VU120 - 1

Rectangular smoke control damper. Rf-Technologies nv  Lange Ambachtstraat 40  9860 Oosterzele  Belgium  Tel +32 9 362 31 71  Fax +32 9 362 33 07  info@rft.be

Open the catalog to page 1
VU120 - 2

Flange types - at the time of order 7 Installation in shaft - cross section view 9 Installation into horizontal or vertical shaft PROMATECT L500 10 Installation into horizontal or vertical shaft GEOFLAM (LIGHT) 11 Installation into horizontal or vertical shaft GEOTEC 12 Installation into horizontal or vertical shaft TECNIVER 13 Installation into horizontal or vertical shaft GLASROC F V500 14 Installation into horizontal or vertical shaft EXTHAMAT 15 Installation into horizontal or vertical shaft DESENFIRE (HD/THD/STR) 16 Installation into vertical concrete shaft 17 Installation at minimal...

Open the catalog to page 2
VU120 - 3

6. Declared performance according to EN 12101-8:2011 Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) Gap between duct and damper (≤ 6 mm) sealed with refractory kit (on a depth ≥ 105 mm) Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) Gap between duct and damper (≤ 80 mm) sealed with refractory kit (on a depth ≥ 105 mm) Type of installation: shaft-mounted 0/90°/180°/270°. Minimal distances authorised. Gap between duct and damper...

Open the catalog to page 3
VU120 - 4

Product presentation VU120 The rectangular VU120 smoke evacuation damper is noted for its superior airtight properties. It was developed in accordance with the European product standard EN 12101-8 and tested according to the EN 1366-10 standard. The VU120 offers a fire resistance up to 120 minutes, and ensures minimum pressure loss. Smoke evacuation shutters and dampers are suitable for use in ventilating protected lobbies, venting to shafts either naturally or mechanically. They open to evacuate smoke in emergency situations whilst maintaining fire resistant integrity in standby position....

Open the catalog to page 4
VU120 - 5

Evolution - kits BLE 24V actuator for smoke control dampers BLE 24V actuator for smoke control dampers with plug (ST) BLE 230V actuator for smoke control dampers

Open the catalog to page 5
VU120 - 6

Evolution - kits KITS NF/SF-VD NF/SF-VD module (NF24/SF24: 24-48 V DC). Only for France. KITS MANF EVO VD24 FDCU Upgradeable remote controlled unlocking mechanism with natural magnet 24 V DC + FDCU KITS MANF EVO VD48 FDCU Upgradeable remote controlled unlocking mechanism with natural magnet 48 V DC + FDCU KITS MANF EVO VM24 FDCU Upgradeable remote controlled unlocking mechanism with electromagnet 24 V DC + FDCU KITS MANF EVO VM48 FDCU Upgradeable remote controlled unlocking mechanism with electromagnet 48 V DC + FDCU Natural magnet 24 V DC + FDCU Natural magnet 48 V DC + FDCU Limit switch...

Open the catalog to page 6
VU120 - 7

Flange types - at the time of order Testbox for mechanisms 24/48 V (magnet, motor, beginning and end of range switches) Alternative connection to standard PS at the shaft side: PG30 connection to ducts with 30 mm flanges, with elliptical holes Ø 8,5 x 16 mm. No connection (standard connection shaft side). Also possible on shaft side: PG30, PG20, PG40, PM. Connection to ducts with 30 mm flanges (either by sliding profile or with bolts). Also possible on shaft side instead of PS connection (at order time). Elliptical holes Ø 8,5 x 16 mm. Alternative connection to standard PS at the shaft...

Open the catalog to page 7
VU120 - 8

Flange types - at the time of order Connection to ducts with 40mm flanges, elliptical holes Ø 8,5 x 16mm. Also possible on shaft side instead of PS / PG30 connection (at order time). Connection to ducts by insertion. This type of frame is used in case of lack of space for a standard PG30 frame. Possible on mechanism side instead of PG30 connection (at order time). Circular connection with rubber sealing ring on a rectangular damper with PG20 flange. Possible on mechanism side instead of PG30 connection (at order time). Grill, very well suited as protection grill on the end piece of a duct...

Open the catalog to page 8
VU120 - 9

Storage and handling Storage and handling As this product is a safety element, it should be stored and handled with care. Avoid: • any kind of impact or damage • contact with water • deformation of the casing It is recommended: • to unload in a dry area • not to flip or roll the product to move it • not to use the damper as a scaffold, working table, etc. • not to store smaller dampers inside larger ones Installation General points ∎  ∎  The installation must comply with the installation manual and the classification report. The installation of the shaft must comply with the classification...

Open the catalog to page 9
VU120 - 10

Installation into horizontal or vertical shaft PROMATECT L500 The product was tested and approved in: 1. Make an opening with dimensions (W+A) x (H+A) mm. A = 2 x thickness sleeve (e) + 6 mm. Fit a sleeve of the same type and thickness of the duct (thickness e) of minimum 105 mm deep in the opening. Fix the sleeve to the shaft wall. First coat the opening with Promacol S. Position the damper in the opening and fix the damper using 12 screws 05x60 (horizontal shaft) or using 10 screws 05x60 (vertical shaft). A Caution: make sure that the bolts don't exceed the sleeve's thickness! The seal...

Open the catalog to page 10
VU120 - 11

1. Make an opening with dimensions (W+80) x (H+80) mm. Fit a sleeve of the same type and thickness of the duct (thickness e) of minimum 105 mm deep in the opening. Seal the joints between uprights and cross pieces and between the lining and the wall with vegetable fibre caulking and plaster. The seal between the casing and the shaft (S) must be completely filled with fibre reinforced plaster. Support the tunnel or tighten the blade in its closed position to prevent deformation of the casing during drying of the sealing material. Fix the grill to the flange using glue type Polyflex. Check...

Open the catalog to page 11
VU120 - 12

Installation into horizontal or vertical shaft GEOTEC The product was tested and approved in: 1. In case of fastening with glue and screws: Make an opening with dimensions (W+6) x (H+6) mm. Fit a sleeve of the same type and thickness of the duct (thickness e) of minimum 105 mm deep in the opening. Fix the sleeve to the shaft wall. Mount the damper in the opening. The seal between the casing and the shaft (S) must be completely filled with fibre reinforced plaster. Support the tunnel or tighten the blade in its closed position to prevent deformation of the casing during drying of the sealing...

Open the catalog to page 12