightgrey; - see page 9 - Process Connect. 2 fittings for flexible tubes, 8mm outside diameter Electr. Connections screw terminals in the terminal box 2 cable fittings PG9/M16 with strain...

Open the catalog to page 3
Product catalog - 4

MU-Analog-65 Ringbalance Differential Pressure Transmitter converts draft, pressure and differential pressure into standard output signals of 0-20mA, 4-20mA and 0-10V MU-Analog-65-2L Ringbalance Differential Pressure Transmitter "Loop-Powered" (2-wire) version large analogous display, 150x150mm (6"x6") Measuring Pickup Magnetic field sensor, non-contact, and with infinite resolution Measuring Ranges from 0...40 Pa (+/-20 Pa) to 0...1.8 kPa - see page 8 Scale Units Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C. Ambient Temp. wall mounting, IP65 (see page 9) Electrical Outputs 2-wire version: 4-20...

Open the catalog to page 4
Product catalog - 5

RW-65-Ex -II Ring balance with integrated, intrinsically safe twin-wire loop current transmitter (4 - 20 mA) for be mounted in Ex zones ( 0,1, 2, 20, 21, 22 ) • dimensions (HxWxD): 235x195x165mm • large dial, 150Êx 150mm • free selection of scaling (Pa, mbar, daPa, mmWs, etc.) • ambient temperature: -20...+50°ÊC • free selection of measuring range (MIN: 0...40Pa (+/-20Pa) – MAX: 0...1.8ÊkPa) and any values in between • max. error of measurement +/-1% of the final value • function as limit sensor (min / max) • transmitter output designed as intrinsically safe current output of 4-20mA...

Open the catalog to page 5
Product catalog - 6

RingbalanceRW65 measuring draft, pressure, differential pressure, and flow optional with contacts Setpoint adjustment (contacts) Measuring Ranges from 0...40 Pa (+/-20 Pa) to 0...1.8 kPa - see page 8 Scale Units Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C. Ambient temp. wall mounting IP65 (see page 9) RW65 with 2 Inductive Contacts Option: Inductive Contacts Inductive sensors according to NAMUR / ATEX [EEx ia IIC T6], 1xMin 1xMax 2xMin 1xMin / 1xMax Type Type Type Type Switching Amplifier vane dips into slot at decreasing pressure vane dips into slot at increasing pressure Isolation Switch...

Open the catalog to page 6
Product catalog - 7

RIXOTACT_4 Ringbalance measuring draft, pressure and differential pressure + integrated Threepoint-Step-Controller + integrated Transmitter Measuring System Actual Value "X" Measuring Ranges from 0...40 Pa (+/-20 Pa) to 0...1.8 kPa - see page 8 Units Pa, kPa, daPa, mbar, mmWS, mmCE, in.W.C. Ambient temper. wall mounting IP65 - see page 9 - Control Mode Measuring Pickup "Hall"- sensor Control Output potential-free contacts, rated at 250V/2A X > W = terminals 7-5 switched X < W = terminals 7-6 switched two setpoints (W1/W2), adjustable from 20% to 80% of full scale reading; switched-over by...

Open the catalog to page 7
Product catalog - 8

Measuring Ranges, Filling Fluids, Overload Protection Device Conversions Pa Measuring Range Filling Fluid Further scale units: mbar / mmWS / mmW.C. / in.W.C. / . . . . Note: All Ringbalances are factory-filled. The type of oil need not be mentioned in the order. Filling Fluids Overload Protection DZ1 Bypass "Oil" Mineral oil, density 0.8 kg/l; for ranges from 0-40 Pa (0.15" W.C.) to 0-700 Pa (3"W.C.) Overflow point at +/-900 Pa (3.5"W.C.) "Galden" Synthetic oil, density 1.9 kg/l; for measuring ranges over +/-700 Pa Overflow point at +/-2.1 kPa (8.5"W.C.) Overload Protection Every...

Open the catalog to page 8
Product catalog - 9

Housing for wall mount - mounting either through inner "screw channels", or with the aid of the attached mounting frame. Glass reinforced polycarbonate, light grey. Hardened front glass pane. Process connections p+ / p-: Fittings for flexible tubes, 8mm outer diameter 8 M16/PG9 with strain relief IP42 Special version designed for the Ringbalance type MU Digital. Polycarbonate, light grey. Protective Case "M" All types of Ringbalances can be delivered in the rugged design housing "M" at additional price. PG9 with strain relief transparent cover swivelling holder