Multi Power 15-294 kVA

Multi Power 15-294 kVA

Multi Power 15-294 kVA

Product catalog summary
Overview: The Riello UPS Multi Power (MPW and MPX) is a modular UPS system designed for data centers and critical IT environments. It offers high availability, scalability, and efficiency, with a power density that supports growing business demands without oversizing.
Specifications: The system supports power capacities from 15 kW to 1176 kW with redundancy. It features a three-level Neutral Point Clamped (NPC) inverter and Power Factor Corrected (PFC) input control, ensuring high efficiency (>96.6%) and low harmonic impact.
Advanced Technology: The Multi Power uses cutting-edge components and control technologies, including custom-designed IGBT modules, to ensure reliability and performance. The wireless power principle minimizes connection issues and power losses.
Scalability: The system is highly scalable, allowing for vertical and horizontal expansion. Power Cabinets can accommodate various power modules, and up to four cabinets can be connected in parallel. Battery Cabinets support multiple configurations for increased autonomy.
Performance: The Multi Power maintains full rated power with unity power factor loads and operates efficiently even at low loads. It has a wide input voltage range and low input harmonic pollution, reducing upstream power source requirements.
Control and Monitoring: The system features multiple microprocessors for operational reliability and advanced communication options, including a 7” LCD touch screen and compatibility with various protocols (UDP, HTTP, SMTP, SNMP, Modbus/TCP).
Flexibility and Modularity: The modular design allows for easy expansion and maintenance, with hot-swappable components and accessible front panels. The system supports both centralized and distributed battery configurations.
Turnkey Solutions: Riello UPS offers turnkey solutions with integrated power and switching cabinets, simplifying installation and reducing total cost of ownership (TCO).
Advanced Communications: The system supports integration with building management systems and data center infrastructure management (DCIM) systems, ensuring seamless operation and monitoring.
Technical Specifications: The Multi Power UPS system ranges from 15 to 294 kW, with input, bypass, battery, and output specifications detailed. Input voltage is 380/400/415 V three-phase + neutral, with a frequency of 50/60 Hz. Bypass nominal power is 252/126 kW, with overload capacity of 125% for 10 minutes and 150% for 1 minute. Battery options include modular and conventional types, with VRLA batteries and monitoring via LCD display. Output voltage is 380/400/415 V three-phase + neutral, with voltage stability of ±1%.
Overall System Features: Cabinet types include MPX 130 PWC, MPW 300 PWC, and various combo cabinets, with nominal power ranging from 45 to 294 kW. Systems are parallelable up to 4 units, with ECO mode efficiency up to 99% and an IP20 rating for cabinet protection. Operating temperature ranges from 0°C to +40°C, with compliance to European directives and standards.
Communication Protocols: Embedded protocols include MPW/MPX, Web Browser, PowerShield3, Mail Server, and Ethernet Switch. Additional protocols with NetMan 208 card include Modbus/TCP and SNMP.
Manufacturer Information: RPS SpA - Riello Power Solutions, part of the Riello Elettronica Group, based in Legnago, Italy.
See more

Catalog excerpts

Multi Power 15-294 kVA-1

Multi Power Lithium compatible SmartGrid ready HIGHLIGHTS • Utmost availability • Ultimate scalability • Unmatched power density • Efficiency >96.6% • Multiple controls • Highly flexible • Advanced comms The Riello UPS Multi Power (MPW and MPX) is the ultimate modular UPS for Data Centers and other CRITICAL LOADs. The Multi Power is designed to protect any critical high-density computer and IT environment, whilst achieving maximum availability. The Multi Power grows along with the demands of the business without over-sizing the UPS - optimizing both the initial investment and the Total Cost of Ownership. As soon as demand increases, the Riello UPS Multi Power modular solution can expand its power capability, maintaining the highest levels of power protection, availability, redundancy and investment savings. Digital technology has an increasingly strong influence on day-to-day activities in almost all sectors and applications such as healthcare, power generation, social networking, telecommunications, commerce and education. Subsequently, any activities and equipment related to data storage, processing and transfer should be supplied from the most reliable power source. Multi Power ensures that a scalable, secure, high quality power supply is available for a variety of critical load applications. The new MPW and MPX Power Modules feature the very latest in UPS technology. With its three-level Neutral Point Clamped (NPC) inverter and Power Factor Corrected (PFC) input control, the Multi Power ensures the highest level of performance in terms of overall efficiency, input power factor and harmonic impact on the sup

 Open the catalog to page 1
Multi Power 15-294 kVA-2

ADVANCED TECHNOLOGY To ensure the highest levels of power availability, only the most reliable, cutting edge power components and innovative control technologies have been used in the development of the MPW and MPX power modules and other major aspects of the system. The major power components and assemblies within the Multi Power have been specifically designed and tailor made in conjunction with the respective component manufacturers. This design work ensures that the Multi Power achieves the highest levels of power and performance. In order to optimise the overall performance of the finished...

 Open the catalog to page 2
Multi Power 15-294 kVA-3

• High system efficiency whilst operating in ON LINE double conversion mode greater than 96.5%. Even when loaded at only 20%, the Multi Power still achieves an outstanding performance greater than 95%. This superior performance ensures extremely low losses at any load level whilst maintaining a true modular solution for any changing UPS environment in terms of power demands. • Low input harmonic pollution, with near unity input power factor and an extremely wide input voltage operating range (+20/-40%), requiring only a minimum upstream power source rating and subsequent reduced investment costs....

 Open the catalog to page 3
Multi Power 15-294 kVA-4

Battery Cabinet (MPW 170 BTC) with open and closed door. Combo Cabinet MPX 75 CBC (1-3 MPX 15 PM or MPX 25 PM) + 1-3 Battery shelves. unit as standard. The system is equipped with a Manual Bypass change over switch and Backfeed control with a mechanical interlock contactor inbuilt, eliminating any maintenance-related downtime (inbuilt contactor is optional for MPX 130 PWC, MPX 75 CBC and MPX 100 CBC). Combination systems (Combo Cabinet) and Battery Cabinet are supplied with a battery switch and shunt trip to enable remote battery switch operation (battery switch not available for MPX 75 CBC)....

 Open the catalog to page 4
Multi Power 15-294 kVA-5

MPX Power Cabinet 15-75 kW or 25-125 kW (front) MPX Power Cabinet 15-75 kW or 25-125 kW (rear) MPW Battery Cabinet (front) MONITORING UNIT (MU) POWER SUPPLY UNIT (PSU) BATTERY UNIT (BU) RELAY SLOT CONNECTIVITY PANEL (CP) AUXILIARY SIGNAL BOARD (ASB) MANUAL BYPASS SWITCH (SWMB) BATTERY SWITCH (SWBATT) MPW Power Cabinet 42-294 kW (front) MPW Power Cabinet 42-294 kW (rear) MPW Battery Cabinet (front) MONITORING UNIT (MU) CONNECTIVITY PANEL (CP) AUXILIARY SIGNAL BOARD (ASB) MANUAL BYPASS SWITCH (SWMB) POWER SUPPLY UNIT (PSU) RELAY SLOT BATTERY SWITCH (SWBATT)

 Open the catalog to page 5
Multi Power 15-294 kVA-6

MPW Combo Cabinet 42-126 kW (front) MPW Combo Cabinet 42-126 kW (rear) MPW Battery Cabinet (front) POWER SUPPLY UNIT (PSU) AUXILIARY SIGNAL BOARD (ASB) MANUAL BYPASS SWITCH (SWMB) BYPASS MODULE (BM) RELAY SLOT BATTERY SWITCH (SWBATT) BATTERY SWITCH (SWBATT) MPW Switching Cabinet 500 + 2x MPW 300 PWC (front without doors) MPW Switching Cabinet 500 + 2x MPW 300 PWC (rear without panels)

 Open the catalog to page 6
Multi Power 15-294 kVA-7

Auxiliary Signal Board (ASB) Connectivity Panel (CP) 10/100 NETWORK POWER SUPPLY UNIT (PSU) SWIN SWMB SWBYP SWBATT SWOUT TEMP OPENING RELEASE SWBATT MAIN COMMUNICATION UNIT (MCU) COMMUNICATION SLOTS Note: 1) On MPX 130 PWC connectivity panel layout is different. 2) Second PSU on MPX 130 PWC is optional. MPW BATTERY CABINET / MPW 170 BTC (MODULAR BATTERY CABINET) Select the Battery configuration according Multi Power range OPTIONS SOFTWARE PowerShield3 PowerNetGuard ACCESSORIES NETMAN 208 MULTICOM 302 MULTICOM 352 MULTICOM 372 MULTICOM 384 MULTICOM 411 MULTICOM 421 MULTI I/O MULTIPANEL PRODUCT...

 Open the catalog to page 7
Multi Power 15-294 kVA-8

Multi Power - from 15 to 294 kW1 INPUT Rated voltage [V] Power factor BYPASS Nominal power [kW] 252 / 126 (According to system power configuration) from 180 (adjustable 180-200) to 264 (adjustable 250-264) referring to Neutral Frequency tolerance Battery arrangement (parallel systems) Conventional Type Separate/common Modular type made up by Battery Unit (named BU) Free Standing Battery cabinet / Shelf Battery features VRLA batteries lined up inside BU; Constant voltage and current measuring at BU level; Battery status monitoring via Multi Power LCD display Conventional battery Blocks VRLA Type...

 Open the catalog to page 8
Multi Power 15-294 kVA-9

MULTI POWER EMBEDDED PROTOCOLS 1 MPW / MPX Web Browser PowerShield3 Mail Server Ethernet Switch MULTI POWER PROTOCOLS ADDING NETMAN 208 CARD 1 2 3 4 5 MPW / MPX NetMan 208 board Modbus/TCP Manager SNMP Manager Ethernet Switch Ethernet The information in this document is subject to change without notice. Riello UPS assumes no responsibility for any errors that may appear in this document. Modbus/TCP Protocol RPS SpA - Riello Power Solutions - Member of the Riello Elettronica Group Viale Europa, 7 - 37045 Legnago (Verona) - ITALY - Tel: +39 0442 635811 www.riello-ups.com

 Open the catalog to page 9